Plan Review Notes
Plan Review Notes For Permit 07030674
Permit Number 07030674
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-28 08:06:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  