| Date |
Text |
| 2007-04-11 10:37:28 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS AND GEN/RES PERMIT |
| | APPLICATION REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATIONREQUIRED FOR GAS |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC, PLEASE |
| | REFERENCE THE ATTACHED ISOMETRIC TO THE GAS COMMENTS |
| | REFLECTING THE PROPOSED GAS SYSTEM. CORRESPONDING |
| | LENGTHS OF ALL CUT SECTIONS OF PIPE MUST BE INDICATED |
| | ON THE RESUBMITTED DRAWING. THE ONLY INDICATED PIPING |
| | MEASUREMENT IS FOR THE UNDERGROUND 1/2" PE. WHAT ARE |
| | THE CORRESPONDING LENGTHS OF THE ABOVE GROUND PIPING? |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: BOTH THE ABOVE AND UNDERGROUND PIPING MATERIALS |
| | AND SIZES MUST BE INDICATED ON THE DRAWINGS. ON THE |
| | SUBMITTED GAS CHECKLIST PIPE/TUBING SPECS. COPPER, PE, |
| | AND GALV. ARE INDICATED AS PIPING MATERIAL BEING USED |
| | BUT ON THE SUBMITTED DRAWING ONLY PE AND GALV. ARE |
| | INDICATED AS BEING USED. PLEASE CORRELATE AND CORRECT |
| | ON THE RESUBMITTAL |
| | |
| | 3. SUBMIT MANUFACTURE SPECIFICATION SHEETS FOR THE |
| | GENERATOR THAT VERIFIES THE BTU LOAD OF GENERATOR AT |
| | 100% RUNNING CAPACITY AND VERIFIES THE BTU LOAD OF |
| | 229,000 INDICATED ON THE DRAWINGS. |
| | |
| | 4. PLEASE SUBMIT TWO COPIES OF THE ABOVE GROUND LP |
| | TANK ANCHORING DETAIL FOR THE RESUBMITTAL. |
| | |
| | 5. CLEARLY SHOW THETYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |