| Date |
Text |
| 2007-04-05 09:13:52 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IT APPEARS THAT THE GARAGE WAS WAS CONVERTED TO A |
| | BEDROOM WITHOUT PERMITS OR INSPECTIONS. THE CITY HAS NO |
| | RECORDS OF A PERMIT TO ENCLOSE THE GARAGE INTO A |
| | BEDROOM AS SHOWN ON THE PLANS. THERE WAS A PERMIT TO |
| | ADD A BATH AND STORAGE TO THE GARAGE. |
| | |
| | 3)THE CHANGE FROM A GARAGE TO ADDITIONAL LIVING SPACE |
| | REQUIRES A REVIEW BY PALM BEACH COUNTY TO SEE IF ANY |
| | IMPACT FEES ARE OWED. |
| | IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 4) SPECIFY THE EXISTING LIVING SPACE OF THE HOUSE AND |
| | THE ADDITIONAL LIVING SPACE THAT WILL BE ADDED BY |
| | CONVERTING THE GARAGE. THE PROPERTY APPRAISER'S RECORDS |
| | SHOW 1166 SQFT UNDER AIR AND 264 SQFT FINISHED GARAGE. |
| | |
| | 5) SUBMIT ENERGY CALCULATIONS FOR THE ENCLOSED GARAGE |
| | PER CHAPTER 13 OF THE FBC. |
| | |
| | 6) SPECIFY THE REQUIRED WINDLOAD PRESSURES FOR THE NEW |
| | WINDOWS. |
| | |
| | 7) THE NEW FENCE WILL REQUIRE A SEPARATE PERMIT. |
| | |
| | 8) PERMITS WILL BE REQUIRED FOR THE ELECTRIC AND |
| | PLUMBING. |
| | |
| | 9) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED |
| | GRADE. |
| | CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND |
| | ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT |
| | ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY |
| | VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM) |
| | ELSEWHERE. |
| | |
| | 10) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR |
| | TERMITES. |
| | IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| | INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| | AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6 INCHES (152 MM). |
| | EXCEPTIONS: |
| | 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS |
| | THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE |
| | MASONRY FOUNDATION SIDEWALL. |
| | 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE |
| | INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH |
| | RAMPS ONLY. |
| | 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO |
| | AND GARAGE SLABS AND ENTRY AREAS. |
| | 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES, |
| | THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR |
| | FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY. |
| | 5.MASONRY VENEERS. |
| | |
| | 11) ASTM C 926 REQUIRES STUCCO APPLIED VERTICALLY TO A |
| | METAL PLASTER BASE TO BE 7/8 INCH THICK. SEE R703.6.1 |
| | |
| | 12) SPECIFY THE CONNECTORS THAT WILL BE USED ON THE NEW |
| | WOOD FRAME WALL TO RESIST LATERAL WIND LOADS. |
| | |
| | 13) SPECIFY THE EMBED DEPTH FOR THE RED HEAD FASTENERS |
| | SPECIFIED ON SHEET A1 FOR ANCHORING THE NEW WALLS TO |
| | THE SLAB. |
| | |
| | 14) SUBMIT PRODUCT APPROVALS FOR THE FOR THE NEW |
| | WINDOW, GLASS BLOCK AND STORM PANELS. |
| | |
| | 15)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 16)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |