| 2007-09-10 13:58:24 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 2} THERE ARE NO RECEPTACLES SHOWN FOR THE A/C UNITS ON |
| | THE PLAN, LOCATE SAME.106.1.1 FBC AS AMENDED. |
| | |
| | 3} THE RISER DIAGRAM HAS A METER MAIN SYMBOL WITH AN |
| | UNDERGROUND FEED TO WHAT APPEARS TO BE A PANEL, BUT |
| | THAT PIECE OF EQUIPMENT IS LABELED ?METER COMB.?. |
| | CLARIFY, SEE COMMENT #1. |
| | |
| | 4} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING |
| | AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE |
| | LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT |
| | GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE |
| | GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| | DWELLING. LOCATE SAME ON THE PLANS. |
| | |
| | 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| | SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE SAME ON |
| | PLANS. ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" |
| | 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, |
| | TO AVOID CONFUSION IN THE FIELD. IF USING DETECTORS |
| | INDICATE THE LOCATIONS OF THE SOUNDING DEVICES. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |