Plan Review Notes
Plan Review Notes For Permit 07030651
Permit Number 07030651
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-10 13:58:24 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} THERE ARE NO RECEPTACLES SHOWN FOR THE A/C UNITS ON
 THE PLAN, LOCATE SAME.106.1.1 FBC AS AMENDED.
  
 3} THE RISER DIAGRAM HAS A METER MAIN SYMBOL WITH AN
 UNDERGROUND FEED TO WHAT APPEARS TO BE A PANEL, BUT
 THAT PIECE OF EQUIPMENT IS LABELED ?METER COMB.?.
 CLARIFY, SEE COMMENT #1.
  
 4} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING. LOCATE SAME ON THE PLANS.
  
 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE SAME ON
 PLANS. ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD. IF USING DETECTORS
 INDICATE THE LOCATIONS OF THE SOUNDING DEVICES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718