| Plan Review Notes For Permit 07030651 |
| Permit Number |
07030651 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-28 16:39:30 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | | | 1} PROVIDE A LOAD CALCULATION PER 220.31, FOR THE | | | ENTIRE RESIDENCE, INCLUDE ADDED LOADS. | | | | | | 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND | | | 106.3.5.4(8) FBC. | | | | | | 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1) | | | AND 210.52 (A) (2). SEE REVIEWED SET FOR EXAMPLES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|