Plan Review Notes
Plan Review Notes For Permit 07030651
Permit Number 07030651
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-24 14:27:13DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE LEFT ELEVATION DOES NOT INDICATE THE DOOR OR ITS
 WIND PRESSURES AT THE NEW ENCLOSED STORAGE ROOM. A
 WINDOW IS SHOWN AT THIS LOCATION.
  
 4) PROVIDE A FRONT ELEVATION WHICH SHOWS THE WINDOW AND
 WIND PRESSURES AT THE ENCLOSED STORAGE ROOM.
  
 5) THE EMERGENCY EGRESS REQUIREMENTS OF THE ROOMS
 ADJACENT TO THE NEW ADDITION OR ENCLOSED CARPORT MUST
 BE MAINTAINED. INDICATE THE ROOM TYPES AND LOCATIONS OF
 THE EXISTING STRUCTURE ON THE FLOOR PLAN. SEE FBC
 R310.
  
 6) PROVIDE DETAILS OF THE FOOTINGS WHERE THE NEW CBS
 WALLS WILL BE INSTALLED TO ENCLOSE THE EXISTING
 CARPORT. PROVIDE A WALL SECTION AT THIS LOCATION. SHOW
 COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 7) THE LOCATION OF THE EXISTING WALLS SHOWN ON THE
 FOUNDATION PLAN AT THE CARPORT DO NOT MATCH THE ONES
 SHOWN ON THE FLOOR PLAN. PLEASE CORRECT.
  
 8) SPECIFY THE BOTTOM CORD LIVE LOAD FOR THE TRUSSES.
 SEE FBC RESIDENTIAL TABLE R301.5.
  
 9) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
  
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 10) ROOF SHEATHING FASTENING IS REQUIRED TO BE IN
 ACCORDANCE WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO
 2004 FBC RESIDENTIAL CODE. WOOD STRUCTURAL PANEL
 SHEATHING SHALL BE FASTENED TO ROOF FRAMING WITH 8D
 RING-SHANK NAILS AT 6 INCHES ON CENTER AT EDGES AND 6
 INCHES ON CENTER AT INTERMEDIATE FRAMING. SPACING OF
 RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN
 NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND
 SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1. REVISE THE
 NAILING SCHEDULE ON SHEET 2 AND THE NOTE ON WALL
 SECTION 1/A4 ON SHEET 4.
  
 11)THE COMPONENT AND CLADDING ZONES FOR THE HIP ROOF
 SPECIFIED ON SHEET 2 OF THE PLANS IS INCORRECT. ROOF
 ZONE 3 IS INCORRECTLY IDENTIFIED ON THE DIAGRAM. THE
 OUTSIDE CORNERS ARE ZONE 3. SEE FBC FIGURE R301.2(8).
  
 12)THE SIMPSON CATALOG INDICATES THAT THE LATERAL
 L0ADS DO NOT APPLY FOR REDUCED FASTENERS ON THE TRUSS
 CONNECTORS. PER TELEPHONE CONVERSATION WITH SIMPSON'S
 ENGINEERING DEPARTMENT THE REDUCTION CALULATIONS FOR
 UPLIFT SHOULD ONLY BE BASED ON THE NUMBER OF NAILS IN
 THE STRAP AND NOT THE SEAT OF THE HETAL CONNECTORS,
 WHICH REDUCES THE UPLIFT VALUE BY 40 PERCENT. BECAUSE
 THE LATERAL LOADS OF THE TRUSS CONNECTORS IS REQUIRED
 TO RESIST WINDLOADS, ALL OF THE NAILS SPECIFIED FOR THE
 CONNECTOR IN THE CATALOG SHOULD BE USED.
  
 13) THE DESIGN CERTIFICATION INFORMATION LISTED ON
 SHEET 3 CONTAINS SOME ERRORS. THE PROJECT IS LOCATED IN
 THE CITY OF WEST PALM BEACH, THEREFORE, THE CITY'S
 AMENDMENTS AND NOTPALM BEACH COUNTY'S ARE APPLICABLE.
 REPLACE PALM BEACH COUNTY WITH CITY OF WEST PALM BEACH.
 THE WRONG EDITION OF ASCE 7 IS SPECIFIED. REPLACE ASCE
 7-98 WITH ASCE 7-02.
  
 14) THE STRUCTURAL NOTES ON SHEET 2 SPECIFY A 2500 PSF
 SOIL BEARING CAPACITY AND GENERAL NOTE 11 ON SHEET 4
 SPECIFIES A 2000 PSF SOIL BEARING CAPACITY. PLEASE
 CORRECT.
  
 15) ON SHEET 4 GENERAL NOTE 1REFERENCES THE STANDARD
 BUILDING CODE AS AMENDED BY PALM BEACH COUNTY. PLEASE
 REVISE TO FLORIDA BUILDING CODE AS AMENDED BY THE CITY
 OF WEST PALM BEACH.
  
 16) THE TYPICAL DOOR JAMB NOTES ON SHEET 4 SPECIFIES A
 FASTENER SPACING THAT DOES NOT CORRESPOND WITH THE
 SPACING SPECIFIED IN THE OTHER BUCK FASTENING DETAILS.
  
 17)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. SEE RULE 9B-72.
  
 18) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 19) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS
 AND CONCRETE LINTELS.
  
 20) THE PRODUCT APPROVAL SUBMITTED FOR THE JELD-WEN
 DOOR IS FOR DOUBLE OUTSWING DOORS AND THE PLAN
 SPECIFIES A SINGLE OUTSWING DOOR. SUBMIT THE CORRECT
 PRODUCT APPROVAL.
  
 21) THE PRODUCT APPROVAL SUBMITTED FOR THE GAF SHINGLES
 HAS BEEN REVISED BY NOA 05-1115.11. SUBMIT THE NEW NOA
 WITH THE FL COVERSHEET.
  
 22) ALSO SEE RED MARKS ON THE PLANS FOR CORRECTIONS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  