| Plan Review Notes For Permit 07030642 |
| Permit Number |
07030642 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-05-07 11:50:12 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE 3/0 CONDUCTORS FROM THE GENERATORS 300 AMP | | | BREAKER DO NOT COMPLY WITH 310.16. THEY NEED TO BE 300 | | | MCM MINIMUM. ALSO THOSE FEEDER CONDUCTORS WOULD BE | | | REQUIRED THE ENTIRE LENGTH OF THE GENERATOR FEED TO THE | | | 200 AMP INDOOR PANEL IF THE CURRENT IS NOT LIMITED TO | | | 200 AMPS AT THE GENERATOR OR THE 300 AMP DISCONNECT | | | SHOWN OUTSIDE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|