| Plan Review Notes For Permit 07030642 |
| Permit Number |
07030642 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-28 07:37:10 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1}PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH. AS | | | FIRST MEANS OF DISCONNECT IT MUST BE SERVICE RATED, | | | CAPABLE OF DISCONNECTING ALL SOURCES OF POWER AND HAVE | | | AN AIC RATING FOR THE SERVICE. | | | | | | 2} PLEASE SUBMIT A SITE PLAN AND LOCATE ALL | | | THE SERVICE AND GENERATOR GEAR ON SAME | | | SO THAT COMPLIANCE WITH | | | 230.72(GROUPING), 225.31-39 FOR THE | | | DISCONNECTING MEANS REQUIREMENTS AND | | | 250.32 FOR GROUNDING CAN BE REVIEWED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|