| 2007-08-07 10:17:18 | DENIED 3RD TIME |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | 1. SHEET PE-1: THE RESUBMITTED SANITARY ISOMETRIC |
| | RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN OF THE |
| | UNDERGROUND SANITARY PLUMBING BEING INDICATED ON SHEET |
| | A-1.0. PLEASE REFERENCE THE SANITARY ISOMETRIC RISER |
| | DIAGRAM THAT REFLECTS THE FLOOR PLAN ATTACHED TO THESE |
| | PLUMBING COMMENTS FOR THE NEXT RESUBMITTAL. |
| | |
| | PER FBC-2004 CHAPTER 1 SECTION 106.1.1 INFORMATION ON |
| | CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| | LOCATIONS. |
| | NOTE: NOT ALL PIPE SIZES AND TRAPS ARE INDICATED ON THE |
| | RESUBMITTED SANITARY ISOMETRIC. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | |
| | END OF COMMENTS: |
| | |