| 2007-04-19 16:47:12 | |
| | |
| | DENIED |
| | |
| | |
| | 1)DRAWINGS TO COMPLY WITH THE LATEST CODE, PLACE NOTE |
| | ON PLANS THAT THEY CONFORM TO THE 2004 FLORIDA BUILDING |
| | CODE WITH 2006 REVISIONS |
| | |
| | 2)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO |
| | BUILDING PER 1603.1.4 FBC |
| | |
| | 3)PROVIDE TYPE OF CONSTRUCTION AND OCCUPANCY GROUP ON |
| | PLANS |
| | |
| | 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC*.VALUE ADJUSTED TO $359,745 WHICH |
| | INCREASES THE PERMIT FEE. BALANCE DUE IS $123.14. |
| | |
| | 5)A DESIGN PROFESSIONAL THAT IS REGISTERED TO |
| | PRACTICE UNDER CHAPTER 481 OR 471 OF |
| | THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, |
| | SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS |
| | PER 106.1 FBC 2004 |
| | |
| | 6)PLAN, ELEVATION AND DOOR, WINDOW SCHEDULE DO NOT |
| | MATCH.LIVINGROOM ELEVATION HAS 1 WINDOW SCHEDULE HAS |
| | 2 AND NO MULLION STATED FOR LIVINGROOM OR MASTER |
| | SUITE. |
| | |
| | 7)BUILDING ELEVATION TO INCLUDE MEAN ROOF HEIGHT AND |
| | ROOF PITCH. THE PITCH ON 1/D1 MAY BE CORRECT BUT DETAIL |
| | IS TYPICAL DETAIL SO IN MAY NOT BE FOR THIS PARTICULAR |
| | BUILDING. |
| | |
| | 8)SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD |
| | |
| | 9)NOA FOR PRE-CAST LINTELS IS INCORRECT SUBMITTED NOA |
| | IS FOR 4, 6 AND 12" WIDE BLOCK APPLICATIONS PROVIDE |
| | MIAMI-DADE NOA # 03-0605.05 FOR 8" LINTELS |
| | |
| | 10)GLASS BLOCK MEETS THE DESIGN PRESSURES REQUIRED |
| | BUT IS ONLY SMALL MISSILE IMPACT RATED. PER 1609.1.4 |
| | FBC GLAZING WITHIN THE FIRST 30 FEET FROM GRADE ARE |
| | REQUIRED TO MEET LARGE MISSILE IMPACT TEST REQUIREMENTS |
| | THEREFORE THESE OPENINGS WILL REQUIRE AN IMPACT |
| | PROTECTION SYSTEM. |
| | |
| | 11)PROVIDE LINTEL SCHEDULE THAT SHOW LINTELS MEET THE |
| | REQUIREMENTS OF 2104.5 FBC FOR MIN END BEARING |
| | |
| | 12)WINDOW #4 FROM SCHEDULE 48"X101" EXCEEDS THE MAX |
| | SQUARE FOOTAGE STATED IN THE PGT PRODUCT APPROVAL NOA |
| | FOR FIXED WINDOWS MAX. SQ.FT. = 32, WINDOW IS 33.66667 |
| | SQ. FT. |
| | |
| | 13)PRODUCT APPROVAL FOR HANSON ROOF TILE REQUIRES |
| | ANSWERS TO NOTE #7 IN ORDER TO CALCULATE MOMENT OF |
| | UPLIFT FOR TILE. |
| | |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| | FBC* = WEST PALM BEACH ADMINISTRATIVE |
| | AMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | |
| | BLDG PLAN REVIEW |