2007-06-12 08:56:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PER OUR CONVERSATION, PLEASE REVISE THE
 INSTALLATION SCHEDULE.AS DISCUSSED, IF YOU DESIGN TO
 A PRESSURE OF -48, YOU MUST USE THE -57 ROW.ANCHORING
 SPECIFIED IS FOR C1, BUT YOU HAVE CIRCLED C2 WALL MOUNT
 ON THE PRODUCT APPROVAL.PLEASE INDICATE ON THE
 INSTALLATION SCHEDULE WHICH CONNECTION TYPE YOU ARE
 USING.