| Plan Review Notes For Permit 07030627 |
| Permit Number |
07030627 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-03-26 13:33:08 | DENIED BY BUILDING | | | | | | 1)THE NOA FOR THE JOHNS MANVILLE BUILT-UP ROOF SYSTEM | | | SPECIFIES A MAXIMUM DESIGN PRESSURE OF -52.5 PSF FOR | | | THE SELECTED SYSTEM, WHICH IS TO LOW FOR ROOF ZONES 2 | | | AND 3. ENHANCED FASTENING IS ALLOWED IN ORDER TO | | | INCREASE THE DESIGN PRESSURES IN THESE AREAS PER | | | GENERAL LIMITATION NUMBER 7 ON PAGE 19 OF THE NOA. | | | HOWEVER, GENERAL LIMITATION NUMBER 7 REQUIRES THAT RAS | | | 117 CALCULATIONS PREPARED, SIGNED AND SEALED BY A | | | FLORIDA REGISTERED ENGINEER, ARCHITECT OR REGISTERED | | | ROOF CONSULTANT. SUBMIT SIGNED AND SEALED RAS 117 | | | CALCULATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|