| 2008-03-31 18:13:12 | ** DENIEDREVIEW ** |
| | |
| | ** REVISIONS SUBMITTED TO FIRE DATED 3/14/ AND |
| | REVISIONS SUBMIT TO ELECTRICAL DATED 3/27 |
| | |
| | 1) NOTE: PLEASE SEE ELECTRICAL RISER HAS NOW CHANGED |
| | THE GENERATOR FROM PROPANE ON-SITE FUEL TO NATURAL GAS. |
| | THIS WAS NOT LABELED AS A REVISION NOR DOES ANY OTHER |
| | ITEM ON THE RISER SHEET SHOW THIS BEING CHANGED. THE |
| | REV #4 WHICH IS NEXT TO GENERATOR WAS ALREADY SUBMITTED |
| | ON PREVIOUS REVISIONS AND DOES NOT CONTAIN THE SAME |
| | WORDING. |
| | THE PREVIOUS CLEARLY INDICATED *PROPANE/ON-SITE FUEL*. |
| | IF THIS GENERATOR IS GOING TO BE *OPTIONAL STAND-BY* |
| | THEN IT IS NOT REQUIRED TO CONTAIN ON-SITE FUEL. ALL |
| | EMERGENCY AND EXIT LIGHTS SHALL CONTAIN BATTERY BACK UP |
| | POWER SOURCE OR OTHER ACCEPTABLE MEANS. |
| | PLEASE SEE LS CODE 101 7.8.2.1, 7.8.2.2 ALONG WITH NEC |
| | 700.12F., 700.12B3, 701.11B3 |
| | PLEASE ADJUST. |
| | |
| | ** SHEETS WHICH CONTAINED STAMPED FROM FIRE REVIEW HAVE |
| | BEEN VOIDED. |
| | MUST RE-SUBMITTED OTHER SHEETS STAMPED BY FIRE MARSHAL |
| | WHEN RESUBMITTING CORRECTED REVISIONS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |