| Date |
Text |
| 2007-06-22 18:32:46 | *** UNSAT2ND REVIEW *** |
| | |
| | ** PLEASE SEE THERE ARE STILL SOME NOTES FROM PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE: PLEASE SEE MOST OF THE CODES WERE ADDRESSED |
| | AND ADJUSTED ON PLANS HOWEVER PLEASE SEE SHEET FA WHICH |
| | STILL INDICATES THE SFBC. |
| | ** PLEASE SEE COMMENT WITH RESPECT TO FA SYSTEMS. ** |
| | SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER |
| | PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT THIS NOTE. |
| | ** PLEASE SEE COMMENTS IN REVIEW WITH RESPECT TO SOME |
| | AREAS OF PLANS WHICH REFLECT THE SOUTH FLORIDA BUILDING |
| | CODE SFBC. THIS HAS NOT BEEN IN EFFECT SINCE 3/1/02. |
| | |
| | 2) NOTE:PLEASE SEE MISSING INFORMATION ON TITLE |
| | BLOCKS FOR L AND IRR SHEETS. PLEASE SEE MISSING THE |
| | PRINTED NAME AND PRINTED LICENSE NUMBER OF THE DESIGNER |
| | OF RECORD. PLEASE ALSO SEE THE SEAL IS NOT VALID UNDER |
| | THE FAC 61G1-16.002 |
| | 61G1-16.004 |
| | |
| | 3) NOTE:PLEASE SEE THE STAIRS AS PREVIOUSLY NOTED |
| | WILL BE REQUIRED TO HAVE BATTERY BACK UP FIXTURES OF |
| | SOME TYPE FOR MINIMUM LIGHTING LEVELS. PLEASE KNOW THE |
| | SINGLE TRIPPING OF THE OCP WILL PLACE THE EGRESS OF |
| | STAIRS IN DARKNESS. PLEASE PROVIDE FURTHER INFORMATION |
| | ON START OF GENERATOR. IF THE GEN UNIT ONLY STARTS |
| | UNDER POWER FAILURE OF MAIN, THEN THE BATTERY BACK UP |
| | LIGHTS ARE REQUIRED. IF THE UNIT START UP IS TRIGGERED |
| | BY THE FAILURES OF THE EMERGENCY DISCONNECT THEN THE |
| | MULTI-CIRCUITS WILL BE OK. PLEASE SEE THE NOTE FROM |
| | PREVIOUS REVIEW BELOW WILL REMAIN. PLEASE CALL TO GO |
| | OVER. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE PROVIDE PHOTO-METRICS FOR STAIR TOWERS WHICH |
| | INDICATE THE MINIMUM OF 10FT CANDLES UNDER NORMAL AND |
| | 1FT CANDLE UNDER EMERGENCY CONDITIONS. |
| | PLEASE ALSO SEE THE FIXTURES AS SHOWN DO NOT PROVIDE |
| | ENOUGH INFORMATION FOR TYPE OF FIXTURE. PLEASE SEE A |
| | BATTERY BACK UP FIXTURE WILL BE REQUIRED FOR THE |
| | MINIMUM LEVELS FOR EGRESS UNDER EMERGENCY CONDITIONS. |
| | PLEASE SEE LS 101 7.8, 7.9, 7.8.1.3, 7.9.2.2. PLEASE |
| | SEE THAT THE FAILING OF A SINGLE DEVICE, OCP, SWITCH |
| | ETC SHALL NOT LEAVE ANY ONE EGRESS AREA IN TOTAL |
| | DARKNESS. |
| | PLEASE INDICATE ON PLANS IF THE EXISTING GENERATOR |
| | ROOM, FIRE PUMP ROOM AND MAIN ELECTRICAL ROOM CONTAIN |
| | EMERGENCY BATTERY BACK UP FIXTURES OF SOME TYPE. IF |
| | EXISTING PLEASE SHOW, IF NOT, PLEASE KNOW THESE WILL BE |
| | REQUIRED. |
| | NEC 700.12E, 700.16, NFPA-101101 7.8, 7.9, NFPA-110 |
| | 7.3.1 |
| | |
| | 4) NOTE: THIS IS THE SAME NOTE. PLEASE SEE THE MINIMUM |
| | LEVELS ARE REQUIRED ON PLANS FOR THE SYSTEM AS SHOWN. |
| | THIS IS REQUIRED UNDER THE FBC FOR ADA COMPLIANCE WHICH |
| | IS MORE RESTRICTIVE THAN NFPA-72. |
| | PLEASE SEE PLANS DO INDICATE A FA SYSTEM. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE THE FA SHEETS AS THESE INDICATE THE HORN |
| | AND STROBE DEVICES FROM THE SFBC AND OTHER CODES WHICH |
| | ARE NO LONGER IN EFFECT. |
| | PLEASE SEE THE MINIMUM LEVELS FOR THESE DEVICES SHALL |
| | BE STATED PER FBC 2004 11-4.28.1,.2 AND .3(4). |
| | |
| | 5) NOTE: THIS IS THE SAME NOTE: THE LPD WHICH ARE SHOWN |
| | ON PLANS WERE VIEWED, HOWEVER THE NEED OF A FIXTURE |
| | LEGEND WHICH COORDINATES WITH THE IDENTIFICATION OF |
| | PLANS IS NEEDED. PLEASE SEE SOME FIXTURES ARE |
| | IDENTIFIED ON PLANS ARE NOT FOUND ON THE *LEGEND* AS |
| | SUBMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT A COMPLETE FIXTURE LEGEND OF ALL |
| | FIXTURES AND CORRELATE WITH PLANS. |
| | PLEASE ALSO SEE THE 2004 FBC W/ 2006 REVISIONS TO |
| | CHAPTER 13 FOR THE POWER ALLOWANCES PERMITTED AND |
| | PERFORMANCE CALCULATIONS PER 13-415.2. |
| | PLEASE PROVIDE WORST CASE VOLTAGE DROP PER |
| | 13-413.1ABC.1 FOR BRANCH CIRCUITS INSTALLED AS NEW. |
| | PLEASE SEE ALL OF CHAPTER 13 FOR LIGHTING AND |
| | CONTROLS. |
| | PLEASE SEE THAT NOT ENOUGH INFORMATION IS PROVIDED FOR |
| | LIGHTING CONTROLS, PANELS, SCHEDULING ETC. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: THIS COULD NOT BE LOCATED IN PACKAGE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT WIND LOADS FOR ROOF TOP LIGHTING POLES |
| | SHOWING THE MINIMUM LOADS FOR POLES AND FIXTURES WITH |
| | THEIR EFFECTIVE PROJECTED AREAS (EFA) TO MEET THE |
| | MINIMUM OF THE FBC 140 MPH WIND LOADS. |
| | THIS INFORMATION WILL BE REVIEWED BY THE STRUCTURAL |
| | PLANS EXAMINER. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE THE GENERATOR IS NOW BEING SHOWN AS |
| | EXISTING AND IS NOW SHOWN AS NATURAL GAS, HOWEVER AS |
| | THE LOADS HAVE BEEN INCREASED THE AMOUNT OF ON-SITE |
| | FUEL NEEDS TO BE VERIFIED. PLEASE SEE THE MINIMUM FUEL |
| | REQUIRED AS STATED IN PREVIOUS REVIEW STILL NEEDS TO BE |
| | SHOWN AND IDENTIFIED ON PLANS. PLEASE SEE AS THERE ARE |
| | SEVERAL ITEMS WHICH IS NEEDED FOR ALL TRADES, THERE MAY |
| | BE NEW COMMENTS FROM OTHER TRADES IF NEW LARGER ON-SITE |
| | TANK IS NEEDED. ** AS STATED IN THE CODE, THE LEGALLY |
| | REQUIRED OR EMERGENCY SYSTEMS SHALL NOT RELY ON |
| | UTILITY. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THAT IT IS UNCLEAR WHAT IS BEING DONE WITH |
| | THE GENERATOR. IS THIS UNIT GOING TO BE NEW OR EXISTING |
| | TO REMAIN? |
| | PLEASE SEE THE RISER SEEMS TO SHOW UNIT AS GAS AND |
| | DIESEL? PLEASE CLARIFY IS THIS NATURAL GAS? OR |
| | GASOLINE? PLEASE VERIFY. |
| | PLEASE SUBMIT THE FUEL CONSUMPTION RATE FOR THE |
| | GENERATOR AT FULL LOAD INCLUDING THE LOAD OF THE FIRE |
| | PUMP AT 100%. |
| | PLEASE SEE NFPA-20 9.6.2.2. |
| | PLEASE SEE 701.11B3 |
| | |
| | 8) NOTE: THIS NOTE REMAINS AS NO LOCKED ROTOR CURRENT |
| | INFORMATION COULD BE LOCATED FOR THE MAIN FIRE PUMP |
| | CONTROLLER. PLEASE SEE THE RISER WAS REVISED TO SHOW A |
| | 1200AMP BREAKER WHICH DOES NOT SEEM TO BE CORRECT. |
| | PLEASE SEE THE REQUIRED OCP ON THE MAG-TRIP IS |
| | TYPICALLY THE SIZE OF THE BREAKER HOWEVER ONLY A |
| | MAG-TRIP WITH SETTINGS. THIS IS NOT ACTUALLY GOING TO |
| | BE A 1200AMP BREAKER? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE INFORMATION IS PROVIDED ON PLANS FOR |
| | THE LOCKED ROTOR OVER CURRENT PROTECTION ON THE PRIMARY |
| | SIDE OF THE FIRE PUMP. |
| | PLEASE SEE 695.4B1, NFPA-20 9.3.2.2.3.2 |
| | PLEASE ALSO SEE OTHER SECTIONS UNDER 9.3 FOR THE FPC. |
| | |
| | 9) NOTE: PLEASE SEE THE ADDRESS FOR THE PROJECT IS |
| | REQUIRED TO BE ON PLANS. PLEASE SEE THE ADDRESS OF 505 |
| | BANYAN BLVD SHOULD BE ON PLANS. PLEASE KNOW THAT ANY |
| | SHEETS WHICH MAY ALREADY BE PASSED AND CONTAINS CITY |
| | STAMPS MAY *PRINT, STAMP OR BY OTHER PERMANENT MEANS* |
| | THE ADDRESS ON TITLE BLOCKS. |
| | FAC 61G1-16.004 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| 2007-06-21 06:59:45 | 2007-02-21 06:59:45 |
| | REVIEW IN PROGRESS |
| 2007-06-20 21:07:42 | 2007-06-20 21:07:42 |
| | IN ELEC FOR REVIEW. |