| 2007-06-28 16:50:46 | BUILDING PLAN REVIEW |
| | PERMIT: 07030592 |
| | ADD: 505 BANYAN BLVD |
| | CONT: THE WEITZ CO |
| | TEL: (561)722-8837 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) 2ND REQUEST, FOR THE THRESHOLD INSPECTOR TO SIGN AN |
| | ORIGINAL AGREEMENT, NOT A PHOT-COPY, HAROLD PISKURA HAS |
| | PUT A LOCK ON THE PERMIT UNTIL THIS MATTER IS RESOLVED. |
| | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. CONTACT HAROLD PISKURA MANAGER |
| | OF THE SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY |
| | BE ISSUED. |
| | |
| | 4-6) COMPLIED. |
| | |
| | 7) PARTIALLY COMPLIED, FL BLD CODE 1609.1.4: |
| | COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD |
| | OR RESIDENT INSPECTOR) OF PRODUCT TESTING REPORTS |
| | ,I(NCOMPLETE) REPORTS ARE AS FOLLOWS: |
| | ROOFING ASSEMBLIES, JOHN MANVILLE MODIFIED BITUMEN |
| | OVER CONCRETE , |
| | THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE |
| | FOLLOW ITEMS: |
| | ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. |
| | |
| | _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE |
| | USED. |
| | |
| | _XX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE |
| | _2&3__ . |
| | |
| | _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7, |
| | SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THEBUILDING OFFICIAL, A |
| | REVISED |
| | FASTENER SPACING, PREPARED , SIGNED AND SEALED BY A |
| | FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| | SUBMITTED. |
| | |
| | ___THE SYSTEM PROVIDED INDICATESLIMITATION# 9, NO |
| | ENHANCEDFASTENING ALLOWED. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) SECOND REQUEST," JOHN MANVILLE MODIFIED BITUMEN" |
| | PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 10-11) COMPLIED. |
| | |
| | 12) NEW COMMENT, SUBMITTAL FOR ALUMINUM LIGHT POLE FOR |
| | TOP OF ROOF DECK DESIGN BY HAPCO ALUMINUM LIGHT POLES |
| | DESIGNED TO THE ASCE 7-98 |
| | NOT THE CURRENT ASCE 7-02. PLEASE SEE SUBMITTALS, ONLY |
| | TWO SEALED DOCUMENTS WERE LOCATED, REQUIRES THREE. |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |