| 2007-05-03 09:25:18 | 1. IT HAS BEEN DECLARED ON THE PLANS, PAGE LS1.0.0 THAT |
| | THE BUILDING IS A MIXED OCCUPANCY BUILDING INSTEAD OF |
| | JUST AN OPEN PARKING GARAGE. |
| | |
| | 2. NFPA 88A, THE STANDARTD FOR PARKING STRUCTURES |
| | DEFINES A PARKING STRUCTURE AS "A BUILDING, STRUCTURE, |
| | OR PORTION THEREOF USED FOR THE PARKING, STORAGE, OR |
| | BOTH OF MOTOR VEHICLES". |
| | |
| | 3. THIS STANDARD FURTHER REQUIRES THAT INTERNAL AREAS |
| | NOT USED FOR PARKING SHALL BE PROVIDED WITH SMOKE |
| | RESISTANT WALLS WHICH DOES NOT APPEAR TO BE DECLARED ON |
| | THE PLANS. |
| | |
| | 4. THE FLORIDA FIRE PREVENTION CODE REQUIRES THAT |
| | "ADDITIONS SHALL CONFORM TO THE PROVISIONS OF NEW |
| | CONSTRUCTION". |
| | |
| | 5. THE MEANS OF EGRESS CHART ON PAGE LS1.0.0 APPEARS TO |
| | BE INCORRECT. THE TOTAL EGRESS CAPACITY OF 972 PERSONS |
| | APPEARS TO BE INCORRECT. PLEASE VERIFY INFORMATION ON |
| | THE PLANS. |
| | |
| | 6. NOTE 16 ON PAGE LS1.0.0 IS INCORRECT. ALL CUTTING |
| | AND WELDING OPERATIONS TO COMPLY WITH NFPA 51B. |
| | |
| | 7. NFPA 88A, FURTHER DEFINES AN OPEN PARKING STRUCTURE |
| | "IS A PARKING STRUCTURE THAT EACH PARKING LEVEL HAS |
| | WALL OPENINGS OPEN TO THE ATMOSPHERE FOR AN AREA NOT |
| | LESS THAN 0.4 FOR EACH LINEAR METER (1.4 FT.2 FOR EACH |
| | LINEAR FOOT ) OF ITS EXTERIOR PERIMETER. SUCH OPENINGS |
| | ARE DISTRIBUTED OVER 40 PERCENT OF THE BUILDING |
| | PERIMETER OR UNIFORMLY OVER TWO OPPOSING SIDES. |
| | INTERIOR WALL LINES AND COLUMN LINES ARE AT LEAST 20 |
| | PERCENT OPEN, WITH OPENINGS DISTRIBUTED TO PROVIDE |
| | VENTIALTION". |
| | |
| | 8. TACTILE SIGNAGE REQUIRED REQUIRED AT ALL EXIT |
| | DOORS. |
| | |
| | 9. PLEASE DECLARE THE USES OF ALL ROOMS WITHIN THE |
| | GARAGE OFFICE AREA ON PAGE A2.1.0. |
| | |
| | 10. PLEASE EXPLAIN PURPOSE OF JERSEY BARRIERS |
| | ILLUSTRATED ON THE PLANS. WHAT IMPACT IF ANY WILL THEY |
| | HAVE ON EXITING. |
| | |
| | 11. STAIRWELL IDENTIFICATION SIGNS WILL BE REQUIRED. |
| | THESE SIGNS SHALL INDICATE FLOOR LLEVEL, STAIR |
| | IDENTITY, TERMINUS TOP AND BOTTOM. |
| | |
| | 12. DOES THE EXISTING BUILDING HAVE THE ADDRESS AFFIXED |
| | TO IT. ON ONE ELEVATION IT APPEARS THAT THE ADDRESS |
| | EXISTS. |
| | |
| | 13. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR THE NEW CABLE RAILING SYSTEM BEING PROPOSED AS |
| | SHOWN ON PAGE A2..5.1. |
| | |
| | 14. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR THE NEW GUARDRAILS TO BE INSTALLED SHOWN ON PAGE |
| | A.2.5.1. |
| | |
| | 15. SEPARATE PLANS AND PERMIT REQUIRED FOR NEW FIRE |
| | ALARM CONTROL PABEL NOTED ON PAGE E1.00. |
| | |
| | 16. DEMOLITION OF EXISTING ELECTRICAL WIRING, FIXTURES, |
| | AND APPURTENANT EQUIPMENT SHALL COMPLY WITH NFPA 70 AND |
| | NFPA 70E. |
| | |
| | 17. NOTE 19 ON PAGE FP1.00 SHALL INCLUDE DOCUMENTATION |
| | OF INSPECTIONS TO THE BUREAU OF FIRE PREVENTION. |
| | |
| | 18. SUBMIT MORE INFORMATION ON NEW FIRE PUMP AND |
| | AUTOMATIC TRANSFER SWITCH. |
| | |
| | 19. PLEASE PROVIDE MORE DETAILS ON PRESSURE REDUCING |
| | VALVES. WILL THEY BE FACTORY OR FIELD ADJUSTABLE. |
| | |
| | 20. ON PAGE FP2.60 THE FIRE DEPARTMENT OUTLET |
| | CONNECTIONS SHOULD BE CHANGED TO ROOF MANIFOLDS. |
| | |
| | 21. ALL EMPLOYEES NEED TO BE TRAINED AND DOCUMENTED IN |
| | THE USE OF PORTABLE FIRE EQUIPMENT AND THE TRANSMISSION |
| | OF ALARMS. |
| | |
| | 22. NFPA 88A THE STANDARD FOR PARKING STRUCTURES DOES |
| | NOT REQUIRE AUTOMATIC FIRE SPRINKLER SYSTEMS IN OPEN |
| | PARKING STRUCTURES. OTHER CODES MAY REQUIRE BE REQUIRE |
| | FIRE SPRINKLER PROTECTION. |
| | |