| 2007-03-23 19:07:13 | ****** UNSAT ****** |
| | |
| | ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOTYET |
| | BEEN SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE NEXT REVIEW. |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | 2003 NFPA-20 |
| | 2002 NFPA-110 |
| | ** SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER |
| | PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT THIS NOTE. |
| | ** PLEASE SEE COMMENTS IN REVIEW WITH RESPECT TO SOME |
| | AREAS OF PLANS WHICH REFLECT THE SOUTH FLORIDA BUILDING |
| | CODE SFBC. THIS HAS NOT BEEN IN EFFECT SINCE 3/1/02. |
| | |
| | 2) NOTE: PLEASE SEE THE *S* SHEETS WHICH IS MISSING |
| | INFORMATION ON TITLE BLOCKS FOR FIRM. PLEASE SEE |
| | MISSING THE CERTIFICATE OF AUTHORIZATION NUMBER AS |
| | REQUIRED PER FAC 61G15-23.002, AND FS 471.023. THIS IS |
| | REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE TITLE BLOCK FOR GARTEK ENGINEERING |
| | IS SMALL AND INFORMATION IS NOT CLEAR. PLEASE SEE TITLE |
| | BLOCK AND ADJUST FONT/PRINTING. |
| | |
| | 4) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR STAIR TOWERS |
| | WHICH INDICATE THE MINIMUM OF 10FT CANDLES UNDER NORMAL |
| | AND 1FT CANDLE UNDER EMERGENCY CONDITIONS. |
| | PLEASE ALSO SEE THE FIXTURES AS SHOWN DO NOT PROVIDE |
| | ENOUGH INFORMATION FOR TYPE OF FIXTURE. PLEASE SEE A |
| | BATTERY BACK UP FIXTURE WILL BE REQUIRED FOR THE |
| | MINIMUM LEVELS FOR EGRESS UNDER EMERGENCY CONDITIONS. |
| | PLEASE SEE LS 101 7.8, 7.9, 7.8.1.3, 7.9.2.2. PLEASE |
| | SEE THAT THE FAILING OF A SINGLE DEVICE, OCP, SWITCH |
| | ETC SHALL NOT LEAVE ANY ONE EGRESS AREA IN TOTAL |
| | DARKNESS. |
| | PLEASE INDICATE ON PLANS IF THE EXISTING GENERATOR |
| | ROOM, FIRE PUMP ROOM AND MAIN ELECTRICAL ROOM CONTAIN |
| | EMERGENCY BATTERY BACK UP FIXTURES OF SOME TYPE. IF |
| | EXISTING PLEASE SHOW, IF NOT, PLEASE KNOW THESE WILL BE |
| | REQUIRED. |
| | NEC 700.12E, 700.16, NFPA-101101 7.8, 7.9, NFPA-110 |
| | 7.3.1 |
| | |
| | 5) NOTE: PLEASE SEE THE FA SHEETS AS THESE INDICATE THE |
| | HORN AND STROBE DEVICES FROM THE SFBC AND OTHER CODES |
| | WHICH ARE NO LONGER IN EFFECT. |
| | PLEASE SEE THE MINIMUM LEVELS FOR THESE DEVICES SHALL |
| | BE STATED PER FBC 2004 11-4.28.1,.2 AND .3(4). |
| | |
| | 6) NOTE: PLEASE SEE THE *CODED NOTES* FOR THE PARKING |
| | BOOTHS DO NOT PROVIDE THE MINIMUM CIRCUITING FOR THE |
| | NEW ELECTRICAL WHICH IS BEING INSTALLED AT BOOTHS. DO |
| | THEY INCREASE IN LOAD? ARE THESE GOING TO BE NEW UNITS |
| | WHICH WILL CONTAIN ALL NEW ELECTRICAL AND PANELS? |
| | PLEASE PROVIDE MORE INFORMATION. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SUBMIT A COMPLETE FIXTURE LEGEND OF ALL |
| | FIXTURES AND CORRELATE WITH PLANS. |
| | PLEASE ALSO SEE THE 2004 FBC W/ 2006 REVISIONS TO |
| | CHAPTER 13 FOR THE POWER ALLOWANCES PERMITTED AND |
| | PERFORMANCE CALCULATIONS PER 13-415.2. |
| | PLEASE PROVIDE WORST CASE VOLTAGE DROP PER |
| | 13-413.1ABC.1 FOR BRANCH CIRCUITS INSTALLED AS NEW. |
| | PLEASE SEE ALL OF CHAPTER 13 FOR LIGHTING AND |
| | CONTROLS. |
| | PLEASE SEE THAT NOT ENOUGH INFORMATION IS PROVIDED FOR |
| | LIGHTING CONTROLS, PANELS, SCHEDULING ETC. |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE SUBMIT WIND LOADS FOR ROOF TOP LIGHTING |
| | POLES SHOWING THE MINIMUM LOADS FOR POLES AND FIXTURES |
| | WITH THEIR EFFECTIVE PROJECTED AREAS (EFA) TO MEET THE |
| | MINIMUM OF THE FBC 140 MPH WIND LOADS. |
| | THIS INFORMATION WILL BE REVIEWED BY THE STRUCTURAL |
| | PLANS EXAMINER. |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURE'S SPECS/CUT |
| | SHEETS FOR ALL NEW EQUIPMENT BEING INSTALLED FOR THE |
| | GENERATOR, FIRE PUMP, FIRE PUMP CONTROLLER, AND ATS(S) |
| | . |
| | PLEASE SEE THERE ARE SEVERAL ITEMS WHICH NEED TO BE |
| | REVIEWED FOR CODE COMPLIANCE WHICH CAN NOT BE DONE AT |
| | THIS TIME. |
| | PLEASE ALSO BE SURE ALL INFORMATION SUBMITTED CONTAINS |
| | LISTINGS FROM ANRTL. |
| | 110.3, 90.7. |
| | |
| | 10) NOTE: PLEASE PROVIDE NOTES ON RISER FOR SIGNAGE AS |
| | REQUIRED PER 230.2E, 700.8, 701.9 ETC. |
| | |
| | 11) NOTE: PLEASE SEE THAT IT IS UNCLEAR WHAT IS BEING |
| | DONE WITH THE GENERATOR. IS THIS UNIT GOING TO BE NEW |
| | OR EXISTING TO REMAIN? |
| | PLEASE SEE THE RISER SEEMS TO SHOW UNIT AS GAS AND |
| | DIESEL? PLEASE CLARIFY IS THIS NATURAL GAS? OR |
| | GASOLINE? PLEASE VERIFY. |
| | PLEASE SUBMIT THE FUEL CONSUMPTION RATE FOR THE |
| | GENERATOR AT FULL LOAD INCLUDING THE LOAD OF THE FIRE |
| | PUMP AT 100%. |
| | PLEASE SEE NFPA-20 9.6.2.2. |
| | PLEASE SEE 701.11B3 |
| | |
| | 12) NOTE: PLEASE SUBMIT ONLY ONE ELECTRICAL RISER WHICH |
| | WILL BE ON THE PERMITTED RECORD SET OF PLANS. IF THE |
| | OTHER OPTION (1 OR 2) IS DONE INSTEAD THEN REVISED |
| | PLANS WILL BE REQUIRED THAT TIME. THE RECORD SET OF |
| | PLANS MUST CONTAIN ONE OPTION. |
| | PLEASE KNOW THE REVIEW WILL BE DONE ON THE ONE |
| | SUBMITTED. |
| | |
| | 13) NOTE: PLEASE SEE RISER AS IT APPEARS TO SHOW THE |
| | SERVICE ENTRANCE CONDUCTORS BEING RUN OVER HEAD TO THE |
| | FIRE PUMP/FPC. |
| | PLEASE SEE NFPA-70 695.6A AS THESE WILL BE REQUIRE DOT |
| | BE RUN OVER HEAD IF THIS IS THE CASE. |
| | PLEASE ALSO SEE NFPA-20 9.3.1* |
| | |
| | 14) NOTE: PLEASE BE SURE INFORMATION IS PROVIDED ON |
| | PLANS FOR THE LOCKED ROTOR OVER CURRENT PROTECTION ON |
| | THE PRIMARY SIDE OF THE FIRE PUMP. |
| | PLEASE SEE 695.4B1, NFPA-20 9.3.2.2.3.2 |
| | PLEASE ALSO SEE OTHER SECTIONS UNDER 9.3 FOR THE FPC. |
| | |
| | 15) NOTE: PLEASE SEE THE CONDUCTORS TO THE FPC FROM FPL |
| | AS THESE ARE NOT SHOWING A NEUTRAL CONDUCTOR TO THE |
| | FIRST MEANS OF DISCONNECT WHICH IS REQUIRED. THIS |
| | CONDUCTOR IS REQUIRED TO TERMINATE IN THIS FPC. PLEASE |
| | ALSO KNOW THAT THERE MAY VERY WELL BE THE NEED FOR THE |
| | NEUTRAL IN THE FPC. THE MANUFACTURE MAY REQUIRE FOR |
| | CONTROLS. |
| | PLEASE SEE THAT THE GENERATOR IS BEING NOTED AS A |
| | SEPARATELY DERIVED SYSTEM AS REQUIRED, PLEASE VERIFY IF |
| | THE NEUTRAL WILL BEBROUGHT FROM THE GENERATOR AS IF |
| | THIS IS A SD GENERATOR THEN THIS FPC WILL CONTAIN A |
| | FOUR POLE ATS. |
| | PLEASE SEE THE FOLLOWING COMMENT. |
| | PLEASE SEE RISER IS CURRENTLY SHOWING *EQUIPMENT |
| | GROUNDING CONDUCTOR* FROM THE FPL TRANSFORMER ETC. |
| | PLEASE SEE 250.6 FOR OBJECTIONABLE CURRENTS AS THE |
| | NEUTRAL IS REQUIRED TO BE BONDED AT THE FIRST MEANS OF |
| | DISCONNECT. 250.24. |
| | 250.30, 250.20 ETC. |
| | PLEASE SEE THE FPC SEEMS TO SHOW A GROUNDING ELECTRODE |
| | BY ITSELF WITHOUT ANY CONNECTIONTO A MINIMUM |
| | SYSTEM(S) PER 250.50 OR BONDING TO THE OTHER SERVICES? |
| | PLEASE VERIFY THIS. |
| | 250.92, 250.94, 250.66 |
| | PLEASE PROVIDE MORE INFORMATION. |
| | FBC 106.1.2 |
| | |
| | 16) NOTE: PLEASE SEE ALTHOUGH GF PROTECTION IS NOT |
| | REQUIRED ON THE EMERGENCY SIDE OF THE EMERGENCY SYSTEM |
| | AND LEGALLY REQUIRED SYSTEMS, PROPER GROUND FAULT |
| | SENSING IS REQUIRED. |
| | PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL |
| | CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING |
| | CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND |
| | THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY |
| | GROUNDED TO ACHIEVE GROUND-FAULT SENSING. |
| | PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM *ASCO* |
| | WHITE PAPER: WHERE GROUND FAULT PROTECTION IS TRIGGERED |
| | BY THE CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED, |
| | SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT |
| | SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE |
| | SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND |
| | FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE |
| | DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND |
| | THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID |
| | CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT |
| | WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE |
| | MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT |
| | DISCONNECT THE ARCING FAULT FROM THE GENERATOR. |
| | COORDINATION IS THUS LOST." |
| | PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL OTHER |
| | MANUFACTURES ALSO AND THE CODE PLEASE BE SURE THE |
| | MANUFACTURES SPECS TO BE SUBMITTED ARE INDEED 4POLE ATS |
| | DEVICES AS NOTED FOR EACH RISER MENTIONS. |
| | PLEASE VERIFY THE FPC/ATS. |
| | PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE |
| | REQUIRED TO BE REVISED. |
| | PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95, |
| | 700.7D, 700.26 |
| | |
| | 17) NOTE: PLEASE CORRELATE PLANS AS THE ELECTRICAL |
| | PLANS INDICATE A 150HP 480V FIRE PUMP AND THE FIRE |
| | PROTECTION SHEETS INDICATE A 125HP 480V PUMP. PLEASE |
| | KNOW AT THIS TIME REVIEW OF THE RISER CONDUCTORS CAN |
| | NOT BE DONE AS IT IS NOT KNOWN WHICH ONE IS BEING |
| | INSTALLED. |
| | FBC 106.1.2 |
| | |
| | 18) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS AT 125%. |
| | PLEASE INCLUDE LOAD CALCULATIONS FOR INCREASED LOADS IN |
| | A LOAD SUMMARY. |
| | 215.5,215.3, 230.42. AND 220. |
| | FBC 106.3.5.1.2 |
| | |
| | 19) NOTE: PLEASE SEE OPTION #2 AS IT STILL INDICATES |
| | 400AMP OCP ON THE 400AMP FEEDERS TO THE 200AMP ATS?? |
| | AND 200AMP DISCONNECT ETC. |
| | PLEASE VERIFY AND COORDINATE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |