| 2007-04-11 16:12:55 | BUILDING PLAN REVIEW |
| | PERMIT: 07030592 |
| | ADD: 505 BANYAN BLVD |
| | CONT: THE WEITZ CO |
| | TEL: (561)722-8837 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| | OF A BUILDING PERMIT FOR THE |
| | CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURL INSPECTION |
| | PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE |
| | BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 3)WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 4)W.P.B. AMENDMENT 105.13.4.4 ALL |
| | PLANS FOR THE BUILDING WHICH ARE |
| | REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CON- |
| | TAIN A STATEMENT THAT, TO THE BEST OF |
| | THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, |
| | THE PLANS AND SPECIFICATIONS COMPLY WITH |
| | THE APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 5) SHEET LS!.0.0 |
| | |
| | 5A) APPLICABLE CODES PLANS SUBMITTED AFTER DEC.8/ 2006 |
| | SHALL REVIEWED UNDER THE 2004 BASE FBC WITH 2006 |
| | AMENDMENTS. |
| | |
| | 5B) BUILDING TYPE & FIRE RESISTANCE, NOTE # 1 USES |
| | TABLE 600 AS A REFRENCE, THIS IS FROM THE FBC 2001 |
| | CODE, PLEASE CORRECT. |
| | |
| | 5C) BUILDING TYPE & FIRE RESISTANCE, NOTE # 3, USES A |
| | CODE SECTION TABLE 705.2.1 IN REFRENCE TO SHAFTS, THIS |
| | ALSO IS A REFRENCE TO THE 2001 FBC BASE CODE, PLEASE |
| | CORRECT. |
| | |
| | 5D)PLANS INDICATE THE OPEN AREA CALCULATIONS LISTED |
| | UNDER 406.3.3.1.PLEASE PROVIDE THE INTERIOR WALL PER |
| | CENTAGES OF OPEN AREAS WITH UNIFORMLY DISTRIBUTED |
| | OPENINGS. |
| | |
| | 5E) OCCUPANCY CLASSIFICATION: PLANS INDICATE A MIXED |
| | USE BUILDING, S2, OFFICE AND INDUSTRIAL USAGE. |
| | PLANS ALSO INDICATE BELOW THE AREA OF REFUGE THIS |
| | BUILDING IS NOT FIRE SPRINKLERED! |
| | 2004 EXISTING BUILDING CODE CHAPTER NINE |
| | ADDITIONS 901.2 CREATION OREXTENTION OF |
| | NONCONFORMITY. AN ADDITION SHALL NOT CREATE OR EXTEND |
| | ANY NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE |
| | ADDITION IS BEING MADE WITH |
| | REGARDS TO ACCESSIBILITY, STRUCTURAL STRENGTH, |
| | FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF |
| | MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS. |
| | |
| | LS1.0.0 CLEARLY INDICATES THIS IS A MIXED USE |
| | BUILDING AND NOT ONLY TO BE USED FOR S-2 OPEN AIR |
| | PARKING. SINCE THIS IS A MIXED USE BUILDING OVER THREE |
| | STORIES THE EXEMPTION FOUND UNDER 903.6(2) ELIMINATING |
| | THE FIRE SPRINKLERS NO |
| | LONGER STANDS. |
| | SINGLE USE 406.3.5.1 |
| | WHEN THE OPEN PARKING GARAGE IS USED EXCLUSIVELY |
| | FOR THE PARKING OR STORAGE OF PRIVATE MOTOR VEHICLES, |
| | WITH NO OTHER USES IN THE BUILDING, THE AREA AND HEIGHT |
| | SHALL BE PERMITTED TO COMPLY WITH TABLE 406.3.5 , ALONG |
| | WITH |
| | INCREASES ALLOWED BY SECTION 406.3.6 . |
| | EXCEPTION: THE GRADE-LEVEL TIER IS PERMITTED TO |
| | CONTAIN AN OFFICE, WAITING AND TOILET ROOMS HAVING A |
| | TOTAL COMBINED AREA OF NOT MORE THAN 1,000 SQUARE FEET |
| | (93 M 2 ). SUCH AREA NEED NOT BE SEPARATED FROM THE |
| | OPEN PARKING |
| | GARAGE. |
| | THE OFFICE AREA ON THE FIRST FLOOR IS 1,425 SQ |
| | FT. |
| | 903.6.1 |
| | ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN |
| | HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC |
| | SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION |
| | 903.1 . |
| | EXCEPTIONS: |
| | (2)A STAND-ALONE PARKING GARAGE CONSTRUCTED |
| | WITH NONCOMBUSTIBLE MATERIALS, THE DESIGN OF WHICH IS |
| | SUCH THAT ALL LEVELS OF THE GARAGE ARE UNIFORMLY OPEN |
| | TO THE ATMOSPHERE ON ALL SIDES WITH THE PERCENTAGES OF |
| | OPENINGS |
| | EQUAL TO OR GREATER THAN THOSE SPECIFIED IN SECTION |
| | 406.3 . SUCH GARAGES SHALL BE SEPARATED FROM ANY OTHER |
| | STRUCTURE BY NOT LESS THAN 20 FEET (6096 MM). A |
| | STAND-ALONE PARKING GARAGE IS ONE THAT IS SOLELY FOR |
| | THE PARKING OF |
| | VEHICLES AND DOES NOT HAVE ANY OTHER OCCUPANCY |
| | GROUP IN THE BUILDING. |
| | THIS BUILDING SHALL REQUIRE FIRE SPRINKLERS |
| | 903.6.1. |
| | ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN |
| | HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC |
| | SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION |
| | 903.1 . |
| | |
| | 6)FP1.00 NOTE# 1 INDICATES FIRE SPRINKLER HEADS TO |
| | BE INSTALLED IN ACCORDANCE WITH NFPA 14, THIS IS FOR |
| | STAND PIPES, NFPA 13 IS FOR FIRE SPRIKLERS. |
| | |
| | 7)FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR) OF PRODUCT |
| | TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | 7A) WINDOWS |
| | 7B) EXTERIOR HOLLOW METAL DOORS |
| | 7C) LOUVERS |
| | 7D) ROOFING ASSEMBLIES |
| | |
| | 8)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 10)A.8.0.0 THE DOOR SCHEDULEINDICATES THE USE OF |
| | GLAZED PANELS IN THE 1 1/2 HR RATED DOORS, PLEASE |
| | PROVIDE THE SIZE OF PANELS AND TYPE OF GLAZING TO BE |
| | USED INT THESE PANELS? |
| | TABLE 715.4& TABLE 715.4.3. |
| | |
| | 11) SHEET A4.0.2 TYPICAL ROOF DETAIL INDICATES O.S. |
| | TAKEN TO MEAN OVERFLOW SCUPPERS IF THIS IS CORRECT THE |
| | RAINWATER COLLECTION HEAD IS DRAWN OFF TO THE SIDE NOT |
| | IN LINE WITH THE OVERFLOW SCUPPERS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |