| Plan Review Notes For Permit 07030570 |
| Permit Number |
07030570 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-16 11:10:00 | ---------------DENIED------------------ | | | | | | PLAN LACKS SUFFICIENT DETAIL FOR REVIEW. THE FOLLOWING | | | MISSING INFORMATION IS REQUIRED PER FBC 106.3.5.4: | | | | | | ENERGY CALCULATIONS | | | EQUIPMENT SCHEDULE | | | DUCT LAYOUT SIZE/GRILL SIZE (INCLUDE CFM) | | | | | | LIVING AREA 10X10 DROP IS SHOWN AS RETURN, BUT ATTACHES | | | TO SUPPLY TRUNK. PLEASE CLARIFY. | | | SIZE OF FLEX FEEDING SAME 10X10 IS MISSING. PLEASE | | | CLARIFY. | | | | | | THERE IS NO SIZE OR LOCATION OF CENTRALIZED RETURN AIR | | | SHOWN ON PLAN. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|