| Plan Review Notes For Permit 07030569 |
| Permit Number |
07030569 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-12-07 10:55:24 | ****************PROVISO************** | | | NOTE: IF TUB ACCESS PANEL IS REMOVED THE TUB SHALL NOT | | | HAVE SLIP JOINT CONNECTIONS. PER *405.8, SLIP JOINT | | | CONNECTIONS. | | | | | | NOTE: ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT | | | AWAY FROM THE STRUCTURE SIDEWALL ON SPLASH BLOCKS. PER | | | *1503.6 PROTECTION AGAINST DECAY AND TERMITES. | | | | | | NOTE: PER *604.9 WATER HAMMER. A WATER-HAMMER | | | ARRESTOR SHALL BE INSTALLED WHERE | | | QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER | | | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURER'S SPECIFICATIONS. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|