Plan Review Notes
Plan Review Notes For Permit 07030569
Permit Number 07030569
Review Stop P
Sequence Number 2
Notes
Date Text
2007-09-27 09:31:43DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO** SHEET D-1 INDICATES REMOVAL OF THE ACCESS
 DOOR TO THE BATH TUB WASTE AND OVERFLOW. PER FBC-2004
 W/-5 7 06 REV. PLUMBING SECTION 405.8 SLIP JOINT
 CONNECTIONS: FIXTURES WITH CONCEALED SLIP JOINT
 CONNECTIONS SHALL BE PROVIDED WITH AN ACCESS PANEL OR
 UTILITY SPACE AT LEAST 12 INCHES IN ITS SMALLEST
 DEMINSION OR OTHER APPROVED ARRANGEMENT SO AS TO
 PROVIDE ACCESS TO THE SLIP JOINT CONNECTIONS FOR
 INSPECTION AND REPAIR.
 NOTE: PLEASE ADD TO SHEET D-1 THAT THIS TUB WILL NOT
 HAVE ANY SLIP JOINT CONNECTIONS ON THE RESUBMITTAL.
  
 2. **OK**
  
 3. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM THE
 FOLLOWING IS STILL REQUIRED FOR THE WASHING MACHINE.
 (A) **OK**
 (B) **OK**
 (C) **NO** 708.9 ACCESS SHALL BE PROVIDED TO ALL
 CLEANOUTS. PLEASE CLEARLY INDICATE ON THE RESUBMITTAL
 THAT THE CLEANOUT FOR THE WASHING MACHINE IS LOCATED AT
 THE BASE OF THE DRAINAGE STACK TO THE OUTSIDE OF THE
 BUILDING OR AT 4 FEET ABOVE FINNISH FLOOR TO THE INSIDE
 OF THE BUILDING ON THE RESUBMITTAL.
  
 4. **OK**
  
 5. **NO/OK** SHEET P-1 ISOMETRIC WATER RISER DIAGRAM:
 PER FBC-2004 W/05 & 06 REV., PLUMBING SECTION 604.9
 WATER HAMMER ARRESTORS ARE REQUIRED FOR QUICK CLOSING
 VALVES.
 NOTE: A WATER HAMMER ARRESTOR IS ALSO REQUIRED ON THE
 HOT WATER TO THE WASHING MACHINE. PLEASE ADD THE
 FOLLOWING NOTE TO THE WATER RISER DIAGRAM "WATER HAMMER
 ARRESTORS ARE TO BE INSTALLED PER FBC-2004 W/05 & 06
 REV. SECTION 604.9".
  
 6. **OK**
  
 7. **OK**
  
 8. **OK**
  
 9. **OK**
  
 ******THE FOLLOWING ARE NEW COMMENTS.
  
 10. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM: THE
 ADDED DOUBLE COMPARTMENT SINK AND DISHWASHER DRAINAGE
 PIPING TO THE DRAWINGS IS WRONG PER FBC-2004 W/05 & 06
 REV. SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 ALSO THIS PIPING NEEDS TO BE SIZED PER FBC-2004 CHAPTER
 1, SECTION 106.3.5.4.
  
 11. SHEET P-1 SANITARY RISER DIAGRAM AND PLUMBING
 FLOOR PLAN THE NEW SHOWER IN THE NEW MASTER BATH IS
 MISLABELED AS A TUB.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK
 ON THE INDICATED PLAN SHEETS BY THIS PLANS EXAMINER FOR
 REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved