| 2007-03-22 13:03:51 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE RISER DIAGRAM INDICATES A NEW 150 AMP PANEL AND |
| | A PANEL INSIDE THE HOUSE. THE PLAN INDICATES EXISTING |
| | METER AND MAIN PANEL "A" ON THE OUTSIDE OF THE HOUSE. |
| | PLEASE CORRELATE AND IF THE PANEL IS INSIDE SHOW THE |
| | LOCATION ON THE PLAN. |
| | |
| | 2} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 3} 250.50 GROUNDING ELECTRODE SYSTEM |
| | ALL GROUNDING ELECTRODES AS DESCRIBED IN 250.52(A)(1) |
| | THROUGH (A)(6) THAT ARE PRESENT AT EACH BUILDING OR |
| | STRUCTURE SERVED SHALL BE BONDED TOGETHER TO FORM THE |
| | GROUNDING ELECTRODE SYSTEM.SEE 250.52(A)(3) FOR |
| | FOOTER STEEL, AS IT WILL BE PRESENT AT THE NEW |
| | ADDITION. THIS IS THE BEST GROUNDING ELECTRODE THAT CAN |
| | BE USED. |
| | |
| | 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. |
| | THERE ARE 5 NEW CIRCUITS IN THE "SCOPE OF WORK" NOTES, |
| | ONLY 3 IN THE "LOAD SUMMARY. THERE MUST BE A MINIMUM OF |
| | 3 FOR LIGHTING, 1 FOR THE BATH PER 210.11(C)(3), 3 FOR |
| | THE TANKLESS @ 100 AMPS (24000 WATTS/240), 1 FOR THE |
| | NEW MICROWAVE, AND THE NAMEPLATE ON THE NEW OVEN SHOULD |
| | BE VERIFIED @ 7500W. |
| | |
| | 5} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW |
| | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS." |
| | |
| | 6} THE NOTE ABOUT SMOKE DETECTORS AND PALM BEACH COUNTY |
| | DO NOT APPLY TO WEST PALM BEACH OR THEIS PROJECT. SEE |
| | R313.1.1 RESIDENTIAL BUILDING CODE. ALSO LOCATE ON |
| | PLANS.ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" |
| | 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, |
| | TO AVOID CONFUSION IN THE FIELD. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |