| 2007-04-17 15:44:52 | BUILDING REVIEWW CHECKLIST: |
| | 1- PROVIDE ARCHITECT'S FIRM LICENSE NUMBER IN THE TITLE |
| | BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| | ADMINISTRATIVE CODE. |
| | ***NOTE: ARCHITECT'S TITLE BLOCK IS PEELING OFF FROM |
| | SHEET AND IS REVEALING ANOTHER ARCHITECT'S FIRM. |
| | UPDATE/REVISE ORIGINALSHEETS TO INCLUDE CORRECT AND |
| | CURRENT ARCHITECT'S FIRM NAME. |
| | |
| | 2- AFTER ALL DRAWINGS ARE REVISED BRING THEMTO PALM |
| | BEACH COUNTY (2300 N. JOG RD. (561)233-5115) TO PAY |
| | IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF ADDITIONAL FEES ARE DUE. |
| | |
| | 3- PROVIDE COMPLETE INFORMATIONSHOWING COMPLIANCE |
| | WITH CRAWL SPACE VENTILATION SIZE AND LOCATION AND |
| | ACCESS. SEE SEC. R408OF 2004 FLORIDA RESIDENTIAL CODE |
| | AND PROVIDE INFORMATION AS REQUIRED. |
| | ***NOTE: KEEP IN MIND THAT THERE IS AN INTERIOR STEM |
| | WALL FOR INTERIOR BEARING WALL. SHOW CROSS VENTILATION |
| | AND ACCESS TO BOTH SIDES OF CRAWL SPACE. |
| | |
| | 4- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH |
| | SEC. R319.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 5- PROVIDE COMPLETE SPECS SHOWING COMPLIANCE WITH SEC. |
| | R320 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION NUMBER |
| | 27190 IS UNDER A DELINQUENT STATUS ACCORDING TO THE |
| | DBPR WEBSITE.ENGINEER NEEDS TO CONTACT DBPR AND |
| | REVISE STATUS AS REQUIRED TO COMPLY WITH SEC. |
| | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 7- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC. |
| | 106.1.1.2 CITY AMENDMENTS TO FBC 2004TO VERIFY THAT |
| | PRODUCT APPROVAL MEETS THE CALCULATED UPLIFT LOADS. |
| | |
| | 8-PROVIDE COMPLETE SPECS AND DETAILS SHOWING |
| | COMPLIANCE WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 9- SHEET SP-1: CLARIFY NOTE ON PROPOSED SITE PLAN |
| | REGARDING LOT GRADING. WHERE IS SEC. R104.3 TAKEN |
| | FROM?. ALSO, SPECIFY GRADING SO WATER IS NOT DRAINED |
| | INTONEIGHBOR'S PROPERTY.SEC. R401.3 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 10- SHEET A-1: |
| | A) FOOTING AND VENTILATION OPENINGS DON'T MATCH |
| | STRUCTURAL PLANS. REVISE AS REQUIRED. |
| | *NOTE: COORDINATE WITH ITEM #3 ABOVE. |
| | ***NOTE: REVISE INFORMATION ON EXTERIOR ELEVATIONS |
| | ALSO. |
| | B) REVISE CODE SECTION REFERENCED FOR WINDOW EGRESS. |
| | CORRECT CODE IS THE 2004 FLORIDA RESIDENTIAL CODE AND |
| | CORRECT SEC. IS SEC. R310. REVISE AS REQUIRED. |
| | |
| | 11- SHEET A2: |
| | A) FLOOR AND ROOF JOIST SIZE AND SPACING TO MATCH |
| | STRUCTURAL DRAWINGS. REVISE AS REQUIRED. |
| | B) REVISE DESIGN CRITERIA. SEE 2004 FLORIDA |
| | RESIDENTIAL CODE AND 2004 FBC FOR CORRECT CODE |
| | SECTIONS. |
| | C) CLARIFY WHAT'S BWS 190MPH? |
| | |
| | 12- SHEET A6 AND A7: COORDINATE SIZE AND SPACING OF |
| | FLOOR AND ROOF JOISTS WITH-STRUCTURAL DRAWINGS. |
| | |
| | 13- SHEET S1: |
| | A) COORDINATE WITH ARCHITECT FOR CRAWL SPACE SIZE, |
| | LOCATION AND ACCESS. SEE ITEM #3 ABOVE. |
| | B) CLARIFY WHY 4" DROP SHOWN ON GROUND FLOOR PLAN. |
| | SEE ARCHITECTURAL PLANS. |
| | C) ENERGY CALCULATIONS CALL FOR R30 INSULATION ON |
| | ROOF.R30 INSULATION DOESN'T FEET ON 2X8 ROOF JOIST. |
| | REVISE AS REQUIRED. |
| | |
| | 14- SHEET S2: |
| | A) TYPICAL INTERIOR WALL SECTION 06/S2: PROVIDE |
| | COMPLETE FASTENING SPECS OF FRAMED WALL TO STEM WALL. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 15- SHEET S3: |
| | A) CLARIFY WHY ROOFS ABOVE FRENCH DOORS IN REAR |
| | ELEVATIONARE CONSIDERED TO BE ON ZONE 2 FOR |
| | COMPONENTS AND CLADDING UPLIFT LOAD SKETCH. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. ALSO, REVISE ROOF |
| | FASTENING SPECS FOR THESE ROOFS AS REQUIRED. SEE DETAIL |
| | 09/S2. |
| | B) REVISE DETAILS 01/S3,02/S3 AND 03/S3TO MATCH |
| | ACTUAL CONDITIONS ON THIS PROJECT. SHOW THE STEM WALL |
| | AND COORDINATECONNECTORS AS SHOWN ON FRAMING PLANS |
| | AND OTHER DETAILS. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | C) THERE IS SOME OVERLAPPING INFORMATION SHOWN ON |
| | STRUCTURAL NOTES RIGHT BELOW THE WATERPROOF MEMBRANES |
| | NOTE. REVISE AS REQUIRED. |
| | D) REVISE MASONRY NOTE #2. SEE SEC. R606.4 OF 2004 |
| | FLORIDA RESIDENTIAL CODE FOR MIN. COMPRESSIVE STRENGTH |
| | REQUIRED. |
| | |
| | 16- PROVIDE SOIL TEST REPORT. |
| | |
| | 17- DESIGNER OF RECORD TO SPECIFYSOIL BEARING |
| | CAPACITYASSUMED FOR THE DESIGN OF THIS STRUCTURE. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 18- PROVIDE COMPLETE SPECS FOR CONSTRUCTION OF NEW |
| | PATIO SLAB. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 19- AFTER ALL PLANS ARE REVISED,PLEASE BRING THEM TO |
| | THE FIFTH FLOOR TO THE HISTORIC DISTRICT DEPARTMENT FOR |
| | APPROVAL AND STAMPING. THEN, RE-SUBMIT THEMTO THIS |
| | OFFICE. |
| | |
| | 20- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) FLAT ROOF SYSTEM: |
| | * NEED LEGIBLE NOA. |
| | ** NEED TO SPECIFY SPECIFIC FASTENING OPTION. SEE |
| | SHEET 28 OF 32. |
| | *** NEED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| | LIMITATION #7. SEE SHEET 32 OF 32. |
| | |
| | B) FIXED WINDOW WITH FROSTED GLASS. PICTURE WINDOW |
| | 701 SUBMITTED IS FOR SINGLE HUNG WINDOWS AND IS |
| | EXPIRED. |
| | C) CLAY TILE. |
| | |
| | 21- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 22- ENERGY CALCULATIONS: |
| | A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. |
| | B) THERE IS NOT SLAB ON GRADE. SEE PLANS. |
| | C) NEED TO HAVE R19 ON EXTERIOR 2X6 FRAMED WALLS. |
| | |
| | D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | E) ENGINEER WHO PREPARED CALCULATIONS NEEDS TO SIGN |
| | AND SEAL THEM AND PROVIDE ALL HIS INFORMATION AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTES AND FLORIDA |
| | ADMINISTRATIVE CODE. |
| | F) OVERHANG LENGTH AND HEIGHT IS INCORRECT. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |