Text |
| 2008-12-29 09:21:00 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS REVIEW. |
| | PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER |
| | 13-415.2.ABC.1.3. THE RESPONSE MENTIONS PER THE PHONE |
| | CONVERSATION FIXTURES WERE BEING REPLACED AND |
| | CALCULATIONS ARE NOT REQUIRED. HOWEVER THE CONVERSATION |
| | OVER THE PHONE WAS THE FACT ONLY COMPONENTS OF THE |
| | EXISTING FIXTURES WERE GOING TO BE REPLACED SUCH AS |
| | BALLAST, BULBS OR EXISTING FIXTURE BALLAST AND LIGHT |
| | BULBS KITS. THE LAST CONVERSATION STATED BY THE |
| | DESIGNER WAS HE WAS GOING TO RE-CONFIRM WITH THE |
| | ELECTRICAL CONTRACTOR THE ACTUAL SCOPE OF WORK FOR |
| | FIXTURES. |
| | THE DESIGNER WAS GOING TO CALL BACK IF IT WAS ANYTHING |
| | MORE THAN REPAIRING EXISTING FIXTURES. |
| | THIS OFFICE INFORMED KAMM CONSULTING DESIGNER THAT IF |
| | FIXTURES WERE BEING REPLACED THEN CALCULATIONS PER |
| | ABOVE WOULD BE NEEDED. IT WAS ONLY IF THE PARTS WERE |
| | BEING REPLACED AND EXISTING FIXTURES WERE REPAIRED THEN |
| | WE WOULD NOT NEED CALCULATIONS. THIS WOULD MEAN ALL |
| | EXISTING FIXTURES WOULD HAVE TO REMAIN. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |