 ** DENIED REVISION**
  
  
 1) NOTE: NEED TO SHOW ALL CIRCUITING FOR NEW LIGHTING
 NOW SHOWN WHICH WILL NEED TO BE ACCOMPANIED BY NEW
 REVISED PANEL SCHEDULES, LOADS, CONDUCTORS ETC
 408.4,310.16,220 ETC
 FBC 106.1.1
  
 2) NOTE: PLEASE PROVIDE NEW REVISED LIGHTING
 PERFORMANCE CALCULATIONS.
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: THE VALUE FOR THE INCREASED SCOPE OF WORK
 NEEDS TO BE REVISED PER FBC 108.3.
  
 ** PLEASE KNOW PLANS INDICATED NEW ADDITION FROM
 EXISTING BUILDING AS A SEPARATE BUILDING.
  
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER