| 2008-03-11 08:55:46 | |
| | DENIED 4TH TIME |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINSTRATIVE CODE |
| | FLORIDA STATUES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | ********THE FOLLOWING COMMENTS ARE NUMBERED TO |
| | CORRESPOND WITH THE PREVIOUS PLUMBING REVIEW COMMENTS |
| | AS WELL AS THE DESIGNER'S RESPONSES FOR THE PURPOSE OF |
| | CONTINUITY. |
| | |
| | 1. SURVEY SHEET REQUIRES THE ORIGINAL SIGNATURE. |
| | SIGNATURE IS A PHOTO-COPY. FAC 61G1-17.002 & FS |
| | 472.025.-THE TITLE BLOCK ADDRESS "OLD" OKEECHOBEE |
| | ROAD DOES NOT REFLECT THE DBPR WEBSITE SHOWING THE |
| | CORRECT ADDRESS OKEECHOBEE ROAD. THE COUNTY (PAPA) DOES |
| | NOT RECOGNIZE "OLD" OKEECHOBEE ROAD, NOR DOES THE CITY |
| | WPB'S ADDRESSING SYSTEM. PLEASE CHANGE THE TITLE BLOCK |
| | TO REFLECT THE CORRECT ADDRESS.-"OLD" OKEECHOBEE IS |
| | ALSO SHOWN IN THE DBPR WEBSITE FOR THE BUSINESS LICENSE |
| | (CERTIFICATE OF AUTHORIZATION) NUMBER. PLEASE SUBMIT AN |
| | ADDRESS CORRECTION TO DBPR WEBSITE INDICATING THE |
| | CORRECT ADDRESS OF OKEECHOBEE ROAD. |
| | ****RESPONSE NOTED, BUT THE ADDRESS ON THE TITLE BLOCK |
| | HAS NOT BEEN CHANGED. |
| | ******RESPONSE NOTED, BUT NOT ADDRESSED. |
| | ********RESPONSE NOTED, BUT NOT ADDRESSED. PLANS NOW |
| | INDICATE ADDRESS AS "P.O. BOX 211747, WPB,FL,33401" |
| | HOWEVER DPBR WEB SITE INDICATES ADDRESS AS "1860 OLD |
| | OKEECHOBEE RD. SUITE 501,WPB,FL,33401. PLEASE CORRECT |
| | AND CORRELATE ADDRESS. |
| | |
| | 2. OK |
| | |
| | 3. ALL CIVIL SHEETS REQUIRE THE BUSINESS LICENSE, |
| | (CERTIFICATE OF AUTHORIZATION), IN THE TITLE BLOCK OF |
| | ARCHITECTURAL ALLIANCE. (SEE ATTACHED SHEET FROM DBPR). |
| | --THE SIGNATURE IS REQUIRED WHEN THE SEAL IS AFFIXED |
| | TO THE DOCUMENTS. IT APPEARS THAT INITIALS WERE USED |
| | WHICH IS NOT APPROVED. IF INDEED THIS IS THE LEGAL |
| | SIGNATURE, THEN A SIGNED, SEALED, NOTORIZED LETTER |
| | SHALL BE SUBMITTED FOR OUR FILES INDICATING THE LEGAL |
| | SIGNATURE. FAC 61G1-16.003, 61G1-16.004(5) & FS |
| | 481.219, 481.2055. |
| | ****RESPONSE NOTED, BUT ARCHITECTURAL ALLIANCE IS STILL |
| | SHOWN ON SOME SHEETS, (CS-1, LD-1 & L-1). CHECK ALL |
| | SHEETS. NO LETTER HAS BEEN SUBMITTED FOR SIGNATURE |
| | VERIFICATION. |
| | ******RESPONSE NOTED, BUT LETTER NOT ADDRESSED. |
| | ********RESPONSE NOTED, CERTIFICATE OF AUTHORIZATION IS |
| | "OK" HOWEVER NO LETTER HAS BEEN SUBMITTED FOR SIGNATURE |
| | VERIFICATION. |
| | |
| | 4. OK |
| | 5. OK |
| | |
| | 6. SHT A-1 KEY PLAN SHOWS A NEW TOILET ROOM AND SERVICE |
| | SINK LOCATION IN THE EXISTING BUILDING. PREVIOUS SHEETS |
| | INDICATE, " EXISTING BUILDING NOT IN CONTRACT", AND THE |
| | APPLICATION DOES NOT MENTION REMODEL OF EXISTING |
| | BUILLDING. PLEASE CLARIFY. APPLICATION REQUIRES A |
| | DESCRIPTION IN DETAIL OF THE PROJECT. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE APPLICATION HAS NOT BEEN |
| | UPDATED. |
| | ******RESPONSE NOTED, BUT APPLICATION NOT REVISED. |
| | ********RESPONSE NOTED, HOWEVER PERMIT APPLICATION HAS |
| | NOT BEEN REVISED. |
| | |
| | 7. **OK** COMMENT ADDRESSED. |
| | |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. OK |
| | |
| | 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONALS AND FS 553.80(2)(B). THIS IS GIVEN AS A |
| | NOTICE ONLY AT THIS TIME. |
| | ******NOTICE GIVEN PREVIOUSLY. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |