| 2008-03-05 16:50:27 | 3501 ELECTRONIC WAY |
| | 4TH REVIEW |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07030559 |
| | ADD: 3501 ELECTRONIC WAY |
| | |
| | CONT: EDWARDS CONSTRUCTION SERVICES |
| | TEL: (352)854-6266 |
| | |
| | MARCH 3, 2008 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 4TH |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) THE NOTICE OF COMMENCEMENT THAT WAS RECORDED IS OVER |
| | 90 DAYS OLD REQUIRING THE DOCUMENT TO BE RE-RECORDED. |
| | FL S S713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID.NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OFCOMMENCEMENT AT THE |
| | CONSTRUCTIONSITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) COMPLIED. |
| | 4 COMPLIED. |
| | 5) COMPLIED. |
| | 6A) COMPLIED |
| | |
| | 6B) **PARTIALLY ADDRESSED** HOWEVER, THE ISOLATEK |
| | ?CAFCO 300SB? ES REPORT FROM ICC FOR IS REQUIRED. WHEN |
| | SUBMITTING THE REPORT INDICATE BY HI-LIGHT OR CIRCLING |
| | THE MINIMUM THICKNESS OF THE SPRAYED ON MATERIAL. SHEET |
| | A-1 REVISION# 2 DOES INDICATE LANGUAGE OF A 3 HR RATED |
| | WALL AND THERE IS A CUT SECTION OF THIS PORTION OF |
| | BUILDING THAT REFERENCES DETAIL6 ON SHEET A6. THIS |
| | DETAIL SHOULD BE OF THE 3 HR RATED WALL BUT WE SEE AN |
| | EXISTING STEEL BEAM AND NO FIRE RATING AS REQUIRED IN |
| | TABLE 715.3. |
| | |
| | 6C)COMPLIED |
| | 7) COMPLIED |
| | 8)COMPLIED. |
| | 9) COMPLIED |
| | |
| | B10) BUILDINGPROVISO, 109.3.10.1 HURRICANE |
| | PROTECTION. |
| | |
| | 11) THIS WILL BE A BUILDING PROVISO109.3.10* IMPACT |
| | OF CONSTRUCTION. |
| | |
| | 12) COMPLIED |
| | 13) COMPLIED |
| | |
| | 14A) 3RD REQUEST, THE BUILDING IS DESIGNED AS AN |
| | ENCLOSED STRUCTURE ALL PRODUCT APPROVALS ARE REQUIRED |
| | BEFORE THE PERMIT CAN BE ISSUED. |
| | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE |
| | 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF |
| | PRODUCT TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A)HOLLOW METAL EXTERIOR DOORS- NO REPORT SUBMITTED. |
| | **OK** |
| | B) OVERHEAD DOORS: NOT ILLEGIBLE WILL REQUIRE FLORIDA |
| | COVERSHEET. **OK** |
| | C) PANEL WALLS: SIDING AND OR WALL LOUVERS- NO REPORT |
| | SUBMITTED |
| | D) ROOF ASSEMBLIES : METAL ROOFING ? NO REPORT |
| | SUBMITTED |
| | |
| | 14B)COMPLIED |
| | 14C)COMPLIED |
| | 15) COMPLIED |
| | 16) **NOTED** |
| | 17-24)COMPLIED |
| | 25) FEES DUE |
| | 26)COMPLIED |
| | |
| | 27) **SEE ELECTRICAL COMMENTS**NEW COMMENT, THE LIGHT |
| | POLE CALCULATIONS DO HAVE A RAISED SEAL BUT A COPIED |
| | SIGNATURE. 61G15-23.002(2) FL. ADMIN. CODE. PLANS |
| | SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL |
| | INCLUDE EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF |
| | THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE |
| | ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS |
| | THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S. |
| | AND 471.023 F.S.). |
| | |
| | NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, |
| | AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |