 4TH REVIEW
  
 BUILDING PLAN REVIEW
 PERMIT: 07030559
 ADD: 3501 ELECTRONIC WAY
  
 CONT: EDWARDS CONSTRUCTION SERVICES
 TEL: (352)854-6266
  
 MARCH 3, 2008
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 4TH
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) THE NOTICE OF COMMENCEMENT THAT WAS RECORDED IS OVER
 90 DAYS OLD REQUIRING THE DOCUMENT TO BE RE-RECORDED.
 FL S S713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OFCOMMENCEMENT AT THE
 CONSTRUCTIONSITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
 4 COMPLIED.
 5) COMPLIED.
 6A) COMPLIED
  
 6B) **PARTIALLY ADDRESSED** HOWEVER, THE ISOLATEK
 ?CAFCO 300SB? ES REPORT FROM ICC FOR IS REQUIRED. WHEN
 SUBMITTING THE REPORT INDICATE BY HI-LIGHT OR CIRCLING
 THE MINIMUM THICKNESS OF THE SPRAYED ON MATERIAL. SHEET
 A-1 REVISION# 2 DOES INDICATE LANGUAGE OF A 3 HR RATED
 WALL AND THERE IS A CUT SECTION OF THIS PORTION OF
 BUILDING THAT REFERENCES DETAIL6 ON SHEET A6. THIS
 DETAIL SHOULD BE OF THE 3 HR RATED WALL BUT WE SEE AN
 EXISTING STEEL BEAM AND NO FIRE RATING AS REQUIRED IN
 TABLE 715.3.
  
 6C)COMPLIED
 7) COMPLIED
 8)COMPLIED.
 9) COMPLIED
  
 B10) BUILDINGPROVISO, 109.3.10.1 HURRICANE
 PROTECTION.
  
 11) THIS WILL BE A BUILDING PROVISO109.3.10* IMPACT
 OF CONSTRUCTION.
  
 12) COMPLIED
 13) COMPLIED
  
 14A) 3RD REQUEST, THE BUILDING IS DESIGNED AS AN
 ENCLOSED STRUCTURE ALL PRODUCT APPROVALS ARE REQUIRED
 BEFORE THE PERMIT CAN BE ISSUED.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF
 PRODUCT TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A)HOLLOW METAL EXTERIOR DOORS- NO REPORT SUBMITTED.
 **OK**
 B) OVERHEAD DOORS: NOT ILLEGIBLE WILL REQUIRE FLORIDA
 COVERSHEET. **OK**
 C) PANEL WALLS: SIDING AND OR WALL LOUVERS- NO REPORT
 SUBMITTED
 D) ROOF ASSEMBLIES : METAL ROOFING ? NO REPORT
 SUBMITTED
  
 14B)COMPLIED
 14C)COMPLIED
 15) COMPLIED
 16) **NOTED**
 17-24)COMPLIED
 25) FEES DUE
 26)COMPLIED
  
 27) **SEE ELECTRICAL COMMENTS**NEW COMMENT, THE LIGHT
 POLE CALCULATIONS DO HAVE A RAISED SEAL BUT A COPIED
 SIGNATURE. 61G15-23.002(2) FL. ADMIN. CODE. PLANS
 SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL
 INCLUDE EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF
 THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S.
 AND 471.023 F.S.).
  
 NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved