Plan Review Notes
Plan Review Notes For Permit 07030559
Permit Number 07030559
Review Stop P
Sequence Number 3
Notes
Date Text
2007-12-14 17:58:19DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINSTRATIVE CODE
 FLORIDA STATUES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. SURVEY SHEET REQUIRES THE ORIGINAL SIGNATURE.
 SIGNATURE IS A PHOTO-COPY. FAC 61G1-17.002 & FS
 472.025.-THE TITLE BLOCK ADDRESS "OLD" OKEECHOBEE
 ROAD DOES NOT REFLECT THE DBPR WEBSITE SHOWING THE
 CORRECT ADDRESS OKEECHOBEE ROAD. THE COUNTY (PAPA) DOES
 NOT RECOGNIZE "OLD" OKEECHOBEE ROAD, NOR DOES THE CITY
 WPB'S ADDRESSING SYSTEM. PLEASE CHANGE THE TITLE BLOCK
 TO REFLECT THE CORRECT ADDRESS.-"OLD" OKEECHOBEE IS
 ALSO SHOWN IN THE DBPR WEBSITE FOR THE BUSINESS LICENSE
 (CERTIFICATE OF AUTHORIZATION) NUMBER. PLEASE SUBMIT AN
 ADDRESS CORRECTION TO DBPR WEBSITE INDICATING THE
 CORRECT ADDRESS OF OKEECHOBEE ROAD.
 ****RESPONSE NOTED, BUT THE ADDRESS ON THE TITLE BLOCK
 HAS NOT BEEN CHANGED.
 ******RESPONSE NOTED, BUT NOT ADDRESSED.
  
 2. OK
  
 3. ALL CIVIL SHEETS REQUIRE THE BUSINESS LICENSE,
 (CERTIFICATE OF AUTHORIZATION), IN THE TITLE BLOCK OF
 ARCHITECTURAL ALLIANCE. (SEE ATTACHED SHEET FROM DBPR).
 --THE SIGNATURE IS REQUIRED WHEN THE SEAL IS AFFIXED
 TO THE DOCUMENTS. IT APPEARS THAT INITIALS WERE USED
 WHICH IS NOT APPROVED. IF INDEED THIS IS THE LEGAL
 SIGNATURE, THEN A SIGNED, SEALED, NOTORIZED LETTER
 SHALL BE SUBMITTED FOR OUR FILES INDICATING THE LEGAL
 SIGNATURE. FAC 61G1-16.003, 61G1-16.004(5) & FS
 481.219, 481.2055.
 ****RESPONSE NOTED, BUT ARCHITECTURAL ALLIANCE IS STILL
 SHOWN ON SOME SHEETS, (CS-1, LD-1 & L-1). CHECK ALL
 SHEETS. NO LETTER HAS BEEN SUBMITTED FOR SIGNATURE
 VERIFICATION.
 ******RESPONSE NOTED, BUT LETTER NOT ADDRESSED.
  
 4. OK
 5. OK
  
 6. SHT A-1 KEY PLAN SHOWS A NEW TOILET ROOM AND SERVICE
 SINK LOCATION IN THE EXISTING BUILDING. PREVIOUS SHEETS
 INDICATE, " EXISTING BUILDING NOT IN CONTRACT", AND THE
 APPLICATION DOES NOT MENTION REMODEL OF EXISTING
 BUILLDING. PLEASE CLARIFY. APPLICATION REQUIRES A
 DESCRIPTION IN DETAIL OF THE PROJECT. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE APPLICATION HAS NOT BEEN
 UPDATED.
 ******RESPONSE NOTED, BUT APPLICATION NOT REVISED.
  
 7. SHT A-4 SUBMIT CALCULATIONS FOR THE EXISTING ROOF.
 THERE WILL BE ADDITIONAL SQUARE FOOTAGE ADDED TO THE
 EXISTING ROOF WITH 1/2 THE AREA OF THE VERTICAL WALL OF
 THE NEW ADDITION CONTRIBUTING TO THE EXISTING ROOF
 DRAINS ADJACENT TO THE ADDITION. SHOW THE SQUARE
 FOOTAGE BEING DRAINED BY THE ROOF DRAINS PRIOR TO AND
 AFTER THIS NEW CONTRIBUTION. SUBMIT AN EXISTING ROOF
 PLAN TO SCALE AS WELL AS AN ELEVATION SHOWING THE
 HEIGHT OF ALL PARAPETS IN ORDER TO VERIFY ALL
 CALCULATIONS. INDICATE THE SIZE OF THE EXISTING RWL'S
 AND ASSOCIATED PIPING FOR THE EXISTING STORM SYSTEM.
 TABLE 1106.3 AND SECTIONS 1106.2, 1106.4. ALSO INDICATE
 THE SIZE OF THE SECONDARY ROOF DRAINS, OR OVERFLOW
 SCUPPERS ON THE EXISTING ROOF TO VERIFY THAT THEY ARE
 SUFFICIENT TO HANDLE THE NEW SQUARE FOOTAGE ADDED TO
 THE EXISTING ROOF. SECTION 1107.3.
 ****RESPONSE NOTED, BUT NO CALCULATIONS WERE SUBMITTED
 INDICATING THE SQUARE FOOTAGE ADDED TO THE EXISTING
 ROOF, THE TOTAL SQUARE FOOTAGE BEING DRAINED TO THE
 SECTION OF ROOF ADJACENT TO THE NEW BUILDING, DOWNSPOUT
 SIZE, LOCATION OF DOWNSPOUTS, TOTAL GUTTER AREA TO
 EXISTING AFFECTED DOWNSPOUTS ETC. SECTIONS 1106.2 &
 1106.4 AND TABLES 1106.3 & 1106.6.
 ******RESPONSE NOTED, NOT ADDRESSED.
  
 8. OK
 9. OK
 10. OK
 11. OK
  
 **********NEW COMMENTS**********
  
 1B. OK
  
 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONALS AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
 ******NOTICE GIVEN PREVIOUSLY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]