| 2007-12-04 09:57:03 | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW |
| | COMMENTS BASED ON REVISED PLANS/INFORMATION ETC. |
| | |
| | 1) NOTE: PLEASE SEE SPECIFIC COMMENTS ON THE TWO |
| | PREVIOUS REVIEWS FOR THE CODES AND THE RELEVANT |
| | EDITIONS TO THE CODES TO BE STATED ON PLANS. THIS WAS |
| | DONE ON ARCHITECTURAL SHEETS HOWEVER NOT THE ELECTRICAL |
| | SHEET E0.1. |
| | PLEASE SEE ONLY ONE CODE WAS UPDATED. |
| | PLEASE KNOW THE FLORIDA BUILDING CODE AND RECORD PLANS |
| | ARE REQUIRED TO HAVE THE EDITION STATED ON PLANS. MAY |
| | NOT QUOTE THE LATEST EDITION AS PERMIT APPLICATION |
| | DATES DO NOT ALWAYS CORRELATE WITH THE LATEST ADOPTED |
| | EDITION. |
| | PLEASE MAKE SURE THE FOLLOWING ARE STATED ON ELECTRICAL |
| | COVER SHEET. |
| | 2005 NFPA-70 (DONE) |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2003 NFPA-20. (IF FIRE SPRINKLER SYSTEM IS NOT PART OF |
| | THE DESIGN OR RESPONSIBILITY OF KAMM CONSULTING, THEN |
| | PLEASE FORWARD THIS PART OF THE COMMENT TO THE FIRE |
| | SPRINKLER DESIGNER AS THE FP SHEETS DO NOT CONTAIN ANY |
| | CODE REFERENCE TO NFPA-20. |
| | |
| | 2) NOTE:THIS IS NOT A KAMM CONSULTING COMMENT. PLEASE |
| | SEE THE FP SHEETS DO NOT CONTAIN THE INFORMATION FOR |
| | RUN TIME OF FIRE PUMP AND FUEL CONSUMPTION AS |
| | PREVIOUSLY REQUESTED. |
| | PLEASE SEE PREVIOUS REVIEW NOTE #4. |
| | PLEASE PROVIDE WHERE THIS INFORMATION IS LOCATED. |
| | PLEASE SEE NOTE FROM FIRE REVIEW ALSO. |
| | |
| | 3) NOTE: THIS IS NOT A KAMM CONSULTING COMMENT. PLEASE |
| | SEE LANDSCAPE SHEETS AND TITLE BLOCKS ARE STILL IN NEED |
| | OF ADDRESSING. PLEASE SEE SHEET L-1 FOR EXAMPLE: PLEASE |
| | SEE THE TITLE BLOCK CONTAINS THE PRINTED NAME OF MR. |
| | HUGH JOHNSON WHICH IS WHO SEALED THE PLANS. PLEASE SEE |
| | THE PRINTED LICENSE NUMBER DIRECTLY UNDER MR. JOHNSON'S |
| | PRINTED NAME IS NOT THAT OF THE LICENSE NUMBER IN |
| | RAISED SEAL FOR MR. JOHNSON ON SHEET. THE NUMBER LISTED |
| | IS * # C000237*. WHEN THIS NUMBER WAS SEARCHED FOR |
| | DBPR, NO RETURNS OR MATCHES CAME BACK. PLEASE CORRECT |
| | AND ADJUST THIS TITLE BLOCK AS PREVIOUSLY NOTED. FAC |
| | 61G10-11, 61G1-16.004, FS 471.219 |
| | |
| | 4) NOTE: THIS IS NOT A KAMM CONSULTING COMMENT. PLEASE |
| | SEE THE WIND LOAD CALCULATIONS WHICH WERE SUBMITTED ARE |
| | NOT ORIGINAL SIGNED, AND DATED. IN FACT THESE AS |
| | SUBMITTED CONTAIN A RAISED SEAL OVER A PHOTO-COPIED |
| | SIGNATURE WHICH IS NOT PERMITTED UNDER FS 471.023 |
| | PLEASE PROVIDE AS PREVIOUSLY NOTED. |
| | |
| | 5) NOTE: PLEASE COMPLETE THE LIGHTING POWER DENSITY |
| | CALCULATIONS PER 13-415.2. |
| | PLEASE SEE FIXTURE LEGEND SHOWS A FIXTURE *D* AS WELL |
| | AS PLANS HOWEVER THE CALCULATIONS ON SHEET E2.1 DO NOT |
| | CONTAIN ANY *D* FIXTURE(S). |
| | PLEASE SEE NO EXTERIOR LIGHTING ALLOWANCES WERE |
| | SUBMITTED. 13-415.2.ABC.1.3 |
| | |
| | 6) NOTE: PLEASE SEE NO SPEC/CUT SHEETS WERE SUBMITTED |
| | FOR THE UPSE INVERTER FOR THE EMERGENCY BACK UP |
| | LIGHTS. |
| | PLEASE SEE NO TIMES FOR THE MINIMUM REQUIRED BACK UP |
| | WAS PROVIDED. AT THE TIME OF THIS REVIEW THE |
| | INFORMATION WAS NOT READILY LOCATED ON THE WEB. PLEASE |
| | SEE NFPA-101 7.8 AND 7.9 AS THE TIME FOR BACK UP OF THE |
| | EGRESS LIGHTING FIXTURES AND UN-INTERRUPTIBLE POWER IN |
| | HID FIXTURES IS OF CONCERN AT THIS TIME. |
| | |
| | 7) NOTE: PLEASE SEE THE MINIMUM CLEARANCES IN THE NEW |
| | ELECTRICAL ROOM FOR ACCESS/EGRESS. PLEASE SEE THE RISER |
| | IS INDICATING THE UPSE WITH ONLY ABOUT ONE FOOT OF ROOM |
| | FROM WALL TO UNIT FOR ACCESS AND EGRESS. |
| | PLEASE SEE THE APPARENT WALL LAYOUTS ON THE ELECTRICAL |
| | PLANS DO NOT PROVIDE THE NEEDED ROOM. THE WALL LAYOUTS |
| | AND ACCESS ON A-SHEETS SEEM TO PROVIDE MORE ROOM BUT |
| | NOT COMPLETELY CLEAR. |
| | 110.26 |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-12-03 18:59:19 | IN ELEC FOR REVIEW. |