| Date |
Text |
| 2007-12-14 16:47:41 | IRON MOUNTAIN 3501 ELECTRONIC WAY |
| | 3RD REVIEW |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07030559 |
| | ADD: 3501 ELECTRONIC WAY |
| | |
| | CONT: EDWARDS CONSTRUCTION SERVICES |
| | TEL: (352)854-6266 |
| | |
| | DEC.14, 2007 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) THE NOTICE OF COMMENCEMENT THAT WAS RECORDED IS |
| | OVER 90 DAYS OLD REQUIRING THE DOCUMENT TO BE |
| | RE-RECORDED. FL S S713.13NOTICE OF COMMENCEMENT, TO |
| | BE FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE |
| | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID.NOTE: |
| | 713.13(6)THE POSTING OF THE NOTICE OFCOMMENCEMENT |
| | AT THE CONSTRUCTIONSITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) COMPLIED. |
| | |
| | 4 COMPLIED. |
| | 5) COMPLIED. |
| | |
| | 6A) CS-1 PLAN REVIEW DATA HAS PARTIALLY COMPLIED WITH |
| | THIS REQUEST. CS-1 STILL HAS THE STATEMENT THAT THIS |
| | BUILDING COMPLIES WITH 507.2 UNLIMITED AREA, THIS IS |
| | NOT TRUE. |
| | THE AREA INCREASES TAKEN ALSO DO NOT MAKE IT CLEAR IF |
| | THIS IS FOR THE NEW METAL BUILDING OR FOR THE BUILDING |
| | (2) ON THE SITE. PLEASE CORRECT THIS WITH EXISTING |
| | BUILDING INFORMATION AND NEW BUILDING INFORMATION. |
| | |
| | 6B) SHEET A-1 REVISION# 2 DOES INDICATE LANGUAGE OF A 3 |
| | HR RATED WALL AND THERE IS A CUT SECTION OF THIS |
| | PORTION OF BUILDING THAT REFERENCES DETAIL6 ON SHEET |
| | A6. THIS DETAIL SHOULD BE OF THE 3 HR RATED WALL BUT WE |
| | SEE AN EXISTING STEEL BEAM AND NO FIRE RATING AS |
| | REQUIRED IN TABLE 715.3. |
| | 6C)SHEET A1& A2 INDICATES A DOOR # 5 AS A 1 ? HR |
| | RATED OPENING PLEASE SEE TABLE 715.3 FOR A 3 HR RATED |
| | FIRE WALL A 3 HR RATED DOOR IS ALSO REQUIRED. DOOR # 2 |
| | WOULD ALSO REQUIRE |
| | A 3HR FIRE RATING PLEASE PROVIDE DOCUMENTATION FOR |
| | BOTH. |
| | |
| | 7)THIRD REQUEST,PLEASECLARIFY, IF THIS IS AN |
| | ADDITION THEN THE 2006 FBC ,EXISTING BUILDING CODE |
| | CHAPTER 9 NEEDS TO BE ADDRESSES UNDER THE PLAN REVIEW |
| | DATA AS WELL AS IN THE EXISTING BUILDING WORK IS ALSO |
| | TO BE COMPLETED UNDER THIS PERMIT, INDICATE TO WHAT |
| | LEVEL OR CLASSIFICATION OF WORK IS TO BE COMPLETED |
| | UNDER THIS PERMIT, PLEASE SEE THE 2004 EXISTING |
| | BUILDING CODE 2004 FOR THE RENOVATION PORTION OF THIS |
| | PROJECT, SEE CHAPTER (3).SHEET SP-1 INDICATES WORK |
| | NOT IN CONTRACT BUT THIS SAME SHEET INDICATES NEW FIRE |
| | SPRINKLER PUMP ROOM, NEW ADA RESTROOMS, EXISTING BAY |
| | DOOR TO BE REPLACED, AND ADA RAMP AND ACCESSIBLE |
| | SIDEWALK? IF THE BUILDING INFORMATION IN COMMENT # 6 IS |
| | CORRECTED THIS COMMENT WILLBE SATISFIED. |
| | |
| | 8)COMPLIED. |
| | |
| | 9) THIS COMMENT AGAIN WOULD DEAL WITH COMMENT NUMBER 6, |
| | WE WILL NEED THE FOLLOWING INFORMATION FOR BOTH |
| | BUILDINGS. 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR |
| | CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT |
| | WAS DESIGNED. ADD INFORMATION FOR THE REMODEL PORTION |
| | OF THIS PROJECT. |
| | |
| | B10) BUILDINGPROVISO, 109.3.10.1 HURRICANE |
| | PROTECTION. |
| | |
| | 11) THIS WILL BE A BUILDING PROVISO109.3.10* IMPACT |
| | OF CONSTRUCTION. |
| | |
| | 12) COMPLIED |
| | |
| | 13) COMPLIED |
| | |
| | 14A) 2ND REQUEST, THE BUILDING IS DESIGNED AS AN |
| | ENCLOSED STRUCTURE ALL PRODUCT APPROVALS ARE REQUIRED |
| | BEFORE THE PERMIT CAN BE ISSUED. |
| | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE |
| | 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF |
| | PRODUCT TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A)HOLLOW METAL EXTERIOR DOORS- NO REPORT SUBMITTED |
| | B) OVERHEAD DOORS: NOT ILLEGIBLE WILL REQUIRE FLORIDA |
| | COVERSHEET. |
| | C) PANEL WALLS: SIDING AND OR WALL LOUVERS- NO REPORT |
| | SUBMITTED |
| | D) ROOF ASSEMBLIES : METAL ROOFING ? NO REPORT |
| | SUBMITTED |
| | |
| | 14B)3RD REQUEST, THE BUILDING IS DESIGNED AS AN |
| | ENCLOSED STRUCTURE ALL PRODUCT APPROVALS ARE REQUIRED |
| | BEFORE THE PERMIT CAN BE ISSUED.PRODUCT APPROVALS |
| | SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED |
| | TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE |
| | STATE WEBSITE ATWWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED |
| | WITH A COVER SHEET THAT LISTS THE PRODUCT IDENTITY |
| | NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR LOCAL |
| | PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 14C)2ND REQUEST, THE BUILDING IS DESIGNED AS AN |
| | ENCLOSED STRUCTURE ALL PRODUCT APPROVALS ARE REQUIRED |
| | BEFORE THE PERMIT CAN BE ISSUED.WPB ADMIN CODE |
| | 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 15) COMPLIED |
| | |
| | 16) THIS SAME SHEET A-1 LOADING DOCK INDICATES A |
| | SECTION "B"/ A4, IT APPEARS THIS SECTION |
| | THE DETAIL 4 ON SHEET A-7 IS A 4 HR RATED FLOOR CEILING |
| | ASSEMBLY. THIS IS A FLOOR CEILING ASSEMBLY PLEASE |
| | PROVIDE TO WHAT LIVE LOAD THIS FLOOR WILL BE DESIGNED |
| | TO, PLEASE SEE TABLE 1607.1. |
| | |
| | 17-24)COMPLIED |
| | |
| | 25) LOW VALUE, FOR THE ADDITION ALONE THE CALCULATED |
| | VALUE IS $4,391, 656.00 THE PERMIT FEES WILL BE |
| | ASSESSED ON THIS DOLLAR AMOUNT |
| | |
| | 26)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | 27) NEW COMMENT, THE LIGHT POLE CALCULATIONS DO HAVE A |
| | RAISED SEAL BUT A COPIED SIGNATURE. 61G15-23.002(2) FL. |
| | ADMIN. CODE. PLANS SIGNED & SEALED BY A PROFESSIONAL |
| | ENGINEER SHALL INCLUDE EITHER THE: NAME, ADDRESS AND |
| | LICENSE NUMBER OF THE ENGINEER OR, THE NAME AND LICENSE |
| | NUMBER OF THE ENGINEER AND THE NAME, ADDRESS AND |
| | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS THROUGH WHICH THE ENGINEER IS PRACTICING |
| | (471.025 F.S. AND 471.023 F.S.). |
| | |
| | NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, |
| | AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |