2007-12-14 16:47:41IRON MOUNTAIN 3501 ELECTRONIC WAY
 3RD REVIEW
  
 BUILDING PLAN REVIEW
 PERMIT: 07030559
 ADD: 3501 ELECTRONIC WAY
  
 CONT: EDWARDS CONSTRUCTION SERVICES
 TEL: (352)854-6266
  
 DEC.14, 2007
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) THE NOTICE OF COMMENCEMENT THAT WAS RECORDED IS
 OVER 90 DAYS OLD REQUIRING THE DOCUMENT TO BE
 RE-RECORDED. FL S S713.13NOTICE OF COMMENCEMENT, TO
 BE FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID.NOTE:
 713.13(6)THE POSTING OF THE NOTICE OFCOMMENCEMENT
 AT THE CONSTRUCTIONSITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4 COMPLIED.
 5) COMPLIED.
  
 6A) CS-1 PLAN REVIEW DATA HAS PARTIALLY COMPLIED WITH
 THIS REQUEST. CS-1 STILL HAS THE STATEMENT THAT THIS
 BUILDING COMPLIES WITH 507.2 UNLIMITED AREA, THIS IS
 NOT TRUE.
 THE AREA INCREASES TAKEN ALSO DO NOT MAKE IT CLEAR IF
 THIS IS FOR THE NEW METAL BUILDING OR FOR THE BUILDING
 (2) ON THE SITE. PLEASE CORRECT THIS WITH EXISTING
 BUILDING INFORMATION AND NEW BUILDING INFORMATION.
  
 6B) SHEET A-1 REVISION# 2 DOES INDICATE LANGUAGE OF A 3
 HR RATED WALL AND THERE IS A CUT SECTION OF THIS
 PORTION OF BUILDING THAT REFERENCES DETAIL6 ON SHEET
 A6. THIS DETAIL SHOULD BE OF THE 3 HR RATED WALL BUT WE
 SEE AN EXISTING STEEL BEAM AND NO FIRE RATING AS
 REQUIRED IN TABLE 715.3.
 6C)SHEET A1& A2 INDICATES A DOOR # 5 AS A 1 ? HR
 RATED OPENING PLEASE SEE TABLE 715.3 FOR A 3 HR RATED
 FIRE WALL A 3 HR RATED DOOR IS ALSO REQUIRED. DOOR # 2
 WOULD ALSO REQUIRE
 A 3HR FIRE RATING PLEASE PROVIDE DOCUMENTATION FOR
 BOTH.
  
 7)THIRD REQUEST,PLEASECLARIFY, IF THIS IS AN
 ADDITION THEN THE 2006 FBC ,EXISTING BUILDING CODE
 CHAPTER 9 NEEDS TO BE ADDRESSES UNDER THE PLAN REVIEW
 DATA AS WELL AS IN THE EXISTING BUILDING WORK IS ALSO
 TO BE COMPLETED UNDER THIS PERMIT, INDICATE TO WHAT
 LEVEL OR CLASSIFICATION OF WORK IS TO BE COMPLETED
 UNDER THIS PERMIT, PLEASE SEE THE 2004 EXISTING
 BUILDING CODE 2004 FOR THE RENOVATION PORTION OF THIS
 PROJECT, SEE CHAPTER (3).SHEET SP-1 INDICATES WORK
 NOT IN CONTRACT BUT THIS SAME SHEET INDICATES NEW FIRE
 SPRINKLER PUMP ROOM, NEW ADA RESTROOMS, EXISTING BAY
 DOOR TO BE REPLACED, AND ADA RAMP AND ACCESSIBLE
 SIDEWALK? IF THE BUILDING INFORMATION IN COMMENT # 6 IS
 CORRECTED THIS COMMENT WILLBE SATISFIED.
  
 8)COMPLIED.
  
 9) THIS COMMENT AGAIN WOULD DEAL WITH COMMENT NUMBER 6,
 WE WILL NEED THE FOLLOWING INFORMATION FOR BOTH
 BUILDINGS. 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR
 CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT
 WAS DESIGNED. ADD INFORMATION FOR THE REMODEL PORTION
 OF THIS PROJECT.
  
 B10) BUILDINGPROVISO, 109.3.10.1 HURRICANE
 PROTECTION.
  
 11) THIS WILL BE A BUILDING PROVISO109.3.10* IMPACT
 OF CONSTRUCTION.
  
 12) COMPLIED
  
 13) COMPLIED
  
 14A) 2ND REQUEST, THE BUILDING IS DESIGNED AS AN
 ENCLOSED STRUCTURE ALL PRODUCT APPROVALS ARE REQUIRED
 BEFORE THE PERMIT CAN BE ISSUED.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF
 PRODUCT TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A)HOLLOW METAL EXTERIOR DOORS- NO REPORT SUBMITTED
 B) OVERHEAD DOORS: NOT ILLEGIBLE WILL REQUIRE FLORIDA
 COVERSHEET.
 C) PANEL WALLS: SIDING AND OR WALL LOUVERS- NO REPORT
 SUBMITTED
 D) ROOF ASSEMBLIES : METAL ROOFING ? NO REPORT
 SUBMITTED
  
 14B)3RD REQUEST, THE BUILDING IS DESIGNED AS AN
 ENCLOSED STRUCTURE ALL PRODUCT APPROVALS ARE REQUIRED
 BEFORE THE PERMIT CAN BE ISSUED.PRODUCT APPROVALS
 SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE ATWWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED
 WITH A COVER SHEET THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR LOCAL
 PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 14C)2ND REQUEST, THE BUILDING IS DESIGNED AS AN
 ENCLOSED STRUCTURE ALL PRODUCT APPROVALS ARE REQUIRED
 BEFORE THE PERMIT CAN BE ISSUED.WPB ADMIN CODE
 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 15) COMPLIED
  
 16) THIS SAME SHEET A-1 LOADING DOCK INDICATES A
 SECTION "B"/ A4, IT APPEARS THIS SECTION
 THE DETAIL 4 ON SHEET A-7 IS A 4 HR RATED FLOOR CEILING
 ASSEMBLY. THIS IS A FLOOR CEILING ASSEMBLY PLEASE
 PROVIDE TO WHAT LIVE LOAD THIS FLOOR WILL BE DESIGNED
 TO, PLEASE SEE TABLE 1607.1.
  
 17-24)COMPLIED
  
 25) LOW VALUE, FOR THE ADDITION ALONE THE CALCULATED
 VALUE IS $4,391, 656.00 THE PERMIT FEES WILL BE
 ASSESSED ON THIS DOLLAR AMOUNT
  
 26)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 27) NEW COMMENT, THE LIGHT POLE CALCULATIONS DO HAVE A
 RAISED SEAL BUT A COPIED SIGNATURE. 61G15-23.002(2) FL.
 ADMIN. CODE. PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE: NAME, ADDRESS AND
 LICENSE NUMBER OF THE ENGINEER OR, THE NAME AND LICENSE
 NUMBER OF THE ENGINEER AND THE NAME, ADDRESS AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS THROUGH WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]