| 2007-08-24 08:09:58 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINSTRATIVE CODE |
| | FLORIDA STATUES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SURVEY SHEET REQUIRES THE ORIGINAL SIGNATURE. |
| | SIGNATURE IS A PHOTO-COPY. FAC 61G1-17.002 & FS |
| | 472.025.-THE TITLE BLOCK ADDRESS "OLD" OKEECHOBEE |
| | ROAD DOES NOT REFLECT THE DBPR WEBSITE SHOWING THE |
| | CORRECT ADDRESS OKEECHOBEE ROAD. THE COUNTY (PAPA) DOES |
| | NOT RECOGNIZE "OLD" OKEECHOBEE ROAD, NOR DOES THE CITY |
| | WPB'S ADDRESSING SYSTEM. PLEASE CHANGE THE TITLE BLOCK |
| | TO REFLECT THE CORRECT ADDRESS.-"OLD" OKEECHOBEE IS |
| | ALSO SHOWN IN THE DBPR WEBSITE FOR THE BUSINESS LICENSE |
| | (CERTIFICATE OF AUTHORIZATION) NUMBER. PLEASE SUBMIT AN |
| | ADDRESS CORRECTION TO DBPR WEBSITE INDICATING THE |
| | CORRECT ADDRESS OF OKEECHOBEE ROAD. |
| | ****RESPONSE NOTED, BUT THE ADDRESS ON THE TITLE BLOCK |
| | HAS NOT BEEN CHANGED. |
| | |
| | 2. OK |
| | |
| | 3. ALL CIVIL SHEETS REQUIRE THE BUSINESS LICENSE, |
| | (CERTIFICATE OF AUTHORIZATION), IN THE TITLE BLOCK OF |
| | ARCHITECTURAL ALLIANCE. (SEE ATTACHED SHEET FROM DBPR). |
| | --THE SIGNATURE IS REQUIRED WHEN THE SEAL IS AFFIXED |
| | TO THE DOCUMENTS. IT APPEARS THAT INITIALS WERE USED |
| | WHICH IS NOT APPROVED. IF INDEED THIS IS THE LEGAL |
| | SIGNATURE, THEN A SIGNED, SEALED, NOTORIZED LETTER |
| | SHALL BE SUBMITTED FOR OUR FILES INDICATING THE LEGAL |
| | SIGNATURE. FAC 61G1-16.003, 61G1-16.004(5) & FS |
| | 481.219, 481.2055. |
| | ****RESPONSE NOTED, BUT ARCHITECTURAL ALLIANCE IS STILL |
| | SHOWN ON SOME SHEETS, (CS-1, LD-1 & L-1). CHECK ALL |
| | SHEETS. NO LETTER HAS BEEN SUBMITTED FOR SIGNATURE |
| | VERIFICATION. |
| | |
| | 4. SHT L-1 THE SIGNATURE IS REQUIRED WHEN THE SEAL IS |
| | AFFIXED TO THE DOCUMENT. IT APPEARS THAT INITIALS WERE |
| | USED WHICH IS NOT APPROVED. IF INDEED THIS IS THE LEGAL |
| | SIGNATURE, THEN A SIGNED, SEALED, NOTORIZED LETTER |
| | SHALL BE SUBMITTED FOR OUR FILES INDICATING THE LEGAL |
| | SIGNATURE. FAC 61G1-16.003, 61G1-16.004(5) & FS |
| | 481.219, 481.2055. |
| | ****RESPONSE NOTED, BUT NO LETTER HAS BEEN SUBMITTED |
| | FOR SIGNATURE VERIFICATION. |
| | |
| | 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES 1004.1.2 & 403.1. SHOW THE TOTAL SQUARE FOOTAGE |
| | FOR EACH OCCUPANCY. |
| | ****RESPONSE NOTED, BUT TWO DRINKING FOUNTAINS ARE |
| | REQUIRED. ONE FOR THE STORAGE OCCUPANCY WAS NOT |
| | INDICATED IN THE CALCULATIONS FOR MINIMUM FACILITIES. |
| | SEE TABLE 403.1. |
| | |
| | 6. SHT A-1 KEY PLAN SHOWS A NEW TOILET ROOM AND SERVICE |
| | SINK LOCATION IN THE EXISTING BUILDING. PREVIOUS SHEETS |
| | INDICATE, " EXISTING BUILDING NOT IN CONTRACT", AND THE |
| | APPLICATION DOES NOT MENTION REMODEL OF EXISTING |
| | BUILLDING. PLEASE CLARIFY. APPLICATION REQUIRES A |
| | DESCRIPTION IN DETAIL OF THE PROJECT. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE APPLICATION HAS NOT BEEN |
| | UPDATED. |
| | |
| | 7. SHT A-4 SUBMIT CALCULATIONS FOR THE EXISTING ROOF. |
| | THERE WILL BE ADDITIONAL SQUARE FOOTAGE ADDED TO THE |
| | EXISTING ROOF WITH 1/2 THE AREA OF THE VERTICAL WALL OF |
| | THE NEW ADDITION CONTRIBUTING TO THE EXISTING ROOF |
| | DRAINS ADJACENT TO THE ADDITION. SHOW THE SQUARE |
| | FOOTAGE BEING DRAINED BY THE ROOF DRAINS PRIOR TO AND |
| | AFTER THIS NEW CONTRIBUTION. SUBMIT AN EXISTING ROOF |
| | PLAN TO SCALE AS WELL AS AN ELEVATION SHOWING THE |
| | HEIGHT OF ALL PARAPETS IN ORDER TO VERIFY ALL |
| | CALCULATIONS. INDICATE THE SIZE OF THE EXISTING RWL'S |
| | AND ASSOCIATED PIPING FOR THE EXISTING STORM SYSTEM. |
| | TABLE 1106.3 AND SECTIONS 1106.2, 1106.4. ALSO INDICATE |
| | THE SIZE OF THE SECONDARY ROOF DRAINS, OR OVERFLOW |
| | SCUPPERS ON THE EXISTING ROOF TO VERIFY THAT THEY ARE |
| | SUFFICIENT TO HANDLE THE NEW SQUARE FOOTAGE ADDED TO |
| | THE EXISTING ROOF. SECTION 1107.3. |
| | ****RESPONSE NOTED, BUT NO CALCULATIONS WERE SUBMITTED |
| | INDICATING THE SQUARE FOOTAGE ADDED TO THE EXISTING |
| | ROOF, THE TOTAL SQUARE FOOTAGE BEING DRAINED TO THE |
| | SECTION OF ROOF ADJACENT TO THE NEW BUILDING, DOWNSPOUT |
| | SIZE, LOCATION OF DOWNSPOUTS, TOTAL GUTTER AREA TO |
| | EXISTING AFFECTED DOWNSPOUTS ETC. SECTIONS 1106.2 & |
| | 1106.4 AND TABLES 1106.3 & 1106.6. |
| | |
| | 8. OK |
| | 9. OK |
| | |
| | 10. ALL MEP SHEETS THE SIGNATURE IS REQUIRED WHEN |
| | SEALING DOCUMENTS. 61G15-23.002(1)(2 & FS 471.025. |
| | ****RESPONSE NOTED, BUT ONLY THE ELECTRICAL SHEETS |
| | COMPLY. |
| | |
| | 11. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. PER SECTION 904.2 EXISTING BUILDING CODE, "AN |
| | ADDITION THAT AFFECTS THE ACCESSIBLIITY TO, OR CONTAINS |
| | AN AREA OF, PRIMARY FUNCTION SHALL COMPLY WITH THE |
| | REQUIREMENTS IN CHAPTER 11 OF THE FLORIDA BUILDING |
| | CODE, BUILDING". SINCE THE FIXTURES FOR THE ADDITION |
| | ARE TO BE IN THE EXISTING BUILDING, AND SERVE AS THE |
| | PRIMARY FUNCTION AREA OF THE ADDITION, THE TOILET ROOMS |
| | IN THE EXISTING BUILDING SHALL COMPLY WITH CHAPTER 11 |
| | OF THE BUILDING CODE AND SHALL BE ACCESSIBLE. PLEASE |
| | SUBMIT A DETAIL FOR THE EXISTING TOILET ROOMS TO SHOW |
| | COMPLIANCE WITH SECTION 11-4.22. |
| | |
| | 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONALS AND FS 553.80(2)(B). THIS IS GIVEN AS A |
| | NOTICE ONLY AT THIS TIME. |
| | |
| | REVIEW BY KEN STEVENS |