Plan Review Notes For Permit 07030559
Permit Number 07030559
Review Stop M
Sequence Number 2
Notes
Date Text
2007-08-03 11:22:091ST RESUMITTAL
 ACTION: DENIED
  
 FBC,M 2004 W/ 2005 AND 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESOPND WITH
 PREVIOUS COMMENTS FOR CONTINUITY.
  
 1. DESIGNER'S REPONSE: "ENGINEER'S FULL SIGNATURE
 MATCHES SIGNATURE ON FILE."
 THE ENGINEER'S FULL SIGNATURE MAY MATCH THE SIGNATURE
 ON FILE, BUT THE ENGINEER'S FULL SIGNATURE AS
 PREVIOUSLY SUBMITTED TO THIS OFFICE WAS NOT PROVIDED ON
 PLANS. PLEASE CORRECT AND RESUBMIT.
  
 2. OK
  
 3. DESIGNER'S RESPONSE: "BY ARCHITECT."
 THE LADDER FOR PERMANENT ACCESS APPEARS TO BE FROM THE
 LOW ROOF ON EXISTING BUILDING TO THE HIGH ROOF ON THE
 NEW BUILDING. THIS DOES NOT MEET THE INTENT OF FBC,M
 306.5. IT STATES "...A PERMANENT MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES' LEVEL SERVICE SPACE."
 THERE IS NO EXCEPTION GIVEN FOR ACCESS FROM A LOWER
 ROOF LEVEL ONLY. IF THERE IS PERMANENT ACCESS TO THE
 LOWER ROOF LEVEL AND THE UPPER ROOF LEVEL, THEN THE
 INTENT - AND REQUIREMENT - OF THIS CODE SECTION HAS
 BEEN SATISFIED. PLEASE SHOW ON PLANS A PERMANENT MEANS
 OF ACCESS WHICH STARTS AT GRADE LEVEL.
  
 4. OK
  
 5. OK
  