| 2007-08-03 11:22:09 | 1ST RESUMITTAL |
| | ACTION: DENIED |
| | |
| | FBC,M 2004 W/ 2005 AND 2006 REVISIONS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESOPND WITH |
| | PREVIOUS COMMENTS FOR CONTINUITY. |
| | |
| | 1. DESIGNER'S REPONSE: "ENGINEER'S FULL SIGNATURE |
| | MATCHES SIGNATURE ON FILE." |
| | THE ENGINEER'S FULL SIGNATURE MAY MATCH THE SIGNATURE |
| | ON FILE, BUT THE ENGINEER'S FULL SIGNATURE AS |
| | PREVIOUSLY SUBMITTED TO THIS OFFICE WAS NOT PROVIDED ON |
| | PLANS. PLEASE CORRECT AND RESUBMIT. |
| | |
| | 2. OK |
| | |
| | 3. DESIGNER'S RESPONSE: "BY ARCHITECT." |
| | THE LADDER FOR PERMANENT ACCESS APPEARS TO BE FROM THE |
| | LOW ROOF ON EXISTING BUILDING TO THE HIGH ROOF ON THE |
| | NEW BUILDING. THIS DOES NOT MEET THE INTENT OF FBC,M |
| | 306.5. IT STATES "...A PERMANENT MEANS OF ACCESS, THE |
| | EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| | THE EQUIPMENT AND APPLIANCES' LEVEL SERVICE SPACE." |
| | THERE IS NO EXCEPTION GIVEN FOR ACCESS FROM A LOWER |
| | ROOF LEVEL ONLY. IF THERE IS PERMANENT ACCESS TO THE |
| | LOWER ROOF LEVEL AND THE UPPER ROOF LEVEL, THEN THE |
| | INTENT - AND REQUIREMENT - OF THIS CODE SECTION HAS |
| | BEEN SATISFIED. PLEASE SHOW ON PLANS A PERMANENT MEANS |
| | OF ACCESS WHICH STARTS AT GRADE LEVEL. |
| | |
| | 4. OK |
| | |
| | 5. OK |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |