| Plan Review Notes For Permit 07030559 |
| Permit Number |
07030559 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-09-04 11:02:00 | *****DENIED***** | | | THE FOLLOWING COMMENTS TASKEN FROM THE PREVIOUS FIRE | | | REVIEW STILL NEED TO BE ADDRESSED; | | | | | | | | | 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED.ON SHEET CS-1, ONLY NFPA 101 SHOULD BE | | | LISTED AS A LIFE SAFETY CODE | | | | | | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.THIS | | | CODE SHOULD BE LISTED, BUT NOT AS LIFE SAFETY | | | | | | 09.PLEASE PROVIDE EMEGENCY LIGHTING DETAIL FOR THE | | | PROPOSED STRUCTURE.PROVIDE INFORMATION THAT THE | | | PROPOSED LIGHTS (WITH QUARTZ RESTRIKE FED VIA UPS | | | SYSTEM) ARE IN ACCORDANCE AND PERFORMANCE FOR EMERGENCY | | | LIGHTING AS PER 7.9 OF NFPA 101. | | | | | | 11.PLEASE INDICATE THE MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS IN TERMS OF CLASS | | | A, CLASS B, OR CLASS C IN EXITS, EXIT CORRIDORS, AND | | | ALL OTHER SPACES. PLEASE INDICATE ON AN APPROPIATE PLAN | | | SHEET | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|