| Date |
Text |
| 2007-07-18 12:13:35 | 2007-07-18 12:13:35 |
| | |
| | ****** UNSAT2ND REVIEW ***** |
| | |
| | ** PLEASE SEE THAT THERE ARE COMMENTS FROM PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. |
| | |
| | ** PLEASE SEE THERE ARE SOME COMPLETELY NEW COMMENTS AS |
| | THERE HAVE BEEN MANY CHANGES TO THE ELECTRICAL RISER |
| | DIAGRAM. |
| | |
| | |
| | |
| | 1) NOTE:PLEASE SEE PREVIOUS REVIEW NOTE WITH RESPECT |
| | TO CODES REQUIRED. PLEASE SEE SOME OF THESE WERE ADDED |
| | TO THE COVER SHEET HOWEVER NOT ON THE TRADE SHEETS ALSO |
| | AS NEEDED. |
| | PLEASE SEE THE COVER SHEET INDICATE 2005 NFPA-70, THEN |
| | WHERE THE PLANS MENTIONS NATIONAL ELECTRICAL CODE IT |
| | SAYS *LATEST EDITION*? |
| | PLEASE SEE THE CODE BELOW ARE REQUIRED FOR RELEVANT |
| | SHEETS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THAT PLANS HAVE BEEN SUBMITTED FOR PERMIT |
| | AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECT UNDER THE |
| | NEW CODES. |
| | PLEASE SEE THE FOLLOWING SHALL BE STATED ON THE |
| | ARCHITECTURAL CS COVER SHEET. PLEASE ALSO BE SURE THE |
| | TRADES REFLECT THE CODES RELEVANT TO THEIR DESIGNS ON |
| | RESPECTIVE SHEETS. |
| | 2004 FBC W/ 2006 REVISIONS (ALL TRADES). |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | 2003 NFPA-20 |
| | |
| | |
| | 2) NOTE: PLEASE SEE THE TITLE BLOCKS FOR MANY OF THE |
| | SHEETS WHICH CONTAINS *ARCHITECTURAL ALLIANCE* ARE NOT |
| | CORRECTED.PLEASE SEE SOME SHEETS STILL INDICATE A |
| | *CERTIFICATE OF CORPORATION NUMBER WHICH WAS IN FACT |
| | THE OLD CERTIFICATE OF AUTHORIZATION NUMBER WHICH IS |
| | NOW NULL AND VOID WITH THE STATE. |
| | PLEASE SEE SOME S SHEETS, C SHEETS, L SHEETS ETC. |
| | PLEASE SEE THE ATTACHED PRINT OUT FROM THE DEPARTMENT |
| | OF BUSINESS AND PROFESSIONAL REGULATION WHICH SHOWS |
| | THIS. |
| | PLEASE SEE THAT THE LANDSCAPE SHEETS ARE ALSO NOT |
| | CORRECT. PLEASE SEE THE PRINTED LICENSE NUMBER FOR THE |
| | LANDSCAPE ARCHITECT IS NOT IN THE TITLE BLOCKS FOR THIS |
| | ARCHITECT. THE NUMBER IN THE INDIVIDUALS TITLE BLOCK IS |
| | ACTUALLY THAT OF THE LANDSCAPE FIRM. PLEASE SEE THE |
| | NUMBER AS LISTED FOR THE LANDSCAPE FIRM IS NOT VALID. |
| | PLEASE SEE AN ADDITIONAL PRINT OUT FROM DBPR WITH THE |
| | INFORMATION FOR LANDSCAPE FIRM AND NULL AND VOID |
| | LICENSE. |
| | PLEASE SEE THE SECTIONS BELOW WHICH WERE GIVEN ON THE |
| | PREVIOUS REVIEW. |
| | FAC 61G1-16.004,FLORIDA STATUTES 481.219 |
| | PLEASE SEE SEVERAL SHEETS IN BOTH SETS WHICH CONTAIN |
| | MISPRINTED INFORMATION. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WITH RESPECT |
| | TO FIRE SPRINKLER SHEETS AND THE INFORMATION NEEDED ON |
| | TITLE BLOCKS. PLEASE SEE THESE ARE STILL MISSING THE |
| | REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR SAID |
| | FIRM. PLEASE SEE THE RESPONSE FROM FS COMPANY MENTIONS |
| | INFORMATION PROVIDED. PLEASE SEE ONLY SOME OF THE |
| | INFORMATION FROM THE PREVIOUS REVIEW WAS DONE. |
| | *** PLEASE SEE THE RESPONSE LETTER FROM THE FIRE |
| | SPRINKLER COMPANY IS CONFUSING. PLEASE SEE THE RESPONSE |
| | IS ADDRESSED TO A CAPTAIN JAY WESTBROOKE AND REFERENCES |
| | A PROJECT LISTED AT 6751 DISCOVERY BLVD. PLEASE KNOW |
| | THE CITY OF WEST PALM BEACH DOES NOT HAVE EITHER OF THE |
| | ABOVE. PLEASE SEE MOST OF THE RESPONSES SEEM TO BE |
| | RELEVANT TO THE ELECTRICAL REVIEW AND FIRE REVIEW, BUT |
| | SOME DO NOT. |
| | PLEASE PROVIDE ANY RESPONSE LETTERS TO THIS AHJ FOR |
| | THESE REVIEW COMMENTS. |
| | THIS SEEMS TO HAVE BEEN MIXED UP WITH ANOTHER PROJECT |
| | THAT PERHAPS THIS FIRM IS WORKING ON?? |
| | PLEASE SEE COMMENTS BELOW WITH RESPECT TO FIRE PUMP AND |
| | REVIEW NOTES. |
| | PLEASE SEE FAC 61G15-23.002, FS 471.023 |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #8 WHICH IS |
| | BELOW REQUESTED FOR THE MANUFACTURES SPECS/CUT SHEETS |
| | TO BE SUBMITTED FOR THE FIRE PUMP, FIRE PUMP CONTROLLER |
| | ETC, YET NO INFORMATION WAS SUBMITTED.? |
| | PLEASE SEE THE RESPONSE FROM THE FS DESIGNER MENTIONS |
| | THIS IS TO BE PROVIDED HOWEVER NO INFORMATION WAS |
| | SUBMITTED? |
| | PLEASE SEE NO INFORMATION WAS SUBMITTED FOR THE TIMES |
| | AND FUEL CONSUMPTION ETC COULD BE LOCATED ON FS PLANS. |
| | THE PREVIOUS NOTE IS BEING LEFT BELOW FOR INFORMATION |
| | NEEDED AND AS STATED ON PREVIOUS REVIEW. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR |
| | THE FIRE PUMP. PLEASE SEE NFPA-20 2003. 110.3, 90.7. |
| | CHAPTER 11 AND 12 OF NFPA-20 |
| | FBC 106.1.2 |
| | PLEASE SEE MINIMUM TIME, FUEL CONSUMPTION IS TO BE |
| | STATED ON PLANS. THIS MAY ALSO BE IN FIRE REVIEWS |
| | COMMENTS. |
| | AS SHOWN DIESEL DRIVEN AND THE AMOUNT OF FUEL REQUIRED |
| | WHICH EQUALS 1GAL PER HP PER HOUR PLUS 5% FOR SUMP AND |
| | 5% FOR EXPANSION. PLEASE SEE THE FOLLOWING THE CODE. |
| | 11.4.3.1 FUEL SUPPLY TANK(S) SHALL HAVE A CAPACITY AT |
| | LEAST EQUAL TO 5.07 L PER KW (1 GAL PER HP), PLUS 5 |
| | PERCENT VOLUME FOR EXPANSION AND 5 PERCENT VOLUME FOR |
| | SUMP AND THE COMMENTARY SECTION AS FOLLOWS. |
| | |
| | 5) NOTE: PLEASE SEE PLANS HAVE NOW BEEN CORRECTED FOR |
| | CORRECT WIND LOADS ON POLES HOWEVER PLANS AND |
| | SUPPORTING DOCUMENTS DO NOT CONTAIN ANY INFORMATION FOR |
| | POLES, EFFECTIVE PROJECTED AREA (EFA) AND CALCULATIONS |
| | AS NEED FOR REVIEW. |
| | EVEN IF THIS INFORMATION FOR WIND LOAD CALCULATIONS IS |
| | NOT DIRECTLY DONE BY KAMM CONSULTING. |
| | PLEASE PROVIDE: FBC 106.1.2 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | ** PLANS INDICATE WIND LOADS FOR LIGHT POLES AT |
| | 120MPH? |
| | PLEASE ALSO SEE SETS CONTAIN A SHEET WITH NO NUMERICAL |
| | DESIGNATION WHICH APPEARS TO BE THE SAME AS SHEET E1.1? |
| | PLEASE VERIFY AND REMOVE AS NEEDED. |
| | * PLEASE PROVIDE ALL MINIMUM WIND LOADING FOR SITE |
| | LIGHTING LIGHT POLES, AND THAT OF THE POLES ON GARAGE |
| | ROOF STRUCTURE. PLEASE KNOW A DETAIL ON HOW THESE WILL |
| | BE ATTACHED ON PARKING DECK OF THE GARAGE AND POLE |
| | DETAIL FOR GROUND MOUNTED/BURIED POLES WILL BE |
| | REQUIRED. PLEASE KNOW ALL SHOW MEET THE FBC 140MPH |
| | (3SEC GUST) 120MPH SUSTAINED. |
| | |
| | THE STRUCTURAL CALCULATIONS WILL BE REVIEWED BY THE |
| | BUILDING PLAN REVIEWER. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 6) NOTE:PLEASE SEE RISER IS NOW SHOWING AN *EQUIPMENT |
| | GROUNDING CONDUCTOR* TO THE FIRST MEANS OF DISCONNECT |
| | AS SHOWN FOR NEW MAIN FOUR. PLEASE SEE 250.6 AND 250.24 |
| | AS THIS IS NOT PERMITTED AND CREATES OBJECTIONABLE |
| | CURRENTS. |
| | |
| | 7) NOTE:PLEASE SEE NOT ENOUGH INFORMATION FOR |
| | REQUIRED FBC CHAPTER 13 LIGHTING CONTROLS ETC WAS |
| | SUBMITTED. |
| | PLEASE SEE RESPONSE LETTER MENTIONS THIS WILL BE DONE |
| | LATER UNDER A SEPARATE PERMIT HOWEVER THE BASE BUILDING |
| | WILL BE REQUIRE TO SHOW MINIMUM CODE COMPLIANCE AT THIS |
| | TIME. PLEASE SEE THAT THE OTHER WORK MAY OR MAY NOT BE |
| | PERMITTED AND WHEN THIS WORK IS PERMITTED IS NOT KNOWN |
| | OR CONFIRMED ETC. |
| | PLEASE KNOW THE MINIMUM AS DESIGNED AND REQUIRED CAN |
| | ALWAYS BE REVISED AT A LATER DATE. |
| | PLEASE SEE THAT PLANS STATE A NOTE THAT THE LIGHTING |
| | PERFORMANCE MEETS 13-415.2. PLEASE KNOW THAT PLANS |
| | SHALL NOT CONTAIN NOTES WHICH STATE CODES, DESIGNS ETC |
| | IN LIEU OF REQUIRED MINIMUM DESIGNS AND INFORMATION |
| | NEEDED ON PLANS. |
| | PLEASE SHOW AND INDICATE METHODS FOR THE CALCULATIONS. |
| | PLEASE SHOW THE ALLOWANCES, DESIGNS ETC. PLEASE SEE |
| | THIS INCLUDES EXTERIOR LIGHTING AS WELL. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1.3 |
| | |
| | ** PREVIOUS REVIEW NOTE FOR REFERENCE** |
| | PLEASE SEE THE 2004 FBC W/ 2006 REVISIONS FOR CHAPTER |
| | 13. AT THIS TIME THERE ARE SEVERAL ITEMS MISSING FOR |
| | REVIEW. |
| | PLEASE SEE NO SCHEDULING OF SYSTEM WAS SUBMITTED. |
| | PLEASE SEE NO INFORMATION ON A SYSTEM WAS SUBMITTED. |
| | PLEASE SEE NO OVER RIDE DEVICES AT THE POINTS OF |
| | EGRESS/INGRESS INTO SPACE FROM ENTRANCE WIN WHICH THE |
| | OCCUPANT CAN SEE THE LIGHTING WHICH IS BEING |
| | CONTROLLED. |
| | PLEASE SEE NO TIMES ON ANY OVER RIDE DEVICES AND TYPES |
| | OF DEVICES. |
| | PLEASE SEE MISSING ENERGY CALCULATIONS. |
| | PLEASE SEE MISSING LIGHTING PERFORMANCE CALCULATIONS. |
| | PLEASE SEE MISSING CERTIFICATIONS PER DESIGNER(S) OF |
| | RECORD. |
| | PLEASE SEE MISSING VOLTAGE DROP CALCULATIONS FOR |
| | LONGEST RUNS. |
| | PLEASE SEE 13-103.1, 13-415.1ABC.1, 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3, 13-415.1.AB.1.1, 13-415.1..A, .B AND .C, |
| | 13-415.2 AND TABLES UNDER THE NEW 2006 REVISIONS. ETC. |
| | |
| | 8) NOTE:PLEASE SEE PREVIOUS NOTE WITH RESPECT TO |
| | EGRESS LIGHTING. PLEASE SEE THERE ARE LIGHTING LEVELS |
| | SUBMITTED BACK HOWEVER PLEASE SEE THE LEVELS FOR STAIRS |
| | COULD NOT BE LOCATED AS THE LIFE SAFETY CODE REQUIRES |
| | 10FCS UNDER NORMAL AND THEN PERMITS AN AVERAGE DOWN TO |
| | 1FC UNDER EMERGENCY CONDITIONS. PLEASE SEE THAT THIS IS |
| | REQUIRED FOR EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. |
| | PLEASE SEE NFPA-101 7.8, 7.9. 7.8.1.3, 7.9.2.2 |
| | |
| | 9) NOTE: PLEASE SEE RESPONSE FOR PREVIOUS NOTE #15 |
| | MENTIONS CUT SHEETS AND SPECS TO BE PROVIDED HOWEVER |
| | NONE WERE SUBMITTED. |
| | PLEASE SEE THE PREVIOUS REVIEW NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE CIRCUITING ON PLANS. PLEASE SEE |
| | 700.12F FOR CIRCUITING OF EMERGENCY LIGHTING AND EXIT |
| | LIGHTING. EXCEPTIONS ARE PERMITTED HOWEVER AT THIS TIME |
| | NOT ENOUGH INFORMATION IS PROVIDED FOR THE LIGHTING. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS ON THE |
| | PROPOSED UPSE. |
| | 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE PREVIOUS NOTE #17 AS THIS REQUIRED |
| | ALL CONTINUOUS LOADS TO BE SHOWN AT 125%. THIS COULD |
| | NOT BE LOCATED ON PLANS AND NOT ON THE SHEET WHICH |
| | RESPONSE LETTER MENTIONS TO SEE. (5.1) |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SHOW ALL CONTINUOUS LOADS AT 125%. 215.3, |
| | 230.42 |
| | |
| | 11) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTE #19. AS |
| | THIS WAS RESPONDED BY THE FIRE SPRINKLER DESIGNER WHICH |
| | STATED A RESPONSE HOWEVER PLEASE PROVIDE THE MINIMUM |
| | INFORMATION ON THE FS PLANS. PLEASE SEE COMMENTS ABOVE |
| | WITH RESPECT TO OTHER INFORMATION NEEDED ON THESE SAME |
| | PLANS. |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE PROVIDE MORE INFORMATION FOR THE FIRE PUMP ROOM |
| | AS REQUIRED PER NFPA-20 CHAPTER 5. 5.12.5 FOR |
| | VENTILATION. |
| | 5.12.6* DRAINAGE. |
| | 5.12.6.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE |
| | OF ESCAPING WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS |
| | THE PUMP, DRIVER, CONTROLLER, AND SO FORTH. |
| | 11.3.1 PUMP ROOM DRAINAGE. THE FLOOR OR SURFACE AROUND |
| | THE PUMP AND ENGINE SHALL BE PITCHED FOR ADEQUATE |
| | DRAINAGE OF ESCAPING WATER AWAY FROM CRITICAL |
| | EQUIPMENT, SUCH AS PUMP, ENGINE, CONTROLLER, FUEL TANK, |
| | AND SO FORTH. |
| | 11.3.2* VENTILATION. |
| | 11.3.2.1 VENTILATION SHALL BE PROVIDED FOR THE |
| | FOLLOWING FUNCTIONS: |
| | (1)TO CONTROL THE MAXIMUM TEMPERATURE TO 49?C |
| | (120?F) AT THE COMBUSTION AIR CLEANER INLET WITH ENGINE |
| | RUNNING AT RATED LOAD |
| | (2)TO SUPPLY AIR FOR ENGINE COMBUSTION |
| | (3)TO REMOVE ANY HAZARDOUS VAPORS |
| | (4)TO SUPPLY AND EXHAUST AIR AS NECESSARY FOR |
| | RADIATOR COOLING OF THE ENGINE WHEN REQUIRED |
| | |
| | 11.3.2.2 THE VENTILATION SYSTEM COMPONENTS SHALL BE |
| | COORDINATED WITH THE ENGINE OPERATION. |
| | 11.3.2.3* AIR SUPPLY VENTILATOR. |
| | 11.3.2.3.1 THE AIR SUPPLY VENTILATOR SHALL BE |
| | CONSIDERED TO INCLUDE ANYTHING IN THE AIR SUPPLY PATH |
| | TO THE ROOM. |
| | 11.3.2.3.2 THE TOTAL AIR SUPPLY PATH TO THE PUMP ROOM |
| | SHALL NOT RESTRICT THE FLOW OF THE AIR MORE THAN 5.1 MM |
| | WATER COLUMN (0.2 IN. WATER COLUMN). |
| | ETC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 12) NOTE: PLEASE SEE PANEL E IS BEING SHOWN AS 277/480V |
| | WHICH IS NOT POSSIBLE AS THIS IS BEING SHOWN BEING FED |
| | FROM A 120/240 DELTA SERVICE. DOES THE UPS EQUIPMENT |
| | CONTAIN A STEP UP TRANSFORMER? |
| | PLEASE SEE THE RISER SHEET NOTE FOR THE 15K UPS ONLY |
| | STATES 120/240 IN AND 120/240 OUT. |
| | PLEASE CLARIFY. |
| | |
| | 13) NOTE: PLEASE CLARIFY PANEL LB AS THIS PANEL IS |
| | BEING SHOWN AS 120/208V AND IS NOTED AS A DELTA PANEL? |
| | HOW IS THIS POSSIBLE? |
| | PLEASE COORDINATE> |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 14) NOTE: PLEASE SEE PLANS INDICATE *HASH* LINES FOR |
| | AREAS WHERE THERE IS NOT SUPPOSE TO BE ANY WORK OR AT |
| | LEAST THAT IS WHAT PLANS INDICATES. PLEASE SEE AREAS |
| | WHERE NEW PANELS AND EQUIPMENT IS BEING ADDED SHOULD |
| | NOT CONTAIN ANY (HASHED LINES) AS THESE AREAS DO |
| | INCLUDE SEVERAL ITEMS OF NEW ELECTRICAL EQUIPMENT ETC. |
| | PLEASE ADJUST PLANS FOR THESE AREAS WHERE WORK IS BEING |
| | DONE. |
| | FBC 106.1. |
| | |
| | 15) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) IS |
| | BEING GIVEN AS SOME OF THE COMMENTS ARE BEING REPEATED |
| | FROM PREVIOUS REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-18 07:04:31 | 2007-07-18 07:04:31 |
| | PLANS REMOVED FROM INCOMING AND IN ELECTRICAL FOR |
| | REVIEW. PLANS WILL RETURN TO INCOMING WAITING FOR COMM |
| | BOARD WHEN REVIEW IS COMPLETED. |