Plan Review Notes
Plan Review Notes For Permit 07030559
Permit Number 07030559
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-18 12:13:352007-07-18 12:13:35
  
 ****** UNSAT2ND REVIEW *****
  
 ** PLEASE SEE THAT THERE ARE COMMENTS FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
  
 ** PLEASE SEE THERE ARE SOME COMPLETELY NEW COMMENTS AS
 THERE HAVE BEEN MANY CHANGES TO THE ELECTRICAL RISER
 DIAGRAM.
  
  
  
 1) NOTE:PLEASE SEE PREVIOUS REVIEW NOTE WITH RESPECT
 TO CODES REQUIRED. PLEASE SEE SOME OF THESE WERE ADDED
 TO THE COVER SHEET HOWEVER NOT ON THE TRADE SHEETS ALSO
 AS NEEDED.
 PLEASE SEE THE COVER SHEET INDICATE 2005 NFPA-70, THEN
 WHERE THE PLANS MENTIONS NATIONAL ELECTRICAL CODE IT
 SAYS *LATEST EDITION*?
 PLEASE SEE THE CODE BELOW ARE REQUIRED FOR RELEVANT
 SHEETS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT PLANS HAVE BEEN SUBMITTED FOR PERMIT
 AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECT UNDER THE
 NEW CODES.
 PLEASE SEE THE FOLLOWING SHALL BE STATED ON THE
 ARCHITECTURAL CS COVER SHEET. PLEASE ALSO BE SURE THE
 TRADES REFLECT THE CODES RELEVANT TO THEIR DESIGNS ON
 RESPECTIVE SHEETS.
 2004 FBC W/ 2006 REVISIONS (ALL TRADES).
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2003 NFPA-20
  
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS FOR MANY OF THE
 SHEETS WHICH CONTAINS *ARCHITECTURAL ALLIANCE* ARE NOT
 CORRECTED.PLEASE SEE SOME SHEETS STILL INDICATE A
 *CERTIFICATE OF CORPORATION NUMBER WHICH WAS IN FACT
 THE OLD CERTIFICATE OF AUTHORIZATION NUMBER WHICH IS
 NOW NULL AND VOID WITH THE STATE.
 PLEASE SEE SOME S SHEETS, C SHEETS, L SHEETS ETC.
 PLEASE SEE THE ATTACHED PRINT OUT FROM THE DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATION WHICH SHOWS
 THIS.
 PLEASE SEE THAT THE LANDSCAPE SHEETS ARE ALSO NOT
 CORRECT. PLEASE SEE THE PRINTED LICENSE NUMBER FOR THE
 LANDSCAPE ARCHITECT IS NOT IN THE TITLE BLOCKS FOR THIS
 ARCHITECT. THE NUMBER IN THE INDIVIDUALS TITLE BLOCK IS
 ACTUALLY THAT OF THE LANDSCAPE FIRM. PLEASE SEE THE
 NUMBER AS LISTED FOR THE LANDSCAPE FIRM IS NOT VALID.
 PLEASE SEE AN ADDITIONAL PRINT OUT FROM DBPR WITH THE
 INFORMATION FOR LANDSCAPE FIRM AND NULL AND VOID
 LICENSE.
 PLEASE SEE THE SECTIONS BELOW WHICH WERE GIVEN ON THE
 PREVIOUS REVIEW.
 FAC 61G1-16.004,FLORIDA STATUTES 481.219
 PLEASE SEE SEVERAL SHEETS IN BOTH SETS WHICH CONTAIN
 MISPRINTED INFORMATION.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WITH RESPECT
 TO FIRE SPRINKLER SHEETS AND THE INFORMATION NEEDED ON
 TITLE BLOCKS. PLEASE SEE THESE ARE STILL MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR SAID
 FIRM. PLEASE SEE THE RESPONSE FROM FS COMPANY MENTIONS
 INFORMATION PROVIDED. PLEASE SEE ONLY SOME OF THE
 INFORMATION FROM THE PREVIOUS REVIEW WAS DONE.
 *** PLEASE SEE THE RESPONSE LETTER FROM THE FIRE
 SPRINKLER COMPANY IS CONFUSING. PLEASE SEE THE RESPONSE
 IS ADDRESSED TO A CAPTAIN JAY WESTBROOKE AND REFERENCES
 A PROJECT LISTED AT 6751 DISCOVERY BLVD. PLEASE KNOW
 THE CITY OF WEST PALM BEACH DOES NOT HAVE EITHER OF THE
 ABOVE. PLEASE SEE MOST OF THE RESPONSES SEEM TO BE
 RELEVANT TO THE ELECTRICAL REVIEW AND FIRE REVIEW, BUT
 SOME DO NOT.
 PLEASE PROVIDE ANY RESPONSE LETTERS TO THIS AHJ FOR
 THESE REVIEW COMMENTS.
 THIS SEEMS TO HAVE BEEN MIXED UP WITH ANOTHER PROJECT
 THAT PERHAPS THIS FIRM IS WORKING ON??
 PLEASE SEE COMMENTS BELOW WITH RESPECT TO FIRE PUMP AND
 REVIEW NOTES.
 PLEASE SEE FAC 61G15-23.002, FS 471.023
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #8 WHICH IS
 BELOW REQUESTED FOR THE MANUFACTURES SPECS/CUT SHEETS
 TO BE SUBMITTED FOR THE FIRE PUMP, FIRE PUMP CONTROLLER
 ETC, YET NO INFORMATION WAS SUBMITTED.?
 PLEASE SEE THE RESPONSE FROM THE FS DESIGNER MENTIONS
 THIS IS TO BE PROVIDED HOWEVER NO INFORMATION WAS
 SUBMITTED?
 PLEASE SEE NO INFORMATION WAS SUBMITTED FOR THE TIMES
 AND FUEL CONSUMPTION ETC COULD BE LOCATED ON FS PLANS.
 THE PREVIOUS NOTE IS BEING LEFT BELOW FOR INFORMATION
 NEEDED AND AS STATED ON PREVIOUS REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR
 THE FIRE PUMP. PLEASE SEE NFPA-20 2003. 110.3, 90.7.
 CHAPTER 11 AND 12 OF NFPA-20
 FBC 106.1.2
 PLEASE SEE MINIMUM TIME, FUEL CONSUMPTION IS TO BE
 STATED ON PLANS. THIS MAY ALSO BE IN FIRE REVIEWS
 COMMENTS.
 AS SHOWN DIESEL DRIVEN AND THE AMOUNT OF FUEL REQUIRED
 WHICH EQUALS 1GAL PER HP PER HOUR PLUS 5% FOR SUMP AND
 5% FOR EXPANSION. PLEASE SEE THE FOLLOWING THE CODE.
 11.4.3.1 FUEL SUPPLY TANK(S) SHALL HAVE A CAPACITY AT
 LEAST EQUAL TO 5.07 L PER KW (1 GAL PER HP), PLUS 5
 PERCENT VOLUME FOR EXPANSION AND 5 PERCENT VOLUME FOR
 SUMP AND THE COMMENTARY SECTION AS FOLLOWS.
  
 5) NOTE: PLEASE SEE PLANS HAVE NOW BEEN CORRECTED FOR
 CORRECT WIND LOADS ON POLES HOWEVER PLANS AND
 SUPPORTING DOCUMENTS DO NOT CONTAIN ANY INFORMATION FOR
 POLES, EFFECTIVE PROJECTED AREA (EFA) AND CALCULATIONS
 AS NEED FOR REVIEW.
 EVEN IF THIS INFORMATION FOR WIND LOAD CALCULATIONS IS
 NOT DIRECTLY DONE BY KAMM CONSULTING.
 PLEASE PROVIDE: FBC 106.1.2
  
 ** PREVIOUS REVIEW NOTE **
 ** PLANS INDICATE WIND LOADS FOR LIGHT POLES AT
 120MPH?
 PLEASE ALSO SEE SETS CONTAIN A SHEET WITH NO NUMERICAL
 DESIGNATION WHICH APPEARS TO BE THE SAME AS SHEET E1.1?
 PLEASE VERIFY AND REMOVE AS NEEDED.
 * PLEASE PROVIDE ALL MINIMUM WIND LOADING FOR SITE
 LIGHTING LIGHT POLES, AND THAT OF THE POLES ON GARAGE
 ROOF STRUCTURE. PLEASE KNOW A DETAIL ON HOW THESE WILL
 BE ATTACHED ON PARKING DECK OF THE GARAGE AND POLE
 DETAIL FOR GROUND MOUNTED/BURIED POLES WILL BE
 REQUIRED. PLEASE KNOW ALL SHOW MEET THE FBC 140MPH
 (3SEC GUST) 120MPH SUSTAINED.
  
 THE STRUCTURAL CALCULATIONS WILL BE REVIEWED BY THE
 BUILDING PLAN REVIEWER.
 FBC 106.1.2 ADMIN SECT.
  
 6) NOTE:PLEASE SEE RISER IS NOW SHOWING AN *EQUIPMENT
 GROUNDING CONDUCTOR* TO THE FIRST MEANS OF DISCONNECT
 AS SHOWN FOR NEW MAIN FOUR. PLEASE SEE 250.6 AND 250.24
 AS THIS IS NOT PERMITTED AND CREATES OBJECTIONABLE
 CURRENTS.
  
 7) NOTE:PLEASE SEE NOT ENOUGH INFORMATION FOR
 REQUIRED FBC CHAPTER 13 LIGHTING CONTROLS ETC WAS
 SUBMITTED.
 PLEASE SEE RESPONSE LETTER MENTIONS THIS WILL BE DONE
 LATER UNDER A SEPARATE PERMIT HOWEVER THE BASE BUILDING
 WILL BE REQUIRE TO SHOW MINIMUM CODE COMPLIANCE AT THIS
 TIME. PLEASE SEE THAT THE OTHER WORK MAY OR MAY NOT BE
 PERMITTED AND WHEN THIS WORK IS PERMITTED IS NOT KNOWN
 OR CONFIRMED ETC.
 PLEASE KNOW THE MINIMUM AS DESIGNED AND REQUIRED CAN
 ALWAYS BE REVISED AT A LATER DATE.
 PLEASE SEE THAT PLANS STATE A NOTE THAT THE LIGHTING
 PERFORMANCE MEETS 13-415.2. PLEASE KNOW THAT PLANS
 SHALL NOT CONTAIN NOTES WHICH STATE CODES, DESIGNS ETC
 IN LIEU OF REQUIRED MINIMUM DESIGNS AND INFORMATION
 NEEDED ON PLANS.
 PLEASE SHOW AND INDICATE METHODS FOR THE CALCULATIONS.
 PLEASE SHOW THE ALLOWANCES, DESIGNS ETC. PLEASE SEE
 THIS INCLUDES EXTERIOR LIGHTING AS WELL.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.3
  
 ** PREVIOUS REVIEW NOTE FOR REFERENCE**
 PLEASE SEE THE 2004 FBC W/ 2006 REVISIONS FOR CHAPTER
 13. AT THIS TIME THERE ARE SEVERAL ITEMS MISSING FOR
 REVIEW.
 PLEASE SEE NO SCHEDULING OF SYSTEM WAS SUBMITTED.
 PLEASE SEE NO INFORMATION ON A SYSTEM WAS SUBMITTED.
 PLEASE SEE NO OVER RIDE DEVICES AT THE POINTS OF
 EGRESS/INGRESS INTO SPACE FROM ENTRANCE WIN WHICH THE
 OCCUPANT CAN SEE THE LIGHTING WHICH IS BEING
 CONTROLLED.
 PLEASE SEE NO TIMES ON ANY OVER RIDE DEVICES AND TYPES
 OF DEVICES.
 PLEASE SEE MISSING ENERGY CALCULATIONS.
 PLEASE SEE MISSING LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE SEE MISSING CERTIFICATIONS PER DESIGNER(S) OF
 RECORD.
 PLEASE SEE MISSING VOLTAGE DROP CALCULATIONS FOR
 LONGEST RUNS.
 PLEASE SEE 13-103.1, 13-415.1ABC.1, 13-415.1.ABC.1.1,
 .1.2 AND .1.3, 13-415.1.AB.1.1, 13-415.1..A, .B AND .C,
 13-415.2 AND TABLES UNDER THE NEW 2006 REVISIONS. ETC.
  
 8) NOTE:PLEASE SEE PREVIOUS NOTE WITH RESPECT TO
 EGRESS LIGHTING. PLEASE SEE THERE ARE LIGHTING LEVELS
 SUBMITTED BACK HOWEVER PLEASE SEE THE LEVELS FOR STAIRS
 COULD NOT BE LOCATED AS THE LIFE SAFETY CODE REQUIRES
 10FCS UNDER NORMAL AND THEN PERMITS AN AVERAGE DOWN TO
 1FC UNDER EMERGENCY CONDITIONS. PLEASE SEE THAT THIS IS
 REQUIRED FOR EGRESS PATHS TO THE PUBLIC RIGHT OF WAY.
 PLEASE SEE NFPA-101 7.8, 7.9. 7.8.1.3, 7.9.2.2
  
 9) NOTE: PLEASE SEE RESPONSE FOR PREVIOUS NOTE #15
 MENTIONS CUT SHEETS AND SPECS TO BE PROVIDED HOWEVER
 NONE WERE SUBMITTED.
 PLEASE SEE THE PREVIOUS REVIEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE CIRCUITING ON PLANS. PLEASE SEE
 700.12F FOR CIRCUITING OF EMERGENCY LIGHTING AND EXIT
 LIGHTING. EXCEPTIONS ARE PERMITTED HOWEVER AT THIS TIME
 NOT ENOUGH INFORMATION IS PROVIDED FOR THE LIGHTING.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS ON THE
 PROPOSED UPSE.
 110.3, 90.7
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE #17 AS THIS REQUIRED
 ALL CONTINUOUS LOADS TO BE SHOWN AT 125%. THIS COULD
 NOT BE LOCATED ON PLANS AND NOT ON THE SHEET WHICH
 RESPONSE LETTER MENTIONS TO SEE. (5.1)
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%. 215.3,
 230.42
  
 11) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTE #19. AS
 THIS WAS RESPONDED BY THE FIRE SPRINKLER DESIGNER WHICH
 STATED A RESPONSE HOWEVER PLEASE PROVIDE THE MINIMUM
 INFORMATION ON THE FS PLANS. PLEASE SEE COMMENTS ABOVE
 WITH RESPECT TO OTHER INFORMATION NEEDED ON THESE SAME
 PLANS.
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE MORE INFORMATION FOR THE FIRE PUMP ROOM
 AS REQUIRED PER NFPA-20 CHAPTER 5. 5.12.5 FOR
 VENTILATION.
 5.12.6* DRAINAGE.
 5.12.6.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE
 OF ESCAPING WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS
 THE PUMP, DRIVER, CONTROLLER, AND SO FORTH.
 11.3.1 PUMP ROOM DRAINAGE. THE FLOOR OR SURFACE AROUND
 THE PUMP AND ENGINE SHALL BE PITCHED FOR ADEQUATE
 DRAINAGE OF ESCAPING WATER AWAY FROM CRITICAL
 EQUIPMENT, SUCH AS PUMP, ENGINE, CONTROLLER, FUEL TANK,
 AND SO FORTH.
 11.3.2* VENTILATION.
 11.3.2.1 VENTILATION SHALL BE PROVIDED FOR THE
 FOLLOWING FUNCTIONS:
 (1)TO CONTROL THE MAXIMUM TEMPERATURE TO 49?C
 (120?F) AT THE COMBUSTION AIR CLEANER INLET WITH ENGINE
 RUNNING AT RATED LOAD
 (2)TO SUPPLY AIR FOR ENGINE COMBUSTION
 (3)TO REMOVE ANY HAZARDOUS VAPORS
 (4)TO SUPPLY AND EXHAUST AIR AS NECESSARY FOR
 RADIATOR COOLING OF THE ENGINE WHEN REQUIRED
  
 11.3.2.2 THE VENTILATION SYSTEM COMPONENTS SHALL BE
 COORDINATED WITH THE ENGINE OPERATION.
 11.3.2.3* AIR SUPPLY VENTILATOR.
 11.3.2.3.1 THE AIR SUPPLY VENTILATOR SHALL BE
 CONSIDERED TO INCLUDE ANYTHING IN THE AIR SUPPLY PATH
 TO THE ROOM.
 11.3.2.3.2 THE TOTAL AIR SUPPLY PATH TO THE PUMP ROOM
 SHALL NOT RESTRICT THE FLOW OF THE AIR MORE THAN 5.1 MM
 WATER COLUMN (0.2 IN. WATER COLUMN).
 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE SEE PANEL E IS BEING SHOWN AS 277/480V
 WHICH IS NOT POSSIBLE AS THIS IS BEING SHOWN BEING FED
 FROM A 120/240 DELTA SERVICE. DOES THE UPS EQUIPMENT
 CONTAIN A STEP UP TRANSFORMER?
 PLEASE SEE THE RISER SHEET NOTE FOR THE 15K UPS ONLY
 STATES 120/240 IN AND 120/240 OUT.
 PLEASE CLARIFY.
  
 13) NOTE: PLEASE CLARIFY PANEL LB AS THIS PANEL IS
 BEING SHOWN AS 120/208V AND IS NOTED AS A DELTA PANEL?
 HOW IS THIS POSSIBLE?
 PLEASE COORDINATE>
 FBC 106.1.2, 106.3.5.1.2
  
 14) NOTE: PLEASE SEE PLANS INDICATE *HASH* LINES FOR
 AREAS WHERE THERE IS NOT SUPPOSE TO BE ANY WORK OR AT
 LEAST THAT IS WHAT PLANS INDICATES. PLEASE SEE AREAS
 WHERE NEW PANELS AND EQUIPMENT IS BEING ADDED SHOULD
 NOT CONTAIN ANY (HASHED LINES) AS THESE AREAS DO
 INCLUDE SEVERAL ITEMS OF NEW ELECTRICAL EQUIPMENT ETC.
 PLEASE ADJUST PLANS FOR THESE AREAS WHERE WORK IS BEING
 DONE.
 FBC 106.1.
  
 15) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) IS
 BEING GIVEN AS SOME OF THE COMMENTS ARE BEING REPEATED
 FROM PREVIOUS REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-18 07:04:312007-07-18 07:04:31
 PLANS REMOVED FROM INCOMING AND IN ELECTRICAL FOR
 REVIEW. PLANS WILL RETURN TO INCOMING WAITING FOR COMM
 BOARD WHEN REVIEW IS COMPLETED.