2007-09-04 12:44:46BUILDING PLAN REVIEW
 PERMIT: 07030559
 ADD: 3501 ELECTRONIC WAY
 CONT: EDWARDS CONSTRUCTION SERVICES
 TEL: (352)854-6266
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION
 SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4A) SHEET C1-C9 ARCHITECT RETE EBERSOLE STILL INDICATES
 HAVING A CERTIFICATE OF AUTHORIZATION ON PLANS. 481.219
 CERTIFICATE OF AUTHORIZATION. THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATE, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER ON THE PLANS. ADD
 NUMBER TO EACH SHEET.
  
 4B) FP1 THE FIRE PREVENTION ENGINEERING CONSORTIUM, NO
 CERTIFICATE OF AUTHORIZATION .471.023 F.S.CERTIFICATE
 OF AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET
 BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 5) COMPLIED.
  
 6) CS-1 PLAN REVIEWDATA DECLAIRS THIS BUILDING AS A IIB
 BUILDING (1 STORY) FULLY SPRINKLERD, IS THIS DESIGN AN
 ADDITION TO A EXISTINGBUILDING CREATING ONE LARGE
 BUILDING WITH AN AREA OF 123,414 SQ FT? OR IS THE
 DESIGN 2 SEPERATE BUILDINGS? NOTED THE COMMENTFOR
 UNLIMITED AREA FOR TYPE II BUILDINGS S OCCUPANCIES FOR
 FULLY SPRINKLERED BUILDINGS FBC 507.2REQUIRES A
 60'-0"CLEARENCE, 507.4 DOES PROVIDE FOR REDUCED OPEN
 SPACE REQUIREMENTS BUT THE EXISTING BUILDING IS 21.29'
 AWAY FROM THE PROPERTY LINE. PLEASE PROVIDE INCREASES
 FOR SPRINKLERS, ONE STORY AND ANY AREA INCREASES THAT
 CAN BE TAKEN PROVIDE CALCULATIONS. TOTAL SQ FT UNDER
 TYPE II-B UNPROTECTED (S-1) IS 17,500 SQ FT, NOT THE
 123,414 AS INDICATED ON THE PLAN.
  
 7) LEASE CLARIFY, IF THIS IS AN ADDITION THEN THE 2006
 FBC, EXISTING BUILDING CODE CHAPTER 9 NEEDS TO BE
 ADDRESSED UNDER THE PLAN REVIEW DATA AS WELL AS IN THE
 BUILDING WORKIS ALSO TO BE COMPLETED UNDER THIS PERMIT,
 INDICATE TO WHAT LEVEL OR CLASSIFICATION OF WORK IS TO
 BE COMPLETED UNDER THIS PERMIT . 2006 FBC EXISTING
 BUILDING CODE CHAPTERTHREE. SHEET SP-1 INDICATE WORK
 NOT IN CONTRACTBUT THIS SAME SHEET INDICATES NEW FIRE
 SPRINKLER PUMP ROOM, NEW ADA RESTROOMS, EXISTING BAY
 DOOR TO BE REPLACED, AND ADA RAMP AND ACCESSIBLE
 SIDEWALK? IF THE BUILDING INFORMATION IN COMMENT# 6 IS
 CORRECTED THIS COMMENT WILL BE SATISFIED.
  
 8) COMPLIED.
  
 9) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICHTHE PROJECT
 WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004. E) IF AN
 AUTOMATIC SPRINKLER SYSTEM ISPROVIDED, WHETHER THE
 SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 G ) FLOOD ZONE
  
 10)BUILDING PROVISO:, 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
  
 11) BUILDING PROVISO
 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 12)2ND REQUEST, COULDN'T FIND ANY CAMERO'S RESPONSE
 LETTER. FTHE NEW ACCESSIBLE ADA SIDEWALK PLEASE PROVIDE
 INFORMATION ON THE CURB CUTS FOR THE ACCESSIBLE CROSS
 WALKS.
 11-4.7.1 LOCATION. CURB RAMPS COMPLYING WITH SECTION
 11-4.7 SHALL BE PROVIDED WHEREVER AN ACCESSIBLE ROUTE
 CROSSES A CURB .
 11-4.7.2 SLOPE.SLOPES OF CURB RAMPS SHALL COMPLY WITH
 SECTION 11-4.8.2 . THE SLOPE SHALL BE MEASURED AS SHOWN
 IN FIGURE 11 . TRANSITIONS FROM RAMPS TO WALKS,
 GUTTERS, OR STREETS SHALL BE FLUSH AND FREE OF ABRUPT
 CHANGES. MAXIMUM SLOPES OF ADJOINING GUTTERS, ROAD
 SURFACE IMMEDIATELY ADJACENT TO THE CURB RAMP, OR
 ACCESSIBLE ROUTE SHALL NOT EXCEED 1:20.
  
 13)COMPLIED.
  
 14) 2ND REQUEST, PLEASE PROVIDE PRODUCT APPROVALS FOR
 GLAZED OPENINGS.
 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 14A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:\
 A) GLAZED OPENINGS
 B) GLAZED DOORS TO THE EXTERIOR
 C) HOLLOW METAL EXTERIOR DOORS
 D) OVERHEAD DOORS
 E) PANEL WALLS: SIDING AND OR WALL LOUVERS
 F) ROOF ASSEMBLIES : METAL ROOFING
  
 14B)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 14C)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 15)COMPLIED.
  
 16) THIS SAME SHEET A-1 LOADING DOCK INDICATES A
 SECTION "B"/ A4, IT APPEARS TO BE A MEZZANINE, IS THIS
 CORRECT? THE DETAIL 4 ON SHEET A-7 IS A 4 HR RATED
 FLOOR CEILING ASSEMBLY. IF THIS MEZZANINE IS TO BE
 BUILT OUT WITH THE SHELL PERMIT PLEASE PROIVIDE A LIFE
 SAFETY PLAN INDICATING THE STAIRS, HANDRAILS, GUARDS,
 USAGE POSSIBLE VERTICAL ACCESSIBILITY, FLOOR LOADING
 ETC.
  
 17) PLEASE PROVIDE A LIFE SAFETY PLAN OF THE NEW
 ADDITION, EVEN FOR A SHELL BUILDING A EXIT PLAN WILL BE
 REQUIRED, OTHERWISE WE ISSUE A PERMIT FOR A NON-CODE
 COMPLIANT BUILDING!
  
 18) NOTE TO BE ACCOMPLISHED UNDER A TENANT BUILD OUT OF
 SHELL.
  
 19)SHEET A-4 INDICATES THE USE OF :
 19A)SECOND REQUEST, POLYMER FINISHED RIGID INSULATION
 BOARDTO BE BUTLER STYWALL II FLAT WALL SYSTEM, PLEASE
 PROVIDE PRODUCT INFORMATION ON THIS SYSTEM ? 106.1.2*
 ADD INFO REQUIRED.
 19B)SECOND REQUEST, KORTECK WALL PANELS, PLEASE
 PROVIDE PRODUCT INFORMATION ON THIS SYSTEM? 106.1.2*
 ADD INFO REQUIRED.
  
 20-23 ) COMPLIED.
  
 24)SECOND REQUEST, BUTLER PLAN INDICATES PRESSURES
 DERIVED FROM ASCE 7-02 / IBC 03 WE DO NOT USE THE IBC
 FLORIDAS BASE CODE MAY OF BEEN DERIVED FROM THE 2003
 IBC BUT PLANS ARE TO BE SUBMITTED UNDER THE 2004 FBC/
 2006 REVISIONS.PLANS ARE TO BE SUBMITTED UNDE THE 2004
 FBC W/ 2006 REVISIONS.
  
 25) LOW VALUE, FOR THE ADDITION ALONE THE CALCULATED
 VALUE IS $4,391, 656.00 PLUS THE DOLLAR AMOUNT FOR THE
 REMODEL OF THE EXISTING BUILDING. SEE ADDITIONAL FEES
 DUE.
  
 26)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]