Plan Review Notes
Plan Review Notes For Permit 07030559
Permit Number 07030559
Review Stop P
Sequence Number 1
Notes
Date Text
2007-04-07 10:17:49DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINSTRATIVE CODE
 FLORIDA STATUES
  
 1. SURVEY SHEET REQUIRES THE ORIGINAL SIGNATURE.
 SIGNATURE IS A PHOTO-COPY. FAC 61G1-17.002 & FS
 472.025.-THE TITLE BLOCK ADDRESS "OLD" OKEECHOBEE
 ROAD DOES NOT REFLECT THE DBPR WEBSITE SHOWING THE
 CORRECT ADDRESS OKEECHOBEE ROAD. THE COUNTY (PAPA) DOES
 NOT RECOGNIZE "OLD" OKEECHOBEE ROAD, NOR DOES THE CITY
 WPB'S ADDRESSING SYSTEM. PLEASE CHANGE THE TITLE BLOCK
 TO REFLECT THE CORRECT ADDRESS.-"OLD" OKEECHOBEE IS
 ALSO SHOWN IN THE DBPR WEBSITE FOR THE BUSINESS LICENSE
 (CERTIFICATE OF AUTHORIZATION) NUMBER. PLEASE SUBMIT AN
 ADDRESS CORRECTION TO DBPR WEBSITE INDICATING THE
 CORRECT ADDRESS OF OKEECHOBEE ROAD.
  
 2. ALL SHEETS FROM BUTLER MFG. CO. THE ENGINEER SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS, AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET.
  
 3. ALL CIVIL SHEETS REQUIRE THE BUSINESS LICENSE,
 (CERTIFICATE OF AUTHORIZATION), IN THE TITLE BLOCK OF
 ARCHITECTURAL ALLIANCE. (SEE ATTACHED SHEET FROM DBPR).
 --THE SIGNATURE IS REQUIRED WHEN THE SEAL IS AFFIXED
 TO THE DOCUMENTS. IT APPEARS THAT INITIALS WERE USED
 WHICH IS NOT APPROVED. IF INDEED THIS IS THE LEGAL
 SIGNATURE, THEN A SIGNED, SEALED, NOTORIZED LETTER
 SHALL BE SUBMITTED FOR OUR FILES INDICATING THE LEGAL
 SIGNATURE. FAC 61G1-16.003, 61G1-16.004(5) & FS
 481.219, 481.2055.
  
 4. SHT L-1 THE SIGNATURE IS REQUIRED WHEN THE SEAL IS
 AFFIXED TO THE DOCUMENT. IT APPEARS THAT INITIALS WERE
 USED WHICH IS NOT APPROVED. IF INDEED THIS IS THE LEGAL
 SIGNATURE, THEN A SIGNED, SEALED, NOTORIZED LETTER
 SHALL BE SUBMITTED FOR OUR FILES INDICATING THE LEGAL
 SIGNATURE. FAC 61G1-16.003, 61G1-16.004(5) & FS
 481.219, 481.2055.
  
 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1004.1.2 & 403.1. SHOW THE TOTAL SQUARE FOOTAGE
 FOR EACH OCCUPANCY.
  
 6. SHT A-1 KEY PLAN SHOWS A NEW TOILET ROOM AND SERVICE
 SINK LOCATION IN THE EXISTING BUILDING. PREVIOUS SHEETS
 INDICATE, " EXISTING BUILDING NOT IN CONTRACT", AND THE
 APPLICATION DOES NOT MENTION REMODEL OF EXISTING
 BUILLDING. PLEASE CLARIFY. APPLICATION REQUIRES A
 DESCRIPTION IN DETAIL OF THE PROJECT. SECTION 106.1.1.
  
 7. SHT A-4 SUBMIT CALCULATIONS FOR THE EXISTING ROOF.
 THERE WILL BE ADDITIONAL SQUARE FOOTAGE ADDED TO THE
 EXISTING ROOF WITH 1/2 THE AREA OF THE VERTICAL WALL OF
 THE NEW ADDITION CONTRIBUTING TO THE EXISTING ROOF
 DRAINS ADJACENT TO THE ADDITION. SHOW THE SQUARE
 FOOTAGE BEING DRAINED BY THE ROOF DRAINS PRIOR TO AND
 AFTER THIS NEW CONTRIBUTION. SUBMIT AN EXISTING ROOF
 PLAN TO SCALE AS WELL AS AN ELEVATION SHOWING THE
 HEIGHT OF ALL PARAPETS IN ORDER TO VERIFY ALL
 CALCULATIONS. INDICATE THE SIZE OF THE EXISTING RWL'S
 AND ASSOCIATED PIPING FOR THE EXISTING STORM SYSTEM.
 TABLE 1106.3 AND SECTIONS 1106.2, 1106.4. ALSO INDICATE
 THE SIZE OF THE SECONDARY ROOF DRAINS, OR OVERFLOW
 SCUPPERS ON THE EXISTING ROOF TO VERIFY THAT THEY ARE
 SUFFICIENT TO HANDLE THE NEW SQUARE FOOTAGE ADDED TO
 THE EXISTING ROOF. SECTION 1107.3.
  
 8. SHT A-7 SHOW COMPLIANCE WITH SECTION
 11-4.15.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING AT THE DRINKING
 FOUNTAIN. INDICATE METHOD OF COMPLIANCE.
  
 9. ALL STRUCTURAL SHEETS A SIGNATURE IS REQUIRED WHEN
 SEALING DOCUMENTS. IT APPEARS THAT INITIALS WERE USED
 WHICH IS NOT APPROVED. IF INDEED THIS IS THE LEGAL
 SIGNATURE, THEN A SIGNED, SEALED, NOTORIZED LETTER
 SHALL BE SUBMITTED FOR OUR FILES INDICATING THE LEGAL
 SIGNATURE. FAC 61G15-23.002(1)(2) & FS 471.025.
  
 10. ALL MEP SHEETS THE SIGNATURE IS REQUIRED WHEN
 SEALING DOCUMENTS. 61G15-23.002(1)(2 & FS 471.025.
  
 11. SHT P0.1 THE WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURES, IN AN "EFFECTIVE RANGE", NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS. ALSO SEE PLUMBING NOTES
 #13.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]