| Plan Review Notes For Permit 07030559 |
| Permit Number |
07030559 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-06 08:04:04 | -----------------DENIED--------------- | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | FBC CH 1 AS AMENDED BY THE CITY OF WEST PALM BEACH. | | | | | | 1. PLEASE SEE ELECTRICAL COMMENT REGARDING ENGINEER'S | | | SIGNATURE. | | | | | | 2. PLEASE PROVIDE DETAIL FOR CURB ATTACHMENT AND | | | ATTACHMENT OF FANS TO CURBS WHICH MEET WIND LOAD | | | REQUIREMENTS PER FBC,M 301.13 AND FBC CH 16 WHICH ARE | | | APPROVED BY A FLORIDA LICENSED STRUCTURAL ENGINEER. FBC | | | 106.1.2. | | | | | | 3. WHERE EQUIPMENT REQUIRING ACCESS IS INSTALLED ON A | | | ROOF AT A HEIGHT EXCEEDING 16 FEET, SUCH ACCESS SHALL | | | BE PROVIDED BY A PERMANENT APPROVED MEANS FROM GRADE OR | | | FLOOR RO EQUIPMENT'S LEVEL SERVICE SPACE. FBC,M 306.5. | | | | | | 4. PLEASE SHOW MEANS OF SUPPORT FOR SUPPLY AND EXHAUST | | | DUCTS. NONE COULD BE FOUND IN STRUCTURAL DRAWINGS AS | | | NOTED IN DETAIL #2. ALSO, PLEASE INDICATE TYPE OF | | | MATERIAL TO BE USED FOR DUCT, WHICH IS TO BE SUPPORTED, | | | FABRICATED AND INSTALLED PER SMACNA DUCT CONSTRUCTION | | | STANDARDS. FBC,M 603.3. | | | | | | 5. NEW BATHROOM: PLEASE SHOW MEANS OF ROOF TERMINATION | | | FOR EXHAUST DUCT. IS THIS DUCT PENETRATING THE EXISTING | | | ROOF OR ATTACHING TO AN EXISTING CURB? PLEASE CLARIFY | | | PER FBC 106.1.1. | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|