| 2007-04-23 14:11:30 | *****DENIED***** |
| | |
| | |
| | 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR |
| | HINDER EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR |
| | VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | 04.PROPOSED FIRE HYDRANTS SHALL BE OPERATIONAL |
| | BEFORE, DURING, AND AFTER CONSTRUCTION. |
| | |
| | 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH |
| | FIRE PROTECTION EQUIPMENT.PROPER CLEARANCE SHALL BE |
| | MAINTAINED AT ALL TIMES. |
| | |
| | 06.IT IS STATED ON DRAWING SP-1 THAT A NEW 10' HIGH |
| | GATE WITH KNOX BOX WILL BE INSTALLED.PLEASE BE |
| | ADVISED THAT AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 |
| | FEET WILL BE REQUIRED.ADDITIONALLY, CONTACT THE |
| | BUREAU OF FIRE PREVENTION AT (561) 804-4724 FOR KNOX |
| | BOX APPLICATIONS. |
| | |
| | 07.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE |
| | DEPARTMENT CONNECTIONS. |
| | |
| | 08.ALL STAIRS AND RAMPS SHALL HAVE HANDRAILS ON BOTH |
| | SIDES. |
| | |
| | 09.PLEASE PROVIDE EMEGENCY LIGHTING DETAIL FOR THE |
| | PROPOSED STRUCTURE. |
| | |
| | 10.PLEASE PROVIDE A LIFE SAFETY PLAN WHICH SHALL |
| | INCLUDE ALL COMMON PATHS OF TRAVEL TO EXITS.FIRE |
| | EXTINGUISHERS RATED 2A:10BC SHALL BE SHOWN AT DISTANCES |
| | TO SATISFY THE 75' TRAVEL DISTANCE REQUIREMENT. |
| | |
| | 11.PLEASE INDICATE THE MINIMUM INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS IN TERMS OF CLASS |
| | A, CLASS B, OR CLASS C IN EXITS, EXIT CORRIDORS, AND |
| | ALL OTHER SPACES. |
| | |
| | 12.WILL THE STRUCTURE HAVE A FIRE ALARM SYSTEM?IF |
| | SO, THE FIRE ALARM SYSTEM WILL BE UL CERTIFIED FOR |
| | CENTAL STATION SERVICEIN CONJUNCTION WITH THE FIRE |
| | SPRINKLER SYSTEM. |
| | |
| | 13.WILL THE FIRE PUMP AND ASSOCIATED EQUIPMENT BE |
| | USED FOR ONE OR BOTH BUILDINGS?PROVIDE MANUFACTURER |
| | SPECIFICATION SHEETS AND NECESSARY DATA INDICATING THAT |
| | THIS EQUIPMENT IS CAPABLE OF SUPPORTING THE FIRE |
| | SPRINKLER SYSTEM. |
| | |
| | 14.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED |
| | FOR FIRE SPRINKLER AND/OR FIRE ALARM SYSTEMS. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |