Plan Review Notes
Plan Review Notes For Permit 07030559
Permit Number 07030559
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-04-23 14:11:30*****DENIED*****
  
  
 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR
 VICINITY THEREOF (INCLUDING FIRE LANES).
  
 04.PROPOSED FIRE HYDRANTS SHALL BE OPERATIONAL
 BEFORE, DURING, AND AFTER CONSTRUCTION.
  
 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 FIRE PROTECTION EQUIPMENT.PROPER CLEARANCE SHALL BE
 MAINTAINED AT ALL TIMES.
  
 06.IT IS STATED ON DRAWING SP-1 THAT A NEW 10' HIGH
 GATE WITH KNOX BOX WILL BE INSTALLED.PLEASE BE
 ADVISED THAT AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20
 FEET WILL BE REQUIRED.ADDITIONALLY, CONTACT THE
 BUREAU OF FIRE PREVENTION AT (561) 804-4724 FOR KNOX
 BOX APPLICATIONS.
  
 07.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
 08.ALL STAIRS AND RAMPS SHALL HAVE HANDRAILS ON BOTH
 SIDES.
  
 09.PLEASE PROVIDE EMEGENCY LIGHTING DETAIL FOR THE
 PROPOSED STRUCTURE.
  
 10.PLEASE PROVIDE A LIFE SAFETY PLAN WHICH SHALL
 INCLUDE ALL COMMON PATHS OF TRAVEL TO EXITS.FIRE
 EXTINGUISHERS RATED 2A:10BC SHALL BE SHOWN AT DISTANCES
 TO SATISFY THE 75' TRAVEL DISTANCE REQUIREMENT.
  
 11.PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IN TERMS OF CLASS
 A, CLASS B, OR CLASS C IN EXITS, EXIT CORRIDORS, AND
 ALL OTHER SPACES.
  
 12.WILL THE STRUCTURE HAVE A FIRE ALARM SYSTEM?IF
 SO, THE FIRE ALARM SYSTEM WILL BE UL CERTIFIED FOR
 CENTAL STATION SERVICEIN CONJUNCTION WITH THE FIRE
 SPRINKLER SYSTEM.
  
 13.WILL THE FIRE PUMP AND ASSOCIATED EQUIPMENT BE
 USED FOR ONE OR BOTH BUILDINGS?PROVIDE MANUFACTURER
 SPECIFICATION SHEETS AND NECESSARY DATA INDICATING THAT
 THIS EQUIPMENT IS CAPABLE OF SUPPORTING THE FIRE
 SPRINKLER SYSTEM.
  
 14.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER AND/OR FIRE ALARM SYSTEMS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722