| 2007-03-24 19:46:37 | ** PLANS WERE REMOVED FROM ZONING AND ARE BEING |
| | RETURNED TO ZONING. |
| 2007-03-24 19:39:50 | |
| | |
| | ****** UNSAT ***** |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | ** PLEASE SEE THAT THERE COMMENTS MADE TO SHEETS OTHER |
| | THAN ELECTRICAL BY THIS REVIEW. THESE COMMENTS ARE |
| | REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| | TRADE. |
| | |
| | ** IMPORTANT** |
| | ONLY ONE SET OF PLANS WILL BE RETURNED. |
| | DUE TO MANY OF THE COMMENTS BELOWAND THE TYPE OF |
| | COMMENTS, ONE COMPLETE SET OF PLANS ARE BEING RETAINED |
| | BY THIS OFFICE. |
| | |
| | 1) NOTE: PLEASE SEE FAC 61G17 AND FS 472.025 AS THE |
| | SURVEY SHEETS ARE REQUIRED TO CONTAIN AN ORIGINAL |
| | SIGNATURE AND DATE. SHEET CONTAINS A RAISED SEAL OVER A |
| | PHOTO-COPIED SIGNATURE WHICH IS NOT PERMITTED. |
| | STATEMENT ON TITLE BLOCK MENTIONS NOT VALID WITHOUT |
| | SIGNATURE. |
| | |
| | 2) NOTE: PLEASE SEE THE SHEETS FROM BUTLER |
| | MANUFACTURING COMPANY DO NOT CONTAIN ANY TITLE BLOCK |
| | FOR THE ENGINEER. |
| | PLEASE SEE FAC 61G15-23.002. |
| | PLEASE ALSO KNOW IF THE ENGINEER IS EMPLOYED BY THE |
| | SAID COMPANY AND COMPANY IS OFFERING ENGINEERING |
| | SERVICES, THEN A CERTIFICATE OF AUTHORIZATION NUMBER IS |
| | REQUIRED FOR SAID FIRM. |
| | PLEASE SEE FS 471.023. |
| | PLEASE SEE THE SHEETS DO NOT CONTAIN ORIGINAL |
| | SIGNATURES ARE REQUIRED PER FS 471.025 AND FAC |
| | 61G15-23.002. THESE CONTAIN A RAISED SEAL OVER A |
| | PHOTO-COPIED SIGNATURE IN BOTH SETS. |
| | **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | |
| | 3) NOTE: PLEASE SEE THE FIRM ARCHITECTURAL ALLIANCE IS |
| | MISSING INFORMATION ON TITLE BLOCKS AS REQUIRED PER FAC |
| | 61G1-16.004. PLEASE SEE MISSING FIRM LICENSE NUMBER, |
| | ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION NUMBER. |
| | |
| | PLEASE SEE FLORIDA STATUTES 481.219 WHICH REQUIRES |
| | THIS. |
| | ** REQUIRED FOR ALL SHEETS WHICH CONTAIN TITLE BLOCKS |
| | FOR FIRM. C, CS,, LANDSCAPE AND A SHEETS ETC. |
| | |
| | 4) NOTE: PLEASE SEE THE FIRE SPRINKLER SHEETS. |
| | A) PLEASE SEE THE SEAL WHICH IS BEING USED BY THE |
| | ENGINEER IS NO LONGER VALID. PLEASE SEE RULE |
| | 61G15-23.001 WHICH WAS CHANGED IN FEB 04 WHICH REQUIRED |
| | ALL ENGINEERS TO OBTAIN A NEW SEAL WITH THE WORDING |
| | *LICENSE* INSTEAD OF*CERTIFICATE*. THIS RULE WAS |
| | EXTENDED TO DECEMBER 31ST, 2005. ALL SEALS AFTER THAT |
| | DATE MUST CONTAIN THE NEW WORDING. |
| | B) PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER FOR COMPANY. |
| | C) PLEASE SEE THE SEAL ITSELF IS NO SIZED AS REQUIRED |
| | PER FAC 61G15-23.001. THE SEAL SHALL BE A MINIMUM OF |
| | 2INCHES. |
| | |
| | 5) NOTE: PLEASE SEE THE SHEETS SIGNED BY KAMM |
| | CONSULTING SHALL BEAR THE SIGNATURES AS RECOGNIZED AND |
| | AS ON FILE WITH THIS OFFICE. |
| | FS 471.025. |
| | |
| | 6) NOTE: PLEASE SEE FS 481.221 AND 471.025 FOR |
| | ARCHITECTS AND ENGINEERS. |
| | |
| | 7) NOTE: PLEASE SEE THAT PLANS HAVE BEEN SUBMITTED FOR |
| | PERMIT AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECT |
| | UNDER THE NEW CODES. |
| | PLEASE SEE THE FOLLOWING SHALL BE STATED ON THE |
| | ARCHITECTURAL CS COVER SHEET. PLEASE ALSO BE SURE THE |
| | TRADES REFLECT THE CODES RELEVANT TO THEIR DESIGNS ON |
| | RESPECTIVE SHEETS. |
| | 2004 FBC W/ 2006 REVISIONS (ALL TRADES). |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | 2003 NFPA-20 |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WITH |
| | RESPECT TO OTHER CODES REQUIRED ON PLANS. |
| | |
| | 8) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE FIRE PUMP. PLEASE SEE NFPA-20 2003. |
| | 110.3, 90.7. CHAPTER 11 AND 12 OF NFPA-20 |
| | FBC 106.1.2 |
| | PLEASE SEE MINIMUM TIME, FUEL CONSUMPTION IS TO BE |
| | STATED ON PLANS. THIS MAY ALSO BE IN FIRE REVIEWS |
| | COMMENTS. |
| | AS SHOWN DIESEL DRIVEN AND THE AMOUNT OF FUEL REQUIRED |
| | WHICH EQUALS 1GAL PER HP PER HOUR PLUS 5% FOR SUMP AND |
| | 5% FOR EXPANSION. PLEASE SEE THE FOLLOWING THE CODE. |
| | 11.4.3.1 FUEL SUPPLY TANK(S) SHALL HAVE A CAPACITY AT |
| | LEAST EQUAL TO 5.07 L PER KW (1 GAL PER HP), PLUS 5 |
| | PERCENT VOLUME FOR EXPANSION AND 5 PERCENT VOLUME FOR |
| | SUMP AND THE COMMENTARY SECTION AS FOLLOWS. |
| | |
| | 9) NOTE: ** PLANS INDICATE WIND LOADS FOR LIGHT POLES |
| | AT 120MPH? |
| | PLEASE ALSO SEE SETS CONTAIN A SHEET WITH NO NUMERICAL |
| | DESIGNATION WHICH APPEARS TO BE THE SAME AS SHEET E1.1? |
| | PLEASE VERIFY AND REMOVE AS NEEDED. |
| | * PLEASE PROVIDE ALL MINIMUM WIND LOADING FOR SITE |
| | LIGHTING LIGHT POLES, AND THAT OF THE POLES ON GARAGE |
| | ROOF STRUCTURE. PLEASE KNOW A DETAIL ON HOW THESE WILL |
| | BE ATTACHED ON PARKING DECK OF THE GARAGE AND POLE |
| | DETAIL FOR GROUND MOUNTED/BURIED POLES WILL BE |
| | REQUIRED. PLEASE KNOW ALL SHOW MEET THE FBC 140MPH |
| | (3SEC GUST) 120MPH SUSTAINED. |
| | |
| | THE STRUCTURAL CALCULATIONS WILL BE REVIEWED BY THE |
| | BUILDING PLAN REVIEWER. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 10) NOTE: PLEASE SEE THE PLANS INDICATE A NEW SERVICE |
| | FOR THIS SECTION OF BUILDING WHICH IS BEING FROM THE |
| | FIRE PUMP AND HAS ELECTRICAL CROSSED OVER TO THE OTHER |
| | EXISTING BUILDING AREA?? |
| | PLEASE SEE THAT A NEW SERVICE IS NOT BEING GRANTED AT |
| | THIS TIME AS THIS IS NOT BEING CONSIDERED A SEPARATE |
| | BUILDING. ELECTRICAL SYSTEMS CROSS, FIRE PUMP IS IN |
| | ANOTHER SECTION OF THE STRUCTURE, SEPARATION AS |
| | REQUIRED PER THE FBC TO CONSIDER THIS A SEPARATE |
| | BUILDING IS NOT MET. |
| | FBC DEFINITIONS. |
| | NEC 230.2. |
| | PLEASE REVISE PLANS AND SHOW HOW AND WHERE THE POWER |
| | WILL BE COMING FROM IN THE EXISTING BUILDING. REVISE |
| | THE RISER DIAGRAM FOR NEW FEEDS FROM THE EXISTING |
| | SERVICE OR SERVICE BEING UPGRADED. |
| | PLEASE SUBMIT LOAD CALCULATIONS FOR THE NEW LOADS ON |
| | EXISTING SERVICE. |
| | PLEASE SEE COMMENTS FROM THE FIRE MARSHAL ALSO. 230.2, |
| | 230.70, 230.72, 220. |
| | FBC 106.3.5.1.2 |
| | |
| | 11) NOTE: PLEASE SEE THE NEW FOOTER STEEL AND |
| | STRUCTURAL STEEL IS REQUIRED TO BE PART OF THE |
| | GROUNDING ELECTRODE SYSTEM OF EXISTING OR UPDATED |
| | EXISTING SERVICE. |
| | 250.50. |
| | |
| | 12) NOTE: PLEASE SEE 250.104 AS THE FIRE SPRINKLER LINE |
| | SHALL BE PART OF THE GE SYSTEM. |
| | |
| | 13) NOTE: PLEASE SEE THE 2004 FBC W/ 2006 REVISIONS FOR |
| | CHAPTER 13. AT THIS TIME THERE ARE SEVERAL ITEMS |
| | MISSING FOR REVIEW. |
| | PLEASE SEE NO SCHEDULING OF SYSTEM WAS SUBMITTED. |
| | PLEASE SEE NO INFORMATION ON A SYSTEM WAS SUBMITTED. |
| | PLEASE SEE NO OVER RIDE DEVICES AT THE POINTS OF |
| | EGRESS/INGRESS INTO SPACE FROM ENTRANCE WIN WHICH THE |
| | OCCUPANT CAN SEE THE LIGHTING WHICH IS BEING |
| | CONTROLLED. |
| | PLEASE SEE NO TIMES ON ANY OVER RIDE DEVICES AND TYPES |
| | OF DEVICES. |
| | PLEASE SEE MISSING ENERGY CALCULATIONS. |
| | PLEASE SEE MISSING LIGHTING PERFORMANCE CALCULATIONS. |
| | PLEASE SEE MISSING CERTIFICATIONS PER DESIGNER(S) OF |
| | RECORD. |
| | PLEASE SEE MISSING VOLTAGE DROP CALCULATIONS FOR |
| | LONGEST RUNS. |
| | PLEASE SEE 13-103.1, 13-415.1ABC.1, 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3, 13-415.1.AB.1.1, 13-415.1..A, .B AND .C, |
| | 13-415.2 AND TABLES UNDER THE NEW 2006 REVISIONS. ETC. |
| | |
| | 14) NOTE: PLEASE SEE MISSING EGRESS LIGHTING |
| | PHOTO-METRICS FOR EGRESS PATHS TO THE PUBLIC RIGHT OF |
| | WAY, INCLUDING OUTSIDE STAIRS AND INTERIOR STAIRS. |
| | PLEASE SEE NFPA-101 7.8, 7.9. 7.8.1.3, 7.9.2.2 |
| | |
| | 15) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS. PLEASE |
| | SEE 700.12E FOR CIRCUITING OF EMERGENCY LIGHTING AND |
| | EXIT LIGHTING. EXCEPTIONS ARE PERMITTED HOWEVER AT THIS |
| | TIME NOT ENOUGH INFORMATION IS PROVIDED FOR THE |
| | LIGHTING. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS ON THE |
| | PROPOSED UPSE. |
| | 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 16) NOTE: PLEASE BE SURE ALL EQUIPMENT CONTAINS THE AIC |
| | RATINGS AS REQUIRED PER 110.9. |
| | |
| | 17) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 |
| | |
| | 18) NOTE: PLEASE PROVIDE LAYOUT OF THE FIRE PUMP ROOM |
| | FOR LIGHTING AS REQUIRED PER 700.16, 700.12E, NFPA-101 |
| | 7.8, 7.9, NFPA-20 5.12.3, 5.12.4. |
| | |
| | 19) NOTE: PLEASE PROVIDE MORE INFORMATION FOR THE FIRE |
| | PUMP ROOM AS REQUIRED PER NFPA-20 CHAPTER 5. 5.12.5 FOR |
| | VENTILATION. |
| | 5.12.6* DRAINAGE. |
| | 5.12.6.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE |
| | OF ESCAPING WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS |
| | THE PUMP, DRIVER, CONTROLLER, AND SO FORTH. |
| | 11.3.1 PUMP ROOM DRAINAGE. THE FLOOR OR SURFACE AROUND |
| | THE PUMP AND ENGINE SHALL BE PITCHED FOR ADEQUATE |
| | DRAINAGE OF ESCAPING WATER AWAY FROM CRITICAL |
| | EQUIPMENT, SUCH AS PUMP, ENGINE, CONTROLLER, FUEL TANK, |
| | AND SO FORTH. |
| | 11.3.2* VENTILATION. |
| | 11.3.2.1 VENTILATION SHALL BE PROVIDED FOR THE |
| | FOLLOWING FUNCTIONS: |
| | (1)TO CONTROL THE MAXIMUM TEMPERATURE TO 49?C |
| | (120?F) AT THE COMBUSTION AIR CLEANER INLET WITH ENGINE |
| | RUNNING AT RATED LOAD |
| | (2)TO SUPPLY AIR FOR ENGINE COMBUSTION |
| | (3)TO REMOVE ANY HAZARDOUS VAPORS |
| | (4)TO SUPPLY AND EXHAUST AIR AS NECESSARY FOR |
| | RADIATOR COOLING OF THE ENGINE WHEN REQUIRED |
| | |
| | 11.3.2.2 THE VENTILATION SYSTEM COMPONENTS SHALL BE |
| | COORDINATED WITH THE ENGINE OPERATION. |
| | 11.3.2.3* AIR SUPPLY VENTILATOR. |
| | 11.3.2.3.1 THE AIR SUPPLY VENTILATOR SHALL BE |
| | CONSIDERED TO INCLUDE ANYTHING IN THE AIR SUPPLY PATH |
| | TO THE ROOM. |
| | 11.3.2.3.2 THE TOTAL AIR SUPPLY PATH TO THE PUMP ROOM |
| | SHALL NOT RESTRICT THE FLOW OF THE AIR MORE THAN 5.1 MM |
| | WATER COLUMN (0.2 IN. WATER COLUMN). |
| | ETC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |