| Plan Review Notes For Permit 07030550 |
| Permit Number |
07030550 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-11 15:45:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | 1.)HAVE AN ENGINEER CERTIFY THE BUILDING HEIGHT. | | | THIS IS BEING REQUESTED BECAUSE OTHER CONTRACTORS HAVE | | | DECLARED A BUILDING HEIGHT HIGHER THAN 173' FOR THIS | | | BUILDING. | | | | | | 2.)SEE NOTE 2G.AN ARCHITECT OR ENGINEER IS TO | | | DECLARE THE BUILDING AS ENCLOSED; OTHERWISE PARTIALLY | | | ENCLOSED PRESSURES MUST BE USED. | | | | | | 3.)THE RESUBMITTAL SHEET HAS A NOTE FROM THE | | | CONTRACTOR STATING THAT THIS UNIT IS "WELL IN EXPOSURE | | | B".THIS IS CONFUSING AS THE JOB IS IN EXPOSURE C PER | | | FBC1609.6.2.1(2), YOUR PAPERWORK IS FOR EXPOSURE C, | | | THIS WAS NOT A CORRECTION ON THE FIRST REVIEW, AND THE | | | SCALED MAP WHICH YOU REFER TO IN YOUR NOTE WAS NOT IN | | | THE PACKAGE. | | | | | | 4.)THIS JOB IS NOT WITHIN THE SCOPE OF A CBC LICENSE | | | (EXTERIOR WALLS AND WINDOWS ARE A STRUCTURAL COMPONENT | | | OF THE BUILDING). |
|