Plan Review Notes
Plan Review Notes For Permit 07030549
Permit Number 07030549
Review Stop M
Sequence Number 2
Notes
Date Text
2007-06-28 09:56:17*** DENIED ***
 1) CONDENSER STANDS APPEAR TO BE PRE-ENGINEERED STANDS
 AND NEED FLORIDA STATE PRODUCT APPROVAL, SEE ATTACHED
 FLORIDA STATUTE 553.842,PLEASE CORRECT.
  
 2) INFORMATION THAT WAS SUBMITTED FOR A/C CONDENSER
 STANDS IS NOT A PRODUCT APPROVAL AND HAS MANY ERRORS ON
 IT (SEE YELLOW HIGH LIGHTS) HAND CHANGES MAY NOT BE
 MADE TO DOCUMENTS, DATE AT SEAL JUN 95, 2007, DOCUMENT
 REFERENCES ASCE 7-98 SHOULD STATE 2002, AND PAGE 3 OF 4
 IS MISSING.
  
 3) THIS IS THE SECOND REQUEST FOR A PRODUCT APPROVAL.
 SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.