| Date |
Text |
| 2007-03-16 11:58:03 | *** DENIED *** |
| | 1) THE ARCHITECT (EVERETT H. JENNER) NEEDS TO SIGN AND |
| | SEAL THE PLANS AS HIS INFORMATION IS IN THE TITLE |
| | BLOCK, SEE FAC 61G1-16.003. |
| | |
| | 2) PLANS NOTE, WORK TO MEET NATIONAL CODES, NEED TO |
| | MEET 2004 FBC, PLEASE CORRECT. |
| | |
| | 3) THIS MECHANICAL SUB-PERMIT CAN NOT PASS REVIEW UNTIL |
| | THE MASTER PERMIT PASSES REVIEW AS THEIR IS INFORMATION |
| | ON THE MASTER PLANS THAT IS NEEDED (ARCHITECTURE). |
| | |
| | 4) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004 |
| | FBC 13-407.1.ABC.1. |
| | |
| | 5) PLEASE SHOW DETAILED OUTDOOR AIR CALCULATIONS, PER |
| | 2004 FBC/M 403.3. |
| | |
| | 6)PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S FOR A/C SYSTEMS AS THE MODEL NUMBERS IN |
| | THE EQUIPMENT LISTING COULD NOT BE FOUND IN THE ARI |
| | DIRECTORY. |
| | |
| | 7) PLEASE SHOW IN THE EQUIPMENT LISTING TOTAL BTU'S, |
| | SENSIBLE BTU'S, COPPER LINE SIZES, AND OTHER PERTINENT |
| | INFORMATION. |
| | |
| | 8) PLEASE SHOW ON PLANS THE INFORMATION FOR THE |
| | BATHROOM EXHAUST FANS. |
| | |
| | 9)PLEASE SUBMIT PRODUCT APPROVAL FOR PER-ENGINEERED |
| | CONDENSER STANDS, SEE FS 553.842(1) AND FAC |
| | 9B-72.010(31)(G). |
| | |
| | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| | |
| | 10) PLEASE SHOW CFM'S AT EACH SUPPLY AIR GRILL. |
| | |
| | 11) PLEASE SHOW RETURN AIR DUCTS AND GRILLS ON PLANS. |
| | |
| | 12) PLEASE SHOW ON PLANS WERE AND HOW CONDENSATE WATER |
| | IS TO BE DISPOSED OF, AND SECONDARY DRAIN. |
| | |
| | 13) PLANS STATE AHU TO SIT ON WOOD PLATFORMS ABOVE |
| | BATHROOMS, AHU #9 IS NOT OVER A BATHROOM (?), PLEASE |
| | CORRECT. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |
| | |