| Date |
Text |
| 2007-09-25 14:39:37 | DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 WITH 2006 REVISIONS FUEL GAS. |
| | ** NFPA-2002 CHAPTER 54. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | 1. **OK** |
| | |
| | 2. **OK** |
| | |
| | 3. **NO/OK** SHEET M-3 |
| | SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE RESUBMITTED ISOMETRIC IS NOT INDICATING ALL |
| | CORRESPONDING LENGTHS OF THE CUT SECTIONS. |
| | |
| | 4. **OK** |
| | |
| | 5. **OK** |
| | |
| | 6. **OK** |
| | |
| | 7. **NO/OK** SHEET M-3 |
| | SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THE INDICATED LONGEST LENGTH IS BEING INDICATED |
| | AS 145', THE TOTAL SUM OF THE INDICATED CUT SECTION |
| | CORRESPONDING LENGTHS IS 105'. PLEASE CORRELATE THE |
| | LONGEST LENGTHS ON THE RESUBMITTAL BY INDICATING ALL |
| | CORRESPONDING LENGTHS OF ALL CUT SECTIONS OF |
| | PIPE.(REFERENCE COMMENT #3) |
| | |
| | 8. **OK** |
| | |
| | 9. **OK** |
| | |
| | 10. **OK** |
| | |
| | **THE FOLLOWING IS A NEW COMMENT |
| | |
| | 11. SHEET M-3 THE RESUBMITTED GAS ISOMETRIC IS |
| | INDICATING THE GAS METER AS BEING UNDERGROUND. PER |
| | NFPA-2002 CHAPTER 54 SECTION 5.7.2.1 GAS METERS SHALL |
| | BE LOCATED IN VENTILATED SPACES READILY ACCESSIBLE FOR |
| | EXAMINATION, READING, REPACEMENT OR NECESSARY |
| | MAINTENANCE AND SECTION 5.7.2.2 GAS METERS SHALL NOT BE |
| | PLACED WHERE THEY WILL BE SUBJECT TO EXCESSIVE |
| | CORROSION. PLEASE INDICATE THE GAS METER AS BEING ABOVE |
| | GROUND AND INDICATE THE REQUIRED CORRESPONDING LENGTHS |
| | TO THE CUT SECTIONS TO CORRECT THIS ON THE |
| | RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK ON |
| | THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR FOR |
| | REFERENCE FOR THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |