| Plan Review Notes For Permit 07030543 |
| Permit Number |
07030543 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-27 13:55:24 | *** DENIED *** | | | 1) MANUAL J CALCULATIONS ARE CALLING FOR THREE A/C | | | SYSTEMS, SYSTEM #1 26,518 SENSIBLE BTU'S, SYSTEM #2 | | | 10,694 SENSIBLE BTU'S, AND SYSTEM #3 11,351 SENSIBLE | | | BTU'S. MECHANICAL PLANS ARE CALLING FOR A/C SYSTEM #1 | | | 44,600 SENSIBLE BTU'S, SYSTEM #2 25,000 SENSIBLE BTU'S, | | | AND SYSTEM #3 25,000 SENSIBLE BTU'S. THE PLANS A/C | | | SYSTEMS ARE TO LARGE. THE PLANS CAN ONLY CALL FOR 15% | | | MORE THAN THE MANUAL J CALCULATIONS, SEE 2004 FBC | | | 13-607.1.ABC.1.1 (12-8-07 REVISION). PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|