| 2007-03-30 16:59:10 | DENIED |
| | REFERENCE: |
| | |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PLEASE REFERENCE PLUMBING COMMENT #1 IN RELATION TO |
| | FIRM LICENSE NUMBER REQUIRED IN TITLE BLOCK. |
| | |
| | 2. 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | NOTE: THE SUBMITTED GAS ISOMETRIC ON SHEET M-3 DOES NOT |
| | REFLECT THE FLOOR PLANS ON SHEETS A-3 AND A-4. GAS |
| | ISOMETRIC INDICATES TWO RANGES IN DIFFERENT LOCATIONS |
| | BUT THE FLOOR PLANS ONLY INDICATE ONE RANGE IN THE |
| | KITCHEN. PLEASE CLARIFY ON THE RESUBMITTAL. |
| | |
| | 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: CORRESPONDING LENGTHS OF CUT SECTIONS ARE NOT |
| | INDICATED. |
| | |
| | 4. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: NOT ALL PIPE SIZES ARE INDICATED AND IF BLACK |
| | STEEL PIPE IS BEING INSTALLED UNDERGROUND PLEASE ADD |
| | THE FOLLOWING TO "GAS NOTES" ON SHEET M-3. |
| | |
| | A} PER FBC-2004 FUEL GAS SECTION 404.8.2 PROTECTIVE |
| | COATINGS AND WRAPPING. PIPE PROTECTIVE COATINGS AND |
| | WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND |
| | SHALL BE FACTORY APPLIED. |
| | |
| | |
| | 5. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) |
| | BEING USED ON THE RESUBMITTAL. |
| | |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 7. CLEARLY SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM ON THE ISOMETRIC |
| | PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 8. PLEASE SUBMIT MANUFACTURER SPECIFICATIONS OF |
| | APPLIANCES (CUT SHEETS) VARIFYING BTU LOADS AND SHOWING |
| | LISTINGS FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY (NRTL). |
| | |
| | 9. PLEASE CLARIFY WHAT THE NIPPLE AND HARD CAP ON THE |
| | RUN OF THE TEE FOR THE POOL HEATER IS. IS THIS SUPPOST |
| | TO BE A SEDIMENT TRAP? IF SO ITS IN THE WRONG LOCATION. |
| | PLEASE CLARIFY ON THE RESUBMITTAL. |
| | |
| | 10. PLEASE DELETE THE SEDIMENT TRAP BEING INDICATED |
| | UNDERGROUND ON THE RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |