| Date |
Text |
| 2007-03-16 08:47:09 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} 210.52(B)(2) ISLAND COUNTER SPACES AT LEAST ONE |
| | RECEPTACLE SHALL BE INSTALLED AT EACH ISLAND COUNTER |
| | SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR |
| | GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR |
| | GREATER. WHERE A RANGETOP OR SINK IS INSTALLED IN AN |
| | ISLAND COUNTER AND THE WIDTH OF THE COUNTER BEHIND THE |
| | RANGETOP OR SINK IS LESS THAN 300 MM (12 IN.), THE |
| | RANGETOP OR SINK IS CONSIDERED TO DIVIDE THE ISLAND |
| | INTO TWO SEPARATE COUNTERTOP SPACES AS DEFINED IN |
| | 210.52(C)(4). |
| | |
| | 2} 210.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET |
| | SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS |
| | 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE |
| | INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE |
| | THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A |
| | RECEPTACLE OUTLET IN THAT SPACE. |
| | |
| | 2} THE CONDENSER DISCONNECTS DO NOT MEET 110.26 |
| | CLEARANCE REQUIREMENTS. |
| | |
| | 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS |
| | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| | TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS |
| | CHANGE. |
| | |
| | 4} NOTE #20 INCORRECTLY REFERENCES 2204 FBC AND 907 |
| | NFPA-72. THE CORRECT REFERENCE STANDARDS PER 2004 FBC |
| | ARE R313 RESIDENTIAL AND CHAPTER 11NFPA-72, 2002 |
| | EDITION. PLEASE CORRECT FOR CLARITY IN THE FIELD. |
| | |
| | 5} A RECEPTACLE, AS WELL AS THE LIGHT INDICATED ON |
| | SHEET E-2, IS REQUIRED IN THE ATTIC FOR SERVICING THE |
| | AIR HANDLER PER 210.63 NEC AND M1305.1.3.1 FBC. |
| | |
| | 6} A RECEPTACLE PER 210.52(D) IS REQUIRED IN BATH #1 |
| | SHEET E-2. |
| | |
| | NOTE: THE #2 EQUIPMENT GROUND RAN WITH THE PANEL |
| | FEEDERS, ALTHOUGH NOT A VIOLATION, IS ONLY REQUIRED TO |
| | BE #6CU. IF IT REMAINS #2 ON THE PLAN IT MUST BE |
| | INSTALLED OR A REVISION WILL BE REQUIRED TO MAKE THE |
| | CHANGE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |