| Date |
Text |
| 2007-04-23 07:16:20 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) THE LICENSE NUMBER FOR THE ARCHITECTURAL FIRM IS |
| | MISSING FROM THE TITLE BLOCK. SEE FAC 61G1-16.004. |
| | |
| | 4) FBC TABLE R301.5 REQUIRES EXTERIOR BALCONIES TO HAVE |
| | A LIVE LOAD OF 60 PSF. PLEASE CORRECT THE STRUCTURAL |
| | NOTE ON SHEET A2. |
| | |
| | 5) ON SHEET A2 COLUMNS C8 ARE INCORRECTLY SPECIFIED AT |
| | THE FRONT ENTRY. |
| | |
| | 6) SPECIFY THE SIZES OF THE ATTIC ACCESSES ON THE |
| | PLANS. |
| | |
| | 7) SUBMIT THE MANUFACTURER'S SPECIFICATIONS, |
| | INSTALLATION INSTRUCTIONS AND LISTING INFORMATION FOR |
| | THE ISOKERN FLUELESS FIREPLACE. |
| | |
| | 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS, |
| | INSTALLATION INSTRUCTIONS AND LISTING INFORMATION FOR |
| | THE GAS BBQ ON THE LOGGIA. NOTE: THE CEILING OF THE |
| | LOGGIA IS COVERED WITH FLAMMABLE MATERIAL. |
| | |
| | 9) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE SPRAY FOAM INSULATION |
| | THAT WILL BE INSTALLED IN THE VENTLESS ATTIC. |
| | |
| | 10) PROVIDE ADDITIONAL INFORMATION FOR THE CHIMNEY. IS |
| | THIS A DECORATIVE ASSEMBLY OR WILL IT BE FUNCTIONING? |
| | PROVIDE DETAILS FOR THE CHIMNEY CAP SHOWN ON THE |
| | ELEVATIONS ON A8. THE ELEVATION SHOWS A STUCCO BAND |
| | WHICH IS NOT SHOWN ON THE STRUCTURAL DETAILS. THE |
| | TRUSSES WILL BE REQUIRED TO BE DESIGNED FOR THE CHIMNEY |
| | ATTACHMENT. |
| | |
| | 11) SHOW COMPLIANCE WITH R502.12 DRAFTSTOPPING |
| | REQUIRED. |
| | WHEN THERE IS USABLE SPACE BOTH ABOVE AND BELOW THE |
| | CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS |
| | SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED |
| | SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 M 2 ). |
| | DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO |
| | APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS |
| | ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING |
| | MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN |
| | FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING |
| | CIRCUMSTANCES: |
| | 1.CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. 2. |
| | FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB OR |
| | PERFORATED MEMBERS. |
| | SPECIFY THE LOCATION OF DRAFTSTOPPING AND MATERIAL THAT |
| | WILL BE USED. SEE R502.12.1. |
| | |
| | 12) PLEASE REVISE ROOF SHEATHING FASTENING NOTES ON A7. |
| | THE 2006 REVISIONS TO THE 2004 FBC REQUIRES RING SHANK |
| | NAILS TO BE USED IN ALL ROOF ZONES. FBC R803.2.3.1 |
| | |
| | 13) SPECIFY THE TREAD DEPTH OF THE STAIRS ON SHEET A11. |
| | SEE R311.5.3.2. |
| | |
| | 14) SPECIFY THE ATTACHMENT THAT WILL BE USED FOR THE |
| | MONIER CONCRETE ROOF TILES. CIRCLE THE APPROPRIATE |
| | FASTENER OR ADHESIVE ON THE PRODUCT APPROVAL. |
| | |
| | 15) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS. |
| | |
| | 16) SUBMIT DRAWING #IRC-5316-175-45 WHICH IS REQUIRED |
| | TO ACCOMPANY THE PRODUCT APPROVAL FOR THE OVERHEAD |
| | GARAGE DOOR. |
| | |
| | 17) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL |
| | MULLIONS, RAISED PANEL/HALF GLASS DOORS AT THE GARAGE |
| | AND LAUNDRY ROOM, THE 4' X 8' MAHOGANY ENTRY DOOR AND |
| | THE FIXED GLASS TRANSOM WINDOW ABOVE WINDOW A. |
| | |
| | 18) THE FLORIDA COVERSHEET SUBMITTED FOR THE MARVIN |
| | IMPACT CASEMENT WINDOW IS NOT THE CORRECT ONE FOR NOA |
| | 02-1113.04. IF THERE IS NO FL# THAT CORRESPONDS TO IT, |
| | THE NOA IS ACCEPTABLE WITHOUT THE FL COVERSHEET. |
| | HOWEVER, IT IS STILL REQUIRED TO BE APPROVED IN WRITING |
| | BY THE DESIGNER OF RECORD. |
| | |
| | 19) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | CASEMENT WINDOWS DO NOT HAVE DESIGN PRESSURES ON PAGE 7 |
| | OF THE NOA THAT ARE ACCEPTABLE FOR WINDOWS A & K AS |
| | SPECIFIED IN THE SCHEDULE ON A5. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |