| 2007-04-30 07:18:59 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FBC2004 |
| | FACFLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)THE SHUTTER INSTALLATION SCHEDULE HAS TWO NUMBERS |
| | FOR SPAN.THERE IS ONLY ONE SPAN.PLEASE REVISE. |
| | |
| | 2.)THE SHUTTER INSTALLATION SCHEDULE SPECIFIES 9" |
| | ANCHOR SPACING, BUT THIS IS ONLY FOR OPENINGS UP TO 5.5 |
| | FEET.CONFLICTING INFORMATION IS PROVIDED ON THE |
| | INSTALLATION SCHEDULE, SPANS NOT CLEAR. |
| | |
| | 3.)TWO NUMBERS WERE PROVIDED FOR THE SHUTTER GLASS |
| | SEPARATION.ONLY ONE NUMBER IS POSSIBLE. |
| | |
| | 4.)3" MINIMUM EDGE DISTANCE IS SPECIFIED, BUT YOU'VE |
| | USED THE 2.5" EDGE DISTANCE CHART. |
| | |
| | 5.)TWO SETS OF ALL PERMIT DOCUMENTS REQUIRED. |
| | |
| | 6.)THREE DIFFERENT PRODUCT APPROVALS SUBMITTED FOR |
| | JELD WEN.PLEASE SUBMIT ONLY THE PRODUCT YOU ARE |
| | INSTALLING AND REMOVE THE UNNECESSARY PAPERWORK. |
| | PROVIDE THIS PRODUCT APPROVAL ON STANDARD PAPER |
| | (NEWSPRINT WAS PROVIDED, DOES NOT GO THROUGH THE |
| | SCANNING MACHINE). |
| | |
| | 7.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | IN ADDITION TO THE NOAS SUBMITTED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |