| Date |
Text |
| 2008-06-27 08:04:56 | REVISION DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | |
| | 1. SHTS P-2.3 & P-3.1 REQUIRE THE CITY PLACE STAMP ON |
| | ALL SHEETS PRIOR TO SUBMITTAL. THIS IS NOT A CITY WPB |
| | REQUIREMENT BUT A CITY PLACE REQUIREMENT. |
| | |
| | 2. SHT P-2.3 REVISION HISTORY IS INCOMPLETE. REVISIONS |
| | ONE AND TWO HAVE BEEN DELETED FROM THE REVISION INDEX. |
| | PLEASE SHOW ALL REVISIONS THAT WERE APPROVED |
| | PREVIOUSLY. SECTION 106.1.3.--REVISIONS SEVEN & |
| | EIGHT HAVE NOT BEEN FOUND ON THE SHEET. PLEASE CLARIFY |
| | & CORRELATE REVISION INDEX WITH REVISIONS TO PLANS. |
| | SECTION 106.1.1. |
| | |
| | 2. SHT P-3.1 REVISION HISTORY IS INCOMPLETE. REVISION |
| | HAS BEEN DELETED FROM THE REVISION INDEX. PLEASE SHOW |
| | ALL REVISIONS THAT WERE APPROVED PREVIOUSLY. SECTION |
| | 106.1.3.--REVISIONS SEVEN & EIGHT HAVE NOT BEEN |
| | FOUND ON THE SHEET.--REVISION TEN SHOWN ON THE PLAN |
| | IS NOT INDICATED ON THE REVISION INDEX. PLEASE CLARIFY |
| | & CORRELATE REVISION INDEX WITH REVISIONS TO PLANS. |
| | SECTION 106.1.1. |
| | |
| | 3. SHT P-3.1 SANITARY IS SHOWN CONNECTING TO EXISTING |
| | GREASE LINE. SANITARY SHALL CONNECT TO THE SANITARY |
| | RISER. SECTION 1003.1. |
| | |
| | 4. SHT P-3.1 INDICATE THE PIPE SIZE FOR THE P-7 FIXTURE |
| | FOR THE THREE COMPARTMENT SINK. TABLE 906.1. |
| | |
| | 5. SHT P-3.1 SHOW HOW THE GREASE LINES CONNECT TO THE |
| | RISER. AS SHOWN THEY DO NOT REFLECT THE FLOOR PLAN. |
| | SECTIONS 106.1.1 & 706. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |