Plan Review Notes
Plan Review Notes For Permit 07030523
Permit Number 07030523
Review Stop P
Sequence Number 6
Notes
Date Text
2008-03-19 14:37:12REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P-2.3 NO HAND WRITTEN CHANGES ON SIGNED, SEALED
 DATED PLANS. SECTION 106.1.3.--IDENTIFY RISERS FOR
 THE GREASE SYSTEM AND THE SANITARY SYSTEM AT THE END OF
 THE SYSTEMS PAST THE LAV IN THE WOMEN'S TOILET ROOM AND
 PAST THE MOP SINK ON THE GREASE SYSTEM BY THE WALK IN
 COOLER. SECTIONS 106.1.1 & 106.1.2.
  
 2. SHTS P-2.3 & P-3.1 THE TELEPHONE NUMBER FOR THE
 ENGINEERING FIRM IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.025. PLEASE SHOW
 REQUIRED PHONE NUMBER.
  
 3. SHT P-3.1 RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN. BOTH RISERS ARE INDICATED AS GREASE RISERS.--
 THE GREASE RISER FROM THE 2ND FLOOR DOES NOT CONNECT TO
 THE GREASE RISER.--FLOOR SINK P-7 IS NOT SHOWN FOR
 FIXTURE 13B.--THE OFFSET AT THE END OF THE GREASE
 SYSTEM PRIOR TO THE RISER TO THE SECOND FLOOR IS NOT
 INDICATED ON THE RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved